COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

Similar documents
600 A 35 kv class PUSH-OP deadbreak connector installation instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

DT400/436 Tee Connector Installation Instructions

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

Effective March 2015 Supersedes S August 2002

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

S Loadbreak Apparatus Connectors WARNING: WARNING:

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

S Surge Arresters

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

Effective May 2017 Supersedes August 2005 (S )

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Booster Pump PB4-60 Replacement Kits

Arbor Terminator Press Operation Manual For IDT Connectors Order No Engineering No: AM

Pressure Dump Valve Service Kit for Series 2300 Units

Inspection Recommendations

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

600 / 600FC OWNER'S MANUAL

Pressure Dump Valve Service Kit for Series 3000 Units

FLANGED TWO-PIECE BALL VALVES

Repair instructions. Pivot bushing replacement. XL-AS10001RM-en-DE Rev B

MUELLER. Mega-Lite Drilling Machine. Reliable Connections. table of contents PAGE. Equipment 2. Operating Instructions 3-4. Parts Information 5

FLANGED TWO-PIECE BALL VALVES

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

750 Cable Cutter INSTRUCTION MANUAL

VL 2K LIFT D-L WINCH INSTRUCTIONS (Applies to P/Ns , , , , , )

Fiber Cable Puller with Tuf-Lugger lite

IMPORTANT: RECEIVING INSTRUCTIONS:

Hydraulic Punch Drivers

Norrsken Family Booklet

602 STRINGING MACHINE OWNER'S MANUAL

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

3M Liqui-Cel EXF-10x28 Series Membrane Contactor

3M Liqui-Cel EXF-10x28 Series Membrane Contactor with ANSI or JIS Connections with Integrated End Caps

COSASCO MODEL 60 RETRACTABLE 1500 PSI SYSTEM RETRACTOR KIT Work Instruction

2000 lb manual winch

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

X-6 STRINGING MACHINE OWNER'S MANUAL. Issue 1 - May Copyright 2004 GAMMA Sports - All Rights Reserved

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

ASG-SD2500 ASG-SD2500

ROPV R40 E Series User Manual

Retractable Hose Reel with 3/8" x 50' PVC Hose

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Angled Sign Light with Shade

This document to be used with Hurley traditional Davits

3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide

4 ANGLE GRINDER MODEL NO: CAT 52 PART

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

Model ASSEMBLY and OPERATING INSTRUCTIONS

SOTR Special Operations Tactical Respirator

3 Post Pressure Fit System Owner s Manual

TABLE OF CONTENTS FRAME FEATURES INTRODUCTION

Interface Devices, Inc. Hydraulic Mini Mule

Pressure Fit System - Two Post Version Owner s Manual

OWNER'S MANUAL. Copyright 2003 GAMMA - All Rights Reserved

12 Inch Barn Light. Owner s Manual

Tripod. System. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

Sunbrite LTC Large Underwater Pool Lights

! WARNING. Model PFC-1-G (direct acting) PFC-1-GR (reverse acting) Modulating Pneumatic Liquid Level Controls INSTRUCTION MANUAL MM-110B

DIRECT DRIVE DIXIE DOUBLE SEAMER Model 25D

User Guide. Tripod. flowtech 75 / 100 Tripod. Part No. S S

1 DRIVE INDUSTRIAL IMPACT WRENCH

A N C H O R T A B S N O R T H W E S T ANCHOR TAB VF. Patented. User Instructions

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

Installation and Operation

Caliber Sled Wheels Assembly Instructions for PN and 13579

Transcription:

Deadbreak Apparatus Connectors MN650052EN Effective May 2017 Supersedes May 2014 (S600-53-3) 600 A 35 kv class PUSH-OP deadbreak connector installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. INSTALLATION INSTRUCTIONS MN650052EN May 2017 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Additional information...1 Acceptance and initial inspection...1 Handling and storage...1 Standards...1 INSTALLATION PROCEDURE.... 2 Install T-Body and reducing tap plug...4 Install push-op terminator on apparatus bushing...5 ii INSTALLATION INSTRUCTIONS MN650052EN May 2017

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 INSTALLATION INSTRUCTIONS MN650052EN May 2017 iii

Hazardous Voltage. All associated apparatus must be de-energized during any hands-on installation or maintenance. Failure to comply could result in death and severe personal injury. Optional Capacitive Test Point Operating Instructions: Use only voltage indicating instruments specifically designed for test points. Use of conventional voltage sensing devices may provide false No Voltage indications. The test point must be dry and free of contaminants when checking for voltage. After indication is taken: clean, dry, and lubricate the test point cap with silicone grease and assemble to the test point. LATCH HANDLE PUSH PLATE 200 A INTERFACE OPERATING EYE FIRST NOTCHES LOCKING TEETH LOCKING SLOT BAIL BRACKET SHROUD PIN The capacitive test point is not sufficiently accurate, nor is it intended for, actual voltage measurements or phasing operations. A reading of no voltage from the test point should not be the only indication of a de-energized circuit obtained before touching the connector. Other procedures can include direct conductor voltage testing or grounding using a live-line tool. Failure to comply could result in death and severe personal injury. Product information Introduction Eaton s Cooper Power series 600 A, 35 kv Class PUSH OP deadbreak connectors are used to terminate high-voltage underground cable on deadfront ap pa ra tus such as transformers, switches, and switchgear. They are fully shielded, submersible, and meet the requirements of IEEE Std 386 standard Separable Insulated Connector Systems. 600 A deadbreak connectors are fully interchangeable with all other manufacturers that also certify compliance with IEEE Std 386 standard. The PUSH-OP deadbreak connector is rated for 900 A when used with all 900 A current carrying components. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Figure 1. Line illustration of typical 35 kv PUSH-OP connector assembly Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Acceptance and initial inspection Each PUSH-OP deadbreak connector is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the PUSH-OP deadbreak connector and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the PUSH-OP deadbreak connector to minimize the possibility of damage. If the PUSH-OP deadbreak connector is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System 1 INSTALLATION INSTRUCTIONS MN650052EN May 2017

Installation procedure Equipment required PUSH-OP Terminator Assembly Kit including: PUSH-OP Body Cable Adapter Coppertop Compression Connector Loadbreak Reducing Tap Plug (LRTP) Protective Cap (when furnished) Silicone Lubricant Tin Plated Copper Contact Probe Instruction Sheet Tools 5/16 Torque Tool (Catalog Number TQHD635) 5/16 T-Wrench (Catalog Number TWRENCH) Step 2. Remove concentric neutral wires or jacket Care should be taken to not cut or score the neutral conductors when cutting the cable jacket. Measure 13 (330 mm) from end of cable. (Refer to Figure 3.) If jacketed neutral cable, remove jacket to 13 dimension. If unjacketed neutral cable, bind neutral wires using (3) wraps of tape at 14 3/4 dimension. Pull back concentric neutral wires. Allow enough extra concentric neutral wires to connect to ground after installation and allow movement to insulated standoff bushing. BUSHING 1 3/4 ± 1/4" (45 mm ± 7 mm) Prepare the cable Step 1. Train cable Position cable vertically so that it is centered between apparatus bushing and parking pocket, parallel to, and 7 (178 mm) from apparatus frontplate. Provide adequate cable slack for cable movement between standoff bushing and apparatus bushing. Support cable as needed to maintain position. Cut cable 1 3/4 (45 mm) from centerline of bushing. (Refer to Fig ure 2.) 7" (178 mm) BUSHING 1 3/4" ± 1/4" (45 mm ± 7 mm) 13 ± 1/4" (375 mm ± 7 mm) CABLE CONCENTRIC NEUTRAL WIRES Figure 3. Line illustration of removing concentric neutral wires Step 3. Remove insulation shield Remove insulation shield 10-1/2 (267 mm) from end of cable. (Refer to Figure 4.) Do not cut or nick insulation. Step 4. Put tape marker in place Measure 1 (25 mm) from end of insulation shield. (Refer to Figure 4.) Wrap two (2) turns of tape to serve as marker for cable adapter location. TAPE MARKER INSULATION SHIELD CABLE INSULATION Figure 2. Line illustration for cable training 1" (25 mm) 10-1/2" ± 1/8" (267 mm ± 3 mm) Figure 4. Line illustration of cable stripback INSTALLATION INSTRUCTIONS MN650052EN May 2017 2

Step 5. Remove conductor insulation Do not pencil cable. Remove insulation exposing bare conductor to length of 4-3/8 (111 mm). (Refer to Figure 5.) Do not unwind conductor strands. only positive tolerance 4-3/8 + 1/4" (111 mm + 7 mm) Step 8. Lubricate and install cable adapter Lubricate exposed cable insulation. Lubricate inside of cable adapter. Slide small end of cable adapter over cable using twisting motion until small end is flush with tape marker. (Refer to Figure 8.) After sliding the cable adapter into position make sure that no bulge is present (see Figure 9). LUBRICATE INSULATION CABLE ADAPTER TAPE MARKER INSULATION BARE CONDUCTOR Figure 5. Line illustration of bare conductor length Step 6. Bevel insulation This step is for ease of installation only and has no effect on electrical characteristics. Remove sharp edge of insulation by beveling at 45 angle for approximately 1/4 (6 mm). (See Figure 6.) BEVEL 1/4 (6 mm) TAPE MARKER LUBRICATE Figure 8. Line illustration of insulation cable adapter Equipment Damage/Personal Injury. Improperly positioned cable adapter may result in equipment damage or personal injury. INSULATION Figure 6. Line illustration of insulation bevel Straight Cable Insulation Not Straight Major OD flared out Step 7. Clean insulation Apply solvent with a rag not directly to cable insulation. Clean insulation thoroughly with solvent dampened rag, wiping from conductor end toward insulation shield. (Refer to Figure 7.) Straight Cable Insulation Shield Tape Marker Not Straight bulge Ensure that all traces of conductive residue are removed. WIPE INSULATION Correct Positioning Incorrect Positioning WIPING DIRECTION Figure 7. Line illustration of insulation cleaning bulge Figure 9. Cross sectional view of cable adapter positioning 3 INSTALLATION INSTRUCTIONS MN650052EN May 2017

Step 9. Install compression connector Refer to chart supplied with the crimp connector for tool and die to be used. Wire brush conductor, only if it is aluminum. Remove protective cap from compression connector. Insert conductor completely into compression connector and rotate connector to distribute inhibitor. Connector must be fully seated on cable conductor. Align flats of compression connector and apparatus bushing for minimum conductor strain. Make first crimp 1/2 (13 mm) below shoulder of compression connector. (Refer to Figure 10.) Rotate each successive crimp 90º on com pres sion connector and allow 1/8 (3 mm) between crimps. Wipe excess inhibitor from connector and adapter surfac es. Install T-Body and reducing tap plug Step 11. Install PDT635 PUSH-OP body Clean and then lubricate outside of cable adapter. Clean and lubricate inside of PUSH-OP. Align PUSH-OP body so that operating eye is oriented away from apparatus bushing. Slide PUSH-OP body onto cable until compression connector eye is centered between 600 A interfaces. (Refer to Figure 12.) Remove tape marker from cable. TOOL SHOULDER BUSHING OPERATING EYE PUSH-OP BODY LUBRICATE CRIMPING AREA CABLE ADAPTER Figure 10. Line il lus tra tion of crimping area CABLE ADAPTER TAPE MARKER Step 10. Check dimensions Check length from end of compression connector to top of cable adapter. Length should be between 6-3/4 and 7-3/4 (171-197 mm). (Refer to Figure 11.) 6-3/4 7-3/4" (171 197 mm) TAPE MARKER COMPRESSION CONNECTOR CABLE ADAPTER CONCENTRIC NEUTRAL WIRES Figure 12. Line illustration of PUSH-OP body installation Step 12. Install LRTP into T-Body Clean and then lubricate the mating 600 A interface of the LRTP and T-body with the lubricant supplied. Remove and recycle the shipping cap from the 200 A LRTP interface and the thread protector from the alignment segment. Insert T-Wrench into throat of LRTP and thru rotating nut and engage alignment segment. (T-Wrench should not rotate without entire LRTP rotating.) Insert the 600 A alignment segment end of the LRTP into the side of T-body opposite the apparatus bushing. (Refer to Figure 13.) Carefully thread the alignment segment into the threads of compression connector by turning the T-Wrench clockwise until a positive stop is felt. Figure 11. Line illustration for dimensional check INSTALLATION INSTRUCTIONS MN650052EN May 2017 4

Continue applying clockwise force to the T-Wrench until the pin connecting the alignment segment to the LRTP shears allowing the T-Wrench and alignment segment to rotate freely. TORQUE TOOL PROBE Align with internal floating nut of LRTP Remove alignment segment by applying pressure to the T-Wrench to separate the alignment segment from the LRTP. Recycle the align ment segment. See Figure 14 for illustration of completed LRTP installation. T-WRENCH T-WRENCH LRTP CLEAN AND LUBRICATE 200 A INTERFACE ALIGNMENT TOOL Figure 15. Line illustration of T-Wrench installation Install push-op terminator on apparatus bushing PUSH-OP T-BODY Figure 13. LRTP installation into T-body PUSH-OP ASSEMBLY T-WRENCH Step 14. Install PUSH-OP terminator on apparatus bushing Clean and lubricate mating interface of PUSH-OP terminator and mating apparatus bushing. Grasp terminator operating eye with clampstick and pull eye completely into clampstick. Move terminator to apparatus bushing, engaging shroud locating pins in bail bracket locking slots (refer to Figure 16), and push until latch plate engages first notches. (Refer to Figure 17.) Release operating eye from clampstick. SEPARATED ALIGNMENT SEGMENT Push forward on push plate firmly with clampstick until a bump is felt and latch plate fully engages locking teeth. (Refer to Figure 18a.) Figure 14. Line illustration of T-Wrench installation Step 13. Install probe Place tin plated copper PUSH-OP probe with stud on 5/16 hex T-Wrench. Insert 5/16 hex T-Wrench into the end of the probe and align the exposed extended length threads of stud-t with the internal floating nut of the LRTP. Do not cross thread probe on floating nut. Insert torque tool into the throat of the LRTP to engage the floating nut. Holding probe in place with 5/16 hex T-Wrench, tighten probe until torque tool begins to ratchet (20 to 25 ft. lbs.). (Refer to Figure 15.) Remove Tools CLAMPSTICK BAIL BRACKET LOCKING SLOTS LOCATING PIN Figure 16. Line illustration of moving terminator to bushing 5 INSTALLATION INSTRUCTIONS MN650052EN May 2017

LATCH PLATE FIRST NOTCH Pull on push plate with clampstick to ensure latch plate is engaged. (Refer to Figure 18b.) CLAMPSTICK Figure 17. Line illustration of beginning engagement of latch plate CLAMPSTICK PUSH PLATE LOCKING TEETH Figure 18b. Check latch engagement If present, thread optional locking pin with clampstick to secure connection. (Refer to Figure 18c.) OPTIONAL LOCKING PIN Figure 18a. Line illustration of full engagement of push plate Figure 18c. Thread optional locking pin INSTALLATION INSTRUCTIONS MN650052EN May 2017 6

Do not push on push plate while threading locking pin as this can cause the latch plate to become disengaged from the locking teeth. This condition can cause the PUSH-OP deadbreak connector to come off of the bushing during mating device removal, resulting in a line-to-ground fault causing serious injury or death. Step 15. Cap the 200 A interface Clean and lubricate 200 A LRTP interface and mating apparatus (i.e., 200 A protective cap, grounding elbow, M.O.V.E. arrester). To cap interface, follow installation instructions supplied with apparatus used. (Refer to Figure 19.) (Refer to Figure 18d for incorrect positioning.) PROTECTIVE CAP LRTP 200 A INTERFACE LATCH PLATE NOT ENGAGED INCORRECT CLEAN AND LUBRICATE Figure 19. Line illustration of protective cap installation Figure 18d. Incorrect latch plate positioning If optional locking pin is used, pull on latch plate s operating eye with clampstick to verify latch plate is still engaged in locking teeth after locking pin is tightened. (Refer to Figure 18e.) LATCH PLATE OPERATING EYE Step 16. Ground system Connect drain wire on insulated protective cap to system ground. Connect drain wire to LRTP grounding tab and shroud grounding tab. Connect drain wire to PUSH-OP body grounding tab and shroud grounding tab. Connect one strand of cable concentric neutral to shroud grounding tab. Connect remainder of concentric neutral wires to system ground. (Refer to Figure 20.) Figure 18e. Verify latch plate engagement GROUNDING TAB Figure 20. Line illustration of grounding GROUNDING TABS 7 INSTALLATION INSTRUCTIONS MN650052EN May 2017

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN650052EN May 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.