HEATEC TEC-NOTE Publication No Revised

Similar documents
HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

OC Panel High Limit Aquastat Kit, Manual Reset p/n

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

WATER CONTROL SYSTEM QUICK START

Preferred Instruments Danbury, CT USA

VTL VFL VCL. Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS

Bante821 Portable Dissolved Oxygen Meter Instruction Manual

Air Eliminators and Combination Air Eliminators Strainers

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

Bante810 Benchtop Dissolved Oxygen Meter Instruction Manual

ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION

BI-680 Online Dissolved Oxygen Controller Instruction Manual

Armfield Distillation Column Operation Guidelines

SCOPE OF THIS GUIDE STARTING-UP. 1 Check mini CORI-FLOW functional properties

Model DE-1, VDE-1 and DE-2 Air Release Heads

Operating Instructions VEGAPULS 66

The HumiSys. RH Generator. Operation. Applications. Designed, built, and supported by InstruQuest Inc.

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

NORMAL OPERATING PROCEDURES Operating Parameter Information

FAULT CODE TROUBLESHOOTING INDEX

TANKTRONIC. STANDARD CONFIGURATION Single Tank. ADVANCED CONFIGURATION Multiple Tanks. Twin Tank (common valve) Twin Tank (separate valves) Vent box

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

Level MEASUREMENT 1/2016

Bante820 Portable Dissolved Oxygen Meter Instruction Manual

OxyScan Graphic. Operating Instructions. UMS Micro-oxygen sensor 501. Microprocessor instrument

MP15 Jockey Pump Controller

A TECHNICAL REFERENCE

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Operating Instructions. Ball valve fitting according to ZB For pressure transmitter VEGABAR 82. Document ID: 50027

Gas Module for Series GMS800

Product information. Capacitive. Level detection in liquid VEGACAP 62 VEGACAP 63 VEGACAP 64 VEGACAP 66 VEGACAP 69. Document ID: 29983

Instruction Manual VCG-6

How to specify a product. Process Sensors and Mechanical Instruments

DOscan10 Pocket Dissolved Oxygen Tester Instruction Manual

Cover Page for Lab Report Group Portion. Head Losses in Pipes

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

AUTOMATIC HOSE TEST UNIT, TYPE SPU

955730_1 4/17/18. FlowSense Operator s Guide For Gen2 20/20 SeedSense Displays

Operating instructions Binary level sensor LI / / 2013

The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions

Royce Interface Level Analyzer and Sensors

American Weigh Scales, Inc. BLADE Series D i g i t a l P o c k e t S c a l e BLADE-550. User Manual BLADE-400 BLADE-1000

5 Function Indicator. Outside Air Temperature (C) Outside Air Temperature (F) Pressure Altitude Density Altitude Aircraft Voltage STD TEMP SL 15000

Operation manual Level sensor DC-LS-50 Operation Manual Level Sensor DC-LS-50

DOMESTIC HOT WATER TEMPERATURE CONTROL with SAFEGUARD

PTG100 Precision Test Gauge

The Discussion of this exercise covers the following points:

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

Model : LMW-9620 Please read this manual carefully before using the instrument Labnics Equipment

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

RGC-IR Remote Gas Calibrator for IR400

SDX Submersible Depth Transmitter User Manual

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Bubble Tube Installations

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions.

PX3005. Rangeable Industrial Pressure Transmitter M-5721/1018

Pneumatic high-pressure controller Model CPC7000

FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL

O2100C Oxygen Measurement Module Technical Use Notes do not use other wall adapters with the O2100Cmodule. 10% / V 5% / V 2% / V 1% / V 10% / V

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments

DTG - LCD Digital Temperature Gauge USER MANUAL

NIV EAU MATIC ST User Manual Made in Canada

Pressure maintenance valve SDV-P / SDV-P-E

Owners Manual Release Date: Thursday, December 29, 2011

Best Practice for Calibrating LTH Conductivity Instruments

HBLT-A1 LIQUID LEVEL SENSOR

User Manual for the Mars Calibration Bench

RAM 4021-DPX Operation Manual

Operating instructions Capacitive sensors KG AC (M18) / / 2010

Sterisil Ac+ Installation & Operating Manual

300C/ 800C/ 990C Plus Series

Simple Set. Pressure Independent Control Valves 2 Way 1/2-2

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

Level, Pressure, and Density Instrumentation for the Petrochemical Industry

T EK-SUB 4800C 19 mm Submersible Level Transmitter

SDX Submersible Depth Transmitter User Manual

RAM 4021 Operation Manual

#LZ400 LEAKALYZER. Water Loss Sensor INSTRUCTION MANUAL Country Dr. #190 St. Paul, MN

WIKA INSTRUMENT CORPORATION

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)

Installation Instructions

Electro Controls. Level WattsIndustries.co.uk

TRANSDUCER KIT 2 INSTALLATION INSTRUCTIONS

PM105 PRESSURE METER USER S MANUAL

Calibration Procedure

ASME and PED Requirements for Drum Level Instrumentation. Presented by: Amir Hedayatnia Clark-Reliance Corp.

Manual for continuous distillation

Troubleshooting Guide: 640 Pediatric Exam Table with Midmark Scale

Quick Installation Guide Doc nr.: C Date:

Rate of Flow Valve Series 120

Pneumatic high-pressure controller Model CPC7000

ASE SOLVENT CONTROLLER INSTALLATION INSTRUCTIONS Dionex Corporation

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

BACK PRESSURE / SUSTAINING

SSI Solaris 150 RTA Revision /27/2016 Page 1 of 9. SSI Solaris 150 RTA

ABB MEASUREMENT & ANALYTICS DATA SHEET. WaterMaster FEW530 Electromagnetic water meter

Transcription:

HEATEC TEC-NOTE Revised 6-17-10 Setting up Vega radar sensors for Heatec vertical asphalt tanks This document provides information for setting up Vega radar sensors installed on Heatec tanks that store liquid asphalt (Figure 1). It applies to VEGA PULS 63.UX (Figure 2) and PULS 65.UX sensors with Indicating and Adjustment Module PLICSCOM (Figure 3). It applies to Heatec vertical tanks with capacities ranging from 10,000 to 35,000 gallons. The sensors are optional equipment for Heatec tanks. The sensors indicate levels of asphalt in the tanks. Levels are shown in feet, measured from the bottom of the tank. This document is furnished with Heatec vertical tanks equipped with the sensor. Applicable operating instructions, published by Vega are also furnished. Both documents are needed to set up the radar sensors for Heatec tanks. The sensors require a preliminary setup and a final setup. The preliminary setup is normally done at the Heatec factory. The final setup should be done in the field after the tank is operational. If a new sensor is installed in the field, and the preliminary setup was not done at Heatec, it must be done before final setup can be done. Figure 2. VEGA PULS 63.UX radar sensor. Figure 1. Heatec vertical asphalt tanks. Figure 3. PLICSCOM indicating and adjustment module.

NOTICE This document supplements the Vega manual and should always be used along with the Vega manual. Be sure to read all appropriate warnings and precautions in the Vega manual before doing any work on Vega sensors. The following statement appears in the Vega manual and should be followed: Authorized personnel All operations described in this operating instructions manual must be carried out only by trained and authorized specialist personnel. For safety and warranty reasons, any internal work on the instruments must be carried out only by VEGA personnel. PRELIMINARY SETUP The preliminary setup can be made either before the sensor is installed on the tank or after it is installed. Use the buttons on the PLICSCOM module (Figure 3) to make the settings. Set the sensor according to the settings shown in Figure 4. Do not change any settings other than the ones shown in Figure 4. These are the settings we use for preliminary setup of the sensors at the Heatec factory. They are the only settings we change from the original Vega factory settings. HINT: Before trying to set the PLICSCOM module, be sure to get familiar with its four keys (refer to applicable instructions in the Vega manual). When navigating the menu on the module of the sensor, make sure the menu numbers (which appear in the upper right-hand corner of the display) match the menu numbers shown in Figure 4. The menu terminology shown in Figure 4 should match the menu terminology that appears on the PLICSCOM module. NOTE: Please disregard any minor differences in terminology shown in Vega manuals and the terminology that appears in the display of the PLICSCOM module. These differences should not affect your setup procedure. FINAL SETUP Final setup of the sensor can only be done after the sensor is installed in the tank. During final setup the sensor creates an electronic profile of the inside Page 2 of the tank. It senses obstructions, such as ladders, mixing blades, etc. It stores the profile in memory and uses it to eliminate false echoes from those components. This procedure is known as False echo memory. We normally run the false echo memory procedure on empty tanks equipped with sensors at the Heatec factory. At that time the tanks are new and have never been filled with asphalt. The profile we create should enable the sensor to provide fairly stable and accurate indications of level. However, the sensor will provide greater stability and accuracy if the procedure is repeated after the inside of the tank is coated with asphalt. The sensor can be set to update the profile that was originally made at Heatec. We recommend that you update the profile after the tank has been used for a while. Do this when the asphalt level is barely above the heating coils or at the lowest level before you would normally refill the tank. If the tank has a mixer, make sure it is running while performing this procedure. Basic instructions for creating false echo profiles are in the Vega manual. Here s how to build an accurate profile: Set the sensor module to menu 4.1 False echo memory. You will see the word: Change? Press the OK button and you will be presented with three choices: Delete, Update, Create new. Be sure to choose update. Otherwise, you will delete the profile that was created at Heatec. NOTE: While you are running the false echo memory procedure you will be prompted to enter the distance from the sensor to the surface of the asphalt. So, be prepared to make actual measurements through the manway in the top of the tank. You will need to measure from the surface of the asphalt to the mounting flange of the sensor. TROUBLESHOOTING The sensor may show erroneous readings if its antenna becomes contaminated with asphalt residues. If this happens you must remove the sensor unit and clean the antenna using a solvent

that will dissolve asphalt. Before removing the sensor be absolutely sure to mark its position so it can be reinstalled in the same position. Otherwise, all of the false echo memory information will be useless and the sensor will not function properly. Note: The sensor has a small hole drilled in the side of its stainless steel body. This hole should always point towards the center of the tank. REVISIONS TO SETTINGS IN FIGURE 4 Over the years we have revised the settings shown in Figure 4 because we have found that some work better than others for asphalt storage tanks. The settings we now recommend are shown in Figure 4. If your unit is new, make sure its settings match those shown in Figure 4. However, if you have an older unit that has been in service for quite a while and it is working well, there is no need to change its settings. EFFECT ON CONTROLLERS The settings shown in Figure 4 are coordinated with settings of the controller used with the radar unit. Be sure to check controller settings to make sure they agree with radar unit settings in Figure 4. Otherwise, level indications will be erroneous and shutoff control will not work properly! See Heatec Tec-Note 6-10-236 Setting Yokogawa UT150 controller used with Heatec vertical asphalt tanks or Tec-Note 5-04-120 Setting SENSOR MENU Figure 4. Settings for VEGA PULS 63 and PULS 65 with Indicating and Adjustment Module PLICSCOM HEATEC VERTICAL TANKS TAV-10 TAV-15 TAV-20 TAV-25 TAV-30 TAV-35 1 Basic Adjustment 1.1 Min. adjustment 16 06 2/16 24 06 2/16 30 06 2/16 38 06 2/16 44 06 2/16 50 06 2/16 1.2 Max. adjustment 1.3 Medium Unknown Unknown Unknown Unknown Unknown Unknown 1.4 Vessel type Stirred Vessel Stirred Vessel Stirred Vessel Stirred Vessel Stirred Vessel Stirred Vessel 1.5 Damping 0 s 0 s 0 s 0 s 0 s 0 s 1.6 Linearization curve Linear Linear Linear Linear Linear Linear 1.7 Sensor-tag Sensor Sensor Sensor Sensor Sensor Sensor 2 Display 2.1 Display value Height Height Height Height Height Height 4 Service 4.3 Current output Output mode Failure mode Min. current 4.6 Select ft (d) ft (d) ft (d) ft (d) ft (d) ft (d) Page 3

Honeywell controller used with Heatec vertical asphalt tanks. SPECIAL SETTINGS All of the current VEGA radar units used on Heatec AC tanks have special factory settings. These settings can only be made using a computer loaded with special Vega software and a special connect cable. These settings cannot be made using the keys on the PLICSCOM module. One of the special settings is known as SECURITY. Prior to September 2004 it was set to ON. The advantage of having this setting turned on, is that the unit provides better control of tank overflow. However, having this setting activated can create a problem in an environment where there is condensation of moisture and vapors. If condensation accumulates on the radar antenna it can keep the radar unit from working properly. This may occur inside an asphalt tank. will shut off the unloading pump when filling the tank and the float activates the proximity switch. An indicator light labeled HIGH ASPHALT FLOAT LEVEL (at the unloading pump controls) comes on when the proximity switch has been activated. For more information on shutoff controls please refer to Heatec Tec-Note 9-04-147 Heatec asphalt tanks maintenance. In normal operation the radar shuts off the unloading pump before the proximity switch is activated. Thus, if the proximity switch shuts off the unloading pump it means that the radar is not working properly. So every time you fill the tank pay special attention to whether the indicator light for high float level comes on. If it does come on, this indicates that the radar failed to shutoff the unloading pump and the shutoff was achieved only by the backup system. Accordingly, radar units used on Heatec AC tanks starting September 2004 have the SECURITY setting set to OFF. This should eliminate possible problems due to condensation. If your Heatec tank uses a radar unit that has settings made prior to September 2004 and you think you may be experiencing problems due to condensation, please contact the Heatec service department. NOTE: The Vega software is designed primarily for use by original equipment manufacturers (OEMs) such as Heatec. It is not recommended for end users. OVERFLOW PROTECTION Turning off the SECURITY setting does not leave the radar without overflow protection. However, it could make the radar overflow control more susceptible to problems if the radar antenna is accidentally immersed in asphalt. In any case, a backup system will prevent overflow if the radar is not working properly. The backup system consists of a proximity switch activated by a float (Figure. 5 and 6). The proximity switch Figure 5. High-level proximity switch and float pipe protruding through sleeve in top of tank. Page 4

The settings shown in Figure 4 cause the radar to shut off the unloading pump when the liquid reaches a level approximately 18-5/8 inches below the bottom surface of the upper bulkhead inside the tank. At this level the asphalt will be 38-1/8 inches from the bottom surface of the flange of the radar unit. This is the surface from which all radar measurements are made. The proximity switch and float system is set up to shut off the unloading pump when the level of asphalt is approximately 7-1/8 inches from the bottom surface of the upper bulkhead Figure 6. Float for high-level proximity switch. If the radar fails to shut off the unloading pump the most likely cause is that the radar antenna was accidentally immersed in asphalt. This should not happen in normal operation. Cleaning the radar antenna should restore the radar unit to normal operation. In the unlikely event that both the radar and proximity switch fails to shut off the unloading pump, the asphalt level will reach the top of the vent/overflow pipe inside the tank. It will then spill into the pipe, which will carry it out of the tank onto the ground at the bottom of the tank. Moreover, if an overflow occurs, you can be sure that the asphalt level was high enough to immerse the radar antenna. RESERVED SPACE Some space in the top of the tank is reserved to allow for expansion of asphalt and for overflow control when filling the tank. So you should not expect to fill the entire space inside a tank with asphalt. Your volume of asphalt will always be somewhat less than the volume of the tank. OLDER TANKS Certain dimensions on vertical tanks manufactured prior to 2001 may differ from those on tanks manufactured after that year. If a radar unit is being retrofitted to a vertical tank manufactured prior to 2001 you may need to use different radar settings than those shown in Figure 4. Otherwise the level indications may be incorrect. Please contact Heatec service department for help. TECHNICAL SUPPORT For questions about sensor settings for Heatec tanks, please contact the Heatec service dept, phone 423-821-5200. Please have the model of your sensor. If your sensor was installed at the Heatec factory, please have the Heatec job number. If you need a manual for the VEGA PLICSCOM sensor you can download one from heatec.com/ literature/tec-notes/actank_pubs.htm. For problems with the sensor, please contact Ohmart/Vega Customer Support at 1-800-367-5383 or 1-800-543-8668. Please have sensor model. Before calling, please verify that your settings match those shown in Figure 4. Heatec, Inc. 5200 Wilson Road Chattanooga, Tennessee 37410 www.heatec.com (423) 821-5200 (800) 235-5200 Fax (423) 821-7673 2010 Heatec, Inc. Page 5