Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Similar documents
Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION Elster GmbH Edition 01.15

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 03.

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 06.

Safety. Operating instructions Filter module VMF Measuring orifice VMO Fine-adjusting valve VMV DANGER. Contents WARNING CAUTION

Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition 02.12

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition Edition 08.

Safety. Operating instructions Motorized valve for gas VK DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 06.

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Pressure switches for gas DG..H, DG..N Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 07.

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 04.

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Tightness controls TC 1 3 and TC 4

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Tightness control TC. Product brochure GB 3 Edition AGA

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Safety. Operating instructions. White meters BK V2 to BK V12. (component of a diaphragm gas meter) DANGER. Contents WARNING CAUTION

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

OPERATING INSTRUCTIONS

GM-7000 Series CE Approved Gas Control Valve

Old documentation - Only for your information! Product is not available anymore!

Dual Solenoid Gas Valve Installation

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves single-stage atmospheric operating mode GB-(LEP) 057 D01

Old documentation - Only for your information! Product is not available any more!

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Integrated gas-air system GB-GD 057 D01

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 055 D01

Old documentation - Only for your information! Product is not available any more!

Type BBS-03, BBS-05, BBS-06, BBS-25

VMR VMR-OTN VMR 6 bar

Declaration of Conformity as per Directive 97/23/EC

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Safety 0 50 Please read and keep in a safe place Operating instructions Solenoid valve for gas VAS 1, double solenoid valve VCS 1

3G Operating instructions. Digital Purge Gas Valve 3G Type: Document no.: D0001 Version: 01. July 2011/Rev.

GM Series Dual-Block Multi-Function Gas Control Valves

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

EG15*... SERIES. SOLENOID GAS VALVES WITH 1/2 CONNECTION AND OPERATING PRESSURE UP TO 500 mbar DESCRIPTION

Compact pressure switches for gas and air

Safety. Operating instructions Burners for gas ZIO 165, ZIO 200 DANGER. Contents WARNING CAUTION Edition 11.11

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

SPECIFICATIONS ATTENTION

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

VGD40.../VGD41... Double gas valves. Building Technologies Division Infrastructure & Cities Sector

GM-7000 Series CE Approved Gas Control Valve

BGC258 Series BASOTROL Gas Valve

Safety DANGER WARNING CAUTION. Contents. Changes to edition Elster GmbH Edition Please read and keep in a safe place

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP

Solenoid valves VZWF, force pilot operated

Operating Manual VSA100A. tina29e1 ( )

Proportional pressure regulators VPPE

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

VGF... VGH... Building Technologies Division Infrastructure & Cities Sector VGG... VGF... VGH...

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

WhirlWind Combined fully integrated gas/air control and safety system GB-WND 055 D01

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

Type 2080 FALTENBALGVENTIL BELLOWS VALVE VANNE A SOUFFLET. Operating Instructions. Bedienungsanleitung Manuel d utilisation

Mounting and Operating Instructions EB 2555 EN. Self-operated Pressure Regulators. Pressure Reducing Valves Type 50 ES Type 50 EM.

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S06*

Gas Pressure Regulator HON 300

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Double valves for biogases and recycling gases

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Declaration of Conformity as per Directive 97/23/EC

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

Type /2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G96 Series BASOTROL Dual Operator Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

3-Way Safety Block DSV

2-port and 3-port valves PN 16

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

Double gas valves for biogases and recycling gases

Safety Relief Valve HON 832

Transcription:

2 Elster GmbH Edition. Translation from the German 22 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Solenoid valve for gas G / G Contents Solenoid valve for gas G / G.... Contents... Safety.... Checking the usage...2 Intended use...2 Type code...2 Part designations...2 Type label....2 Installation...2 Wiring... Tightness test... Commissioning.... Setting the flow rate... Setting the start gas rate... Replacing the solenoid actuator... Replacing a defective damping unit.... Maintenance... Assistance in the event of malfunction... Technical data... Designed lifetime... Logistics...8 Certification...8 Declaration of conformity...8 Approval for Australia...8 Eurasian Customs Union...8 Contact...8 Safety Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com. Explanation of symbols,,,... = Action = Instruction Liability We will not be held liable for damage resulting from non-observance of the instructions and non-compliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. CAUTION Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Changes to edition. The following chapters have been changed: Installation Certification -

Checking the usage Intended use Gas solenoid valve for safeguarding gas or air on various appliances. This function is only guaranteed when used within the specified limits see page (Technical data). Any other use is considered as non-compliant. WARNING Cleaning work on the solenoid actuator may not be performed using high pressure and/or chemical cleaning agents. This can cause moisture to get into the solenoid actuator and may lead to a dangerous failure. Type code Code Description G Gas solenoid valve / Nominal size R Rp internal thread F Flange to ISO 2 p u max. 2 mbar p u max. mbar p u max. bar 8 p u max..8 bar L Slow opening, quick closing N T Q K Quick opening, quick closing Mains voltage: 22/2 AC, / Hz Mains voltage: 2 AC, / Hz Mains voltage: 2 DC Terminal connection box, IP Screw plug at the inlet Screw plug at the inlet and outlet D With flow adjustment M Suitable for biologically produced methane iton valve disc seal Z With rolling diaphragm Part designations 2 Housing 2 Solenoid actuator Connection box Damping unit Screw plug for inlet pressure p u Screw plug for outlet pressure p d G / /2: hexagonal nut (actuator) G : cap 2-2 Type label Rated voltage, electrical power consumption, installation position, max. inlet pressure p u max., ambient temperature, enclosure and medium: see type label. Installation www.kromschroeder.com Osnabrück, Germany G CE - CM 88 CAUTION Please observe the following to ensure that the G is not damaged during installation and operation: Do not clamp the unit in a vice. Only secure the flange by holding the octagon with a suitable spanner. Risk of external leakage. Do not install or store the unit in the open air. Dropping the device can cause permanent damage. In this event, replace the entire device and associated modules before use. Check max. ambient temperature see type label. Check max. inlet pressure see type label. Installation position: black solenoid actuator in the vertical upright position or tilted up to the horizontal, not upside down. The housing must not be in contact with masonry. Minimum clearance 2 mm (.9"). > 2 mm Sealing material and dirt, e.g. thread cuttings, must not be allowed to get into the valve housing. Install a filter upstream of every system. Use approved sealing material only. Use a suitable spanner. Ensure that there is sufficient space for installation and adjustment. On G / /2, the inlet pressure p u can be measured at the pressure test point p u

G..R On G, the inlet pressure p u and the outlet pressure p d can be measured at the respective pressure test point. p u p d 2 Wiring WARNING Attention! Please observe the following to ensure that no damage occurs: Electric shocks can be fatal! Before working on possible live components, ensure the unit is disconnected from the power supply. The solenoid actuator heats up during operation. Surface temperature approx. 8 C (approx. 8 F) pursuant to EN -. Gas compression fittings The seals in some gas compression fittings are approved for temperatures of up to C (8 F). This temperature limit will not be exceeded if the flow through the pipe is at least m /h (. SCFH) of gas and the maximum ambient temperature is C (22 F). Use temperature-resistant cable (> 8 C/ F). Wiring to EN 2-. Disconnect the system from the electrical power supply. 2 Shut off the gas supply. The solenoid actuator can be rotated to allow it to be repositioned for electrical connection. On G..N, the hexagonal nut/cap on the solenoid actuator must be loosened for this. = N ( ) blue, 2 = L () black G..F 2 N L - Set the solenoid actuator to the correct position again and screw the hexagonal nut/cap tight if applicable. -

G with socket = N ( ), 2 = L () 9 After seconds, increase the text pressure to. x p u max.. 2, x p u max Tightness OK: open the pipeline. Unit leaking: remove the G and return it to the manufacturer. 8 Follow the reverse procedure when reassembling. Tightness test CAUTION Please observe the following to ensure that the G is not damaged during the tightness test: Check max. inlet pressure see type label. Test pressure. x max. inlet pressure. The tightness test procedure on G is functionally the same for all nominal sizes. The following figures apply to all G variants by way of example. Close the solenoid valve. 2 Shut off the gas supply. To be able to check the tightness, shut off the downstream pipeline as close as possible to the valve. Checking for external tightness, x p u max. Open the solenoid valve., x pu max. Commissioning Setting the flow rate At the factory, the gas solenoid valve is adjusted for maximum flow rate. G / /2 The minimum and maximum flow rates can be set within half a turn. G The minimum and maximum flow rates can be set within 2 turns. - Setting the start gas rate The start gas rate can be set with a maximum of turns. G..L ~ mm Start p u 2 Pipeline leaking: check the seal. Checking for internal tightness Close the solenoid valve. 8 ca. mbar -

- Replacing the solenoid actuator We recommend replacing the entire actuator set when replacing the solenoid actuator. The actuator set is available separately as a spare part. Disconnect the system from the electrical power supply. 2 Shut off the gas supply. G..N To be able to remove the solenoid actuator, loosen the hexagonal nut/cap on the solenoid actuator. Slide the O-ring approx. mm up. Can be rotated max. x. Adjust the start gas rate. 8 9 8 2, x p u max 9 N L - = N (-) bue 2 = L () black Screw the solenoid actuator into place. 2 Release the gas supply. G..L 2 Tightness OK: release the gas supply. Replacing a defective damping unit Disconnect the system from the electrical power supply. 2 Shut off the gas supply. 8 9 2 N L - Slide the O-ring approx. mm up. = N (-) blue 2 = L () black We recommend replacing all parts from the spare parts kit. 8 Can be 8 rotated max. x. Adjust 9 the start gas rate. 9, x p u max, x p u max -

Maintenance CAUTION In order to ensure smooth operation: check the tightness and function of the G every year, or every six months if operated with biologically produced methane. Disconnect the system from the electrical power supply. 2 Shut off the gas supply. If the flow rate is correct, see page (Tightness test). If the flow rate has dropped, clean the strainer. G / /2 G 2 2 G / 8 2 9 8 2 9 ~ mm ~ mm ~ mm Follow the reverse procedure when reassembling. Checking tightness and function When the solenoid actuator is removed, the gas-filled space in the G is opened. Therefore, check for tightness once the actuator has been reinstalled., x p u max. In order to determine whether the G is tight and closes securely, check the internal and external tightness, see page (Tightness test). Check electrical installations in line with local regulations; pay particular attention to the PE wire. Assistance in the event of malfunction WARNING Electric shocks can be fatal! Before working on possible live components, ensure the unit is disconnected from the power supply. Fault-clearance must only be undertaken by authorized trained personnel. Unauthorized repairs or incorrect electrical connections can cause the solenoid valve to become defective. In this case, our warranty will be rendered void.? Fault! Cause Remedy? The solenoid valve does not open, there is no flow downstream of the solenoid valve.! There is no power 2 supply. Have wiring checked by authorized trained personnel.! Guiding elements bent. Incorrect handling when installing the unit. 2 2 Remove the unit and return it to the manufacturer. -

? The solenoid valve does not close securely, the flow downstream of the solenoid valve does not stop.! alve seat is dirty. Clean the valve seat, see page (Maintenance). Install a filter upstream of the solenoid valve.! alve seat is damaged. Remove the unit and return it to the manufacturer.! alve seal is damaged or hardened. Remove the unit and return it to the manufacturer.! Guiding elements bent. Incorrect handling when installing the unit. Power consumption: oltage 2 DC Type 2 AC 2 AC 22 AC G 2 A / W 8 A / W G /2R8 A / W A / W G 2, G 2, G /2 A / W 2 A / W G A / W 8 A / W G, G 8 A / W 99 A / W Switching frequency: max. /min. alve housing: aluminium. alve disc: NBR. Internal thread: Rp to ISO -. Flange: ISO (DN to DI), PN. Air flow rate. (Q) for pressure loss Δp = mbar. p = mbar Remove the unit and return it to the manufacturer. Technical data Gas types: natural gas, town gas, LPG (gaseous), biologically produced methane (max.. %-byvol. H 2 S, G..M only) or clean air; other gases on request. The gas must be dry in all temperature conditions and must not contain condensate. Max. inlet pressure p u : see type label. Opening time: G..N: quick opening, s. G..L: slow opening, s. Closing time: G..N, G..L: s. Ambient temperature: -2 to C ( to F). No condensation permitted. Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life (please contact manufacturer). Storage temperature: -2 to C (8 to F). Safety valve: Class A, Group 2 pursuant to EN. Mains voltage: 22/2 AC, /-%, / Hz, 2 AC, /-%, / Hz, 2 DC, /-%. Electrical connection of G / /2: plug with socket to EN -8, cable gland: PG, connection terminal: 2. mm 2. Electrical connection of G : plug with socket to EN -8, cable gland: PG., connection terminal: 2. mm 2. Enclosure: IP. Duty cycle: %. Power factor of the solenoid coil: cos φ =.. (Q) [m /h] G /. G.8 G /2 2. G 2 8. G 2. G 2/.8 G /2 8.. (Q) [m /h] G 2. G /. G. G /9 2. G / 8. G. G /9. G 8 8. G. Designed lifetime This information on the designed lifetime is based on using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safety-relevant products must be replaced. Designed lifetime (based on date of manufacture) in accordance with EN for G: Designed lifetime Type Switching cycles Time [years] G / 2 2, G /2, G 8, G, -

You can find further explanations in the applicable rules and regulations and on the afecor website (www.afecor.org). This procedure applies to heating systems. For thermoprocessing equipment, observe local regulations. The production is subject to the surveillance procedure pursuant to Directive 29/2/EC Annex II paragraph (valid until 2 April 28) and to Regulation (EU) 2/2 Annex III paragraph (valid from 2 April 28). Elster GmbH Logistics Transport Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page 2 (Part designations). Report any transport damage immediately. Storage Store the product in a dry and clean place. Storage temperature: see page (Technical data). Storage time: months in the original packaging before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time. Packaging The packaging material is to be disposed of in accordance with local regulations. Disposal Components are to be disposed Scan of the Declaration of conformity (D, ) see www.docuthek.com Approval for Australia AGA Australian Gas Association, Approval No.: 98 www.aga.asn.au/product_directory Eurasian Customs Union The product G meets the technical specifications of the Eurasian Customs Union. Certification Declaration of conformity We, the manufacturer, hereby declare that the product G, marked with product ID No. CE-BL, and valves G for high pressures (.8 bar), marked with product ID No. CE-CM88, comply with the requirements of the listed Directives. Directives: 29/2/EC GAD (valid until 2 April 28) 2//EU 2//EU Regulation: (EU) 2/2 GAR (valid from 2 April 28) The relevant product corresponds to the tested type sample. Contact If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from Elster GmbH. We reserve the right to make technical modifications in the interests of progress. -8 Elster GmbH Strotheweg, D-9 Lotte (Büren) Tel. 9 2- Fax 9 2- hts.lotte@honeywell.com, www.kromschroeder.com