Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 06.

Similar documents
Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 03.

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition 02.12

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition Edition 08.

Safety. Operating instructions Filter module VMF Measuring orifice VMO Fine-adjusting valve VMV DANGER. Contents WARNING CAUTION

Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION Elster GmbH Edition 01.15

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Motorized valve for gas VK DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 06.

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Pressure switches for gas DG..H, DG..N Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions. White meters BK V2 to BK V12. (component of a diaphragm gas meter) DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 07.

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 04.

Tightness control TC. Product brochure GB 3 Edition AGA

OPERATING INSTRUCTIONS

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

Type 2080 FALTENBALGVENTIL BELLOWS VALVE VANNE A SOUFFLET. Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Tightness controls TC 1 3 and TC 4

Type BBS-03, BBS-05, BBS-06, BBS-25

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

VGD40.../VGD41... Double gas valves. Building Technologies Division Infrastructure & Cities Sector

Type /2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

SAV. Safety Shut-off Valve. Safety Shut-off Valve Type SAV

Safety. Operating instructions Burners for gas ZIO 165, ZIO 200 DANGER. Contents WARNING CAUTION Edition 11.11

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

VGF... VGH... Building Technologies Division Infrastructure & Cities Sector VGG... VGF... VGH...

Safety Relief Valve HON 832

Safety. Operating instructions Diaphragm gas meters BK-G1.6 to BK-G25 DANGER. Contents WARNING CAUTION. Changes to edition 11.13

Gas Pressure Regulator R 51

Declaration of Conformity as per Directive 97/23/EC

Gas plug-in hose, straight-through form. Instructions for Use. suitable for gas socket model G2019T, G2016T. G2023 from 01/1990.

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. AWA Change-over Valve

Double valves for biogases and recycling gases

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Safety valves. Component-tested safety valves DN Compressed Air Accessories II Hoses, valves etc. 15. Technical data. Exhaust capacity air

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

Ball valve. Operating instructions for series. Version BA Print-No TR MA DE Rev001

SV5 Safety Valve Installation and Maintenance Instructions

CAST IRON SAFETY VALVE TYPE 6301

G type DUCTED EXHAUST SAFETY VALVE 2871 AND 288X SERIES. Model/Ref:

Safety Shut-Off Valve HON 720

Contents. 1. General information BROEN BALLOMAX Steel Ball Valves Approvals Quality Management...2

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

Two-port valves, male threaded, PN25

PSG 901. Pressure Switch for Gas. elektrogas.com EE141-07/12

Double gas valves for biogases and recycling gases

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Safety shut-off valve S 100. Product information

Peak Pressure Indicator MSI-3

Neotecha SAPRO - Aseptic sampling valve SV Installation, operation and maintenance instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Safety shut-off valve S 50. Product information

3-port seat valves with externally threaded connection, PN 16

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Ball valve HKSF-W100. Ball valve HKSF-W100. RMA Kehl GmbH & Co. KG Oststrasse 17 D Kehl / Germany

Flowmeter. Original operating manual DFM

Technical Information Ball valves for high pressure applications

3-Way Safety Block DSV

ATS430 turbidity sensor Retractable insertion assembly

Gas Pressure Regulator HON 300

Safety. Operating instructions Burners for gas BIO, BIOA DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

2-port and 3-port valves PN 16

2-port seat valves PN25 with externally threaded connections

Installation and Operating Instructions Bypass Flow Meter DST

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Straight-Way Valve with Packing Gland

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Manual Brass Shut-Off Valve DN10 through DN22

MV-01. Features. 2/2-way Solenoid Valve for Fluids. Description: Application:

safety Shut-Off Valve HON 721

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Overview of types. Technical data. Safety notes

Overflow valves Type OFV REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

Operating instructions Two-way / three-way valves for drinking water plants

Centrifugal Gas Separator ZGA. Operating Manual. Dimensions, weights and other technical data are subject to changes.

6-way characterised control valves DN15 / DN 20 / DN 25

Operating instructions - Translation of the original -

Safety shut-off valve Control Control Lock-up Over pressure set point Under pressure set point pressure range accuracy class

Seated valves VRB 3, VRG 3

GAS PRESSURE CONTROL UNIT TYPE 132

Gas Pressure Regulator HON 200

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Operating Manual FSV, FSÖV, SSVF

Valves for Biogases and Recycling Gases

Diaphragm Pressure Keeping Valve

ATEX installation and service instruction

Declaration of Conformity as per Directive 97/23/EC

Transcription:

06 Elster GmbH Edition 09.6 Translation from the German 33000 D F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Manual valves, flow adjusting cocks GEHV, GEH, LEH Contents Manual valves, flow adjusting cocks GEHV, GEH, LEH... Contents... Safety.... Checking the usage... Intended use... Type code... Part designations... Type label.... Installation... Tightness test...3 Maintenance...3 Technical data...3 Logistics...5 Certification...5 Declaration of conformity...5 Declaration of performance pursuant to annex III of Regulation (EU) No. 305/0... 6 Eurasian Customs Union...6 Contact...6 Safety Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com. Explanation of symbols,,,... = Action = Instruction Liability We will not be held liable for damage resulting from non-observance of the instructions and non-compliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. CAUTION Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Changes to edition 06.5 The following chapters have been changed: Technical data -

Checking the usage Intended use Manual valve is used for the manual shut-off of all gases to DVGW Code of Practice G 60/I and air. GEHV, GEH, LEH Flow adjusting cocks GEHV, GEH, LEH are used for precise flow rate adjustment. This function is only guaranteed when used within the specified limits see page 3 (Technical data). Any other use is considered as non-compliant. Type code Code Description Manual valve 6 50/00 Nominal size R Rp internal thread F Flange to ISO 7005 Max. inlet pressure 50 p u max. 5 bar 60 p u max. 6 bar B Brass housing S Steel housing M Stainless steel housing, suitable for biogas G Two-part housing, GGG 0, ball: cast steel C Two-part housing, GGG 0, ball: stainless steel K Short length Code Description GEHV Flow adjusting cock for gas and air GEH Flow adjusting cock for gas LEH Flow adjusting cock for air 8 50 Nominal size R Rp internal thread Max. inlet pressure 0 p u max. bar 0 p u max. bar 50 p u max. 5 bar Part designations 5 00F60C 5 50/00F60G 3 GEHV GEH 8 5 3 GEH 3 50 LEH with safety cap Type label Ambient temperature and max. inlet pressure, see type label. D-908 Osnabrück Installation 6 50R50B 5 50R60S, 5 50R60M CAUTION Please observe the following to ensure that the unit is not damaged during installation and operation: For gases which tend to form condensation, installation of a condensate drain is recommended. Do not clamp the unit in a vice. Risk of external leakage. Sealing material and dirt, e.g. thread cuttings, must not be allowed to get into the housing. -

Any installation position and flow direction. Install the unit in the pipe free of mechanical stress. Avoid subjecting the unit to shocks and vibrations. Use approved sealing material only. The device must not be in contact with masonry. Ensure that there is sufficient installation space and that the lever can be operated freely...r, GEHV, GEH, LEH Use the lever and hand wheel for shut-off or adjustment only. Tightness test The test procedure is the same for the threaded and flanged versions. Close the manual valve. N N,5 x p u max.,5 x p u max. 3 Open the manual valve. 0 0 0 N,5 x p u max...f..f60c-htb meets the requirement for internal tightness under increased thermal stress. CAUTION In the case of increased thermal stress, please observe the following: When installing, use high temperature resistant seals. GEH 3 Adjust the flow rate. Use an Allen key, screwdriver or spanner. LEH 3 Adjust the flow rate using the hand wheel. A safety cap is enclosed for locking the air flow setting. 5 6 Turn the safety cap as far as it will go. Maintenance The valves require little servicing. An annual function check is recommended. Technical data Media: all gases to DVGW Code of Practice G 60/I and air. 6 50R50B With internal thread to DIN 999. for gas p u max. : 5 bar, other media p u max. : 6 bar. for gas: -0 to +60 C, other media: -0 to +80 C. Housing: Ms 58, nickel-plated. Ball: Ms 58, chromium-plated. Stem: brass, nickel-plated. Stem seal: Viton O-rings. 5 50R60S, 5 50R60M With internal thread to DIN 999. for gas p u max. : 6 bar, other media p u max. : 6 bar. for gas: -0 to +60 C, other media: -0 to +80 C....S housing: cast steel.069, galvanized....m housing: stainless steel.08. Ball: stainless steel.08. Stem: stainless steel.0. Stem seal: PTFE/Viton. -3

5 00F60C Flanged connection to EN 09-, PN 6. Inlet pressure p u max. : 6 bar. for gas: -0 to +70 C, other media: -0 to +80 C. Housing: GGG 0. Ball: stainless steel.30. Stem: stainless steel.0. Stem seal: FKM (Viton). Housing flange seal: Perbunan. Up to PN, this series meets the requirements for high thermal capacity (HTR) as well as for internal tightness pursuant to DIN 3537-. 5 50/00F60G 50/00F60G: with bore reduced to DN 00. Flanged connection to EN 09-, PN 6. Inlet pressure p u max. : 6 bar. for gas: -0 to +60 C, other media: -0 to +80 C. Housing: GGG 0. Ball: cast steel GG 5. Stem: stainless steel. Stem seal: Viton. Housing flange seal: Perbunan. GEHV, GEH Gas type: natural gas, town gas, LPG (gaseous) and air. GEHV Connection: internal thread to DIN 999. for gas p u max. : 5 bar, for air p u max. : 5 bar. for gas: -0 to +60 C, for air: -0 to +90 C. Housing: CW 67 N (.00), nickel-plated. Ball: CW 67 N (.00), hard chromium-plated. Spindle seal: NBQ. Hand wheel: PA 6 polyamide. GEH 8 5R0 Connection: internal/external thread to DIN 999. for gas p u max. : bar, for air p u max. : bar. for gas: -5 to +60 C, for air: -5 to +60 C. Housing: Ms 58. Ball: Ms 58. Ball seal: O-ring, nitrile. Spindle seal: O-ring, nitrile. GEH 3 50R50 Connection: internal/external thread to DIN 999. for gas p u max. : 5 bar, for air p u max. : 6 bar. for gas: -0 to +60 C, for air: -0 to +0 C. Housing: Ms 58, nickel-plated. Ball: Ms 58, chromium-plated. Ball seal: PTFE. Spindle seal: O-rings, Viton. LEH Gas type: air. Connection: internal thread to DIN 999. Inlet pressure p u max. : bar. 0 to 0 C. Housing: pressed brass. Seal: gland. Storage temperature (for all): -0 to +0 C. Designed lifetime This information on the designed lifetime is based on using the product in accordance with these operating instructions. Once the designed lifetime has been reached, safetyrelevant products must be replaced. Designed lifetime (based on date of manufacture): 0 years. You can find further explanations in the applicable rules and regulations and on the afecor website (www.afecor.org). This procedure applies to heating systems. For thermoprocessing equipment, observe local regulations. -

Logistics Transport Protect the unit from external forces (blows, shocks, vibration). On receipt of the product, check that the delivery is complete, see page (Part designations). Report any transport damage immediately. Storage Store the product in a dry and clean place. Storage temperature: see page 3 (Technical data). Storage time: 6 months before using for the first time. If stored for longer than this, the overall service life will be reduced by the corresponding amount of extra storage time. Packaging The packaging material is to be disposed of in accordance with local regulations. Disposal Components are to be disposed of separately in accordance with local regulations. Certification Declaration of conformity We, the manufacturer, hereby declare that the products..r50b, marked with product ID No. CE- 0085AU07, 5 50R60S/M, marked with product ID No. CE-0085BQ0576, 5 50F60G, 65 50F60G, marked with product ID No. CE-0085AT038, 5 50/00F60G, marked with product ID No. CE-0085BN075, 5F60CK 00F60C, 65 00F60C, marked with product ID No. CE-0085CM053, flow adjusting cocks GEHV 0..50, GEH 3 50R50, meet the requirements of the listed Directives, Regulations and Standards...R50B 009//EC Regulation: 305/0 EU DIN EN 33 5 50R60S/M 009//EC DIN EN 377, DVGW VP 303 5 00F60G 90/396/EEC 97/3/EC ( 65 50F60G) DIN EN 377 5 50/00F60G 009//EC 97/3/EC DIN EN 377 5F60CK 00F60C 009//EC 97/3/EC ( 65 00F60C) DIN EN 377 GEHV 0..50, GEH 3 50R50 97/3/EC The relevant products (not GE... and LEH) correspond to the types tested by the notified body 0085. The production is subject to the surveillance procedure according to Directive 009//EC (90/396/EEC) Annex II paragraph 3 and Directive 97/3/EC Annex III Module D or Annex III Module A. Elster GmbH Scan of the Declaration of conformity (D, ) see www.docuthek.com -5

Declaration of performance pursuant to annex III of Regulation (EU) No. 305/0 6 50R50B Eurasian Customs Union Elster GmbH Strotheweg 950 Lotte (Büren) Germany 05 The products, GEHV, GEH and LEH meet the technical specifications of the Eurasian Customs Union. DIN EN 33 Manual valve (DN)R50B Manual valve for gas installations Fuel gases of the st, nd and 3 rd gas families pursuant to G 60 DIN-DVGW NG-3AU07 Features: DIN EN 33 Pressure class: MOP 5 bar Temperature class: -0 C to +60 C Rated flow rate: passed Dimensional tolerances: passed Tightness test: 0 cm³/h Mechanical strength: passed Operating torque: passed Strength of stops: passed Endurance: passed Contact If you have any technical questions, please contact your local branch office/agent. The addresses are Elster GmbH available on the Internet or from Elster GmbH. Strotheweg, D-950 Lotte (Büren) Tel. +9 5-0 We reserve the right to make technical modifications Fax +9 5-370 in the interests of progress. info@kromschroeder.com, www.kromschroeder.com -6