Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

Similar documents
Dri-Line Mk3 Monnier Compressed Air Drain Trap

DF1 and DF2 Diffusers

TSS21 Sealed Thermostatic Steam Tracer Trap

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

MF2M Monnier Miniature Compressed Air Filter

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

TP1 and TP2 Temporary Cone Shaped Strainers

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

ML3M Monnier Miniature Compressed Air Lubricator

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

PV4 and PV6 Piston Valves

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

CP10 Sensor Installation and Maintenance Instructions

AVC32 Carbon Steel Air Vent for Steam Systems

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

APT14, APT14HC and APT14SHC Spares 2

AVM7 Stainless Steel Thermostatic Air Vent

FV Flash Vessel Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

CVS10 Sanitary Check Valves

Manual Actuated Boiler Blowdown Valves

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

CA44, CA44S, CA46 and CA46S Air and Gas Traps

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

DCV6 Disc Check Valve

Spirax Compact FREME Flash Recovery Energy Management Equipment

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

TW Temperature Control Valve

BCV31 DN40 - Blowdown Control Valve

S and SF Inverted Bucket Steam Traps

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

SRV66 Sanitary Pressure Reducing Valve

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

BPT13 Balanced Pressure Thermostatic Steam Traps

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

CS10-1 Stainless Steel Clean Steam Separator

BRV71 and BRV73 Pressure Reducing Valves

PC10HP Pipeline Connector (ASME 600)

SRV2S Pressure Reducing Valve

BCV31 DN20 - Blowdown Control Valve

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

MFP14-PPU (Vented) Automatic Packaged Pump Units

CA10S, CA14 and CA14S Air and Gas Traps

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

BDV1 and BDV2 Blowdown / Depressurisation Valves

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

Vane Flow Switches Colima FLU Series

SCA Series Inverted Bucket Steam Traps

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

QuickHeat TM Packaged Heat Exchanger Solutions

Thermocirc Installation and Maintenance Instructions

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

M111 Spiraflo Transducer

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

BDV60 Blowdown Vessel Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

Colima TOR Magnetic Level Switches

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BCVi43 Blowdown Control Valve

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

IP2, IP2A and IP2D. Spirax-Monnier International Compressed Air Filter/ Regulators

Transcription:

0509950/2 IM-P050-21 CH Issue 2 Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and operation 4. Spare parts and maintenance IM-P050-21 Printed in the CH UK Issue 2 Copyright 2009 1

1. Safety information Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/ application. The product complies with the requirements of the European Pressure Equipment Directive 97/23/EC and falls within the category 'SEP'. It should be noted that products within this category are required by the Directive not to carry the mark. i) This product has been specifically designed for use on compressed air, which is in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 2 IM-P050-21 CH Issue 2

1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 90 C (194 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). IM-P050-21 CH Issue 2 3

1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 IM-P050-21 CH Issue 2

2. General product information 2.1 General description The Spirax-Monnier Dri-Line Mk2 is a float operated compressed air condensate drain trap. It is designed for use on systems up to 16 bar g. Principal features: - Black epoxy finish - internal and external. - Discharge can be piped to drain. - Built-in strainer screen. - High discharge capacity. - Blast action discharge. or 1 3 2 Fig. 1 Dri-Line Mk2 Spirax-Monnier compressed air drain trap 2.2 Sizes and pipe connections ½" screwed BSP (BS 21 - Rp). 4 6 mm push-in fitting 4 Autodrain mechanism 2.3 Operating limits Maximum working pressure Minimum operating pressure 16 bar g 0.1 bar g Maximum working temperature 80 C Maximum discharge capacity 2.4 Materials No. Part 20 L/h @ 6 bar Material 1 Body Epoxy coated aluminium LM25WP 2 Autodrain mechanism Acetal plastic / nickel plated brass 3 Strainer screen 0.8 mm perforated 316L 4 'O' rings Nitrile IM-P050-21 CH Issue 2 5

3. Installation and operation Note: Before actioning any installation observe the Safety information in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended application. 3.1 Dimensions / weights (approximate) in mm and kg Size A B C D E F G Weight ½" 90 57 146 30 80 75 6 mm PIF 0.46 D A 6 C E G F B E = Withdrawal distance for bottom cap F = Withdrawal distance for strainer screen Fig. 2 Dri-line Mk2 dimensional drawing 3.2 Installation: - The Dri-Line Mk2 should be fitted with the inlet port (top or side entry) at the top, so that the float mechanism can rise and fall vertically. Please note: The unit is supplied ready for top entry installation. To change the inlet to side entry for connection to pipework, unscrew the ½" socket pipe plug (6), and re-use it to seal the top connection. - Adequate space should be provided around the unit to allow easy access for routine maintenance requirements (see Figure 2 for withdrawal distances). - Connect the unit so that the airflow is in the direction indicated by the arrow on the body. - The unit should be installed as close as possible to the equipment it is serving. 6 IM-P050-21 CH Issue 2

3.3 Typical installations 6 Self-venting ball valve " minimum diameter Fig. 3 Dri-Line Mk2 draining a receiver or larger filter " minimum diameter Self-venting ball valve Fig. 4 Dri-Line Mk2 draining a compressed air main relay point " minimum diameter Self-venting ball valve Fig. 5 Dri-Line Mk2 draining a separator on a compressed air main 3.4 Operation The Spirax-Monnier Dri-Line Mk2 is a selfacting device. To activate manual override, twist the lowermost part of the mechanism anticlockwise from O to I. Drain operation Pressure to close drain: Greater than 0.3 bar g. Pressure to open drain: Less than 0.2 bar g. Minimum air flow to close drain: 0.6 dm³/s Fig. 6 IM-P050-21 CH Issue 2 7

4. Spare parts and maintenance 4.1 Spare parts The spare parts available are shown in solid outline. Parts drawn in broken line are not supplied as spares. Available spares Internal autodrain sub-assembly Strainer screen Strainer cap 'O' ring (packet of 3) Discharge tube adaptor (Optional extra - not shown) A, C, D, W V X 4.2 Maintenance Note: Before actioning any maintenance observe the 'Safety information' in Section 1. - Isolate and vent the unit from the system pressure (preferably using a self-venting ball valve). - The unit can be dismantled in-situ for either servicing / maintenance, or removed completely from the air system. 4.2.1 How to clean or replace the strainer screen (V): - Unscrew the strainer cap (G) using a " A/F spanner and remove the strainer screen from the body. - Clean or replace the strainer screen (V) and refit. Fit a new 'O' ring (X). Tighten the strainer cap (G) to 10 N m. 4.2.2 How to clean or replace the autodrain mechanism: - Unscrew the bottom cap (D using the special tool available from Spirax Sarco) and remove the autodrain mechanism. - Unscrew the locking ring (C). - Clean the screen (F) using soap and water. Do not attempt to dismantle the autodrain mechanism (A) as it is a non-servicable item. - Refit or replace the autodrain mechanism (A) and hand tighten using the locking ring (C). - Please note that the silicone free nitrile rubber gasket (B) is a non-replaceable item. - Insert the bottom cap (D) complete with autodrain mechanism (A) into the body using a new 'O' ring (W) and tighten to 15 N m. A "- 18UNF-2A 13 mm A/F hexagon Fig. 7 Dri-Line Mk2 spares drawing B V X G W D C 8 IM-P050-21 CH Issue 2