INSTALLATION INSTRUCTIONS

Similar documents
INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions For Natural Gas Conversion

Installation Instructions For Propane Gas Conversion (Kit Part No ) This kit is designed for conversion to Propane Gas

Installation Instructions

Parts List. Qty. Qty.

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Installation Instructions

ACCESSORY KIT INSTALLATION MANUAL

Installation Instructions

Installation Instructions

Natural Gas to L.P. Gas Conversion Kit

Installation Instructions

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Natural Gas to L.P. Gas Conversion Kit

Installation Instructions

Installation Instructions

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

installation instructions

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Your safety and the safety of others are very important.

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

INSTALLATION INSTRUCTIONS

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

WARNING: AVERTISSEMENT. LP & HIGH ALTITUDE LP CONVERSION KIT FOR INSTALLATIONS IN the United STATES (0-10,000 Ft)

Installation Instructions

Installation Instructions

ACCESSORY KIT INSTALLATION INSTRUCTIONS

/2004 US/CA

INSTALLATION INSTRUCTIONS

Installation Instructions

GAS KITS & ACCESSORIES 504,986M 11/2004 HIGH ALTITUDE KIT

Installation Instructions

Installation Instructions For Propane Gas Conversion

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F29, F30, F31, F32 & F33

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

Installation Instructions

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F13, RXGY-F27 AND RXGY-F28

Gas Conversion Kits CERAMIC HEATER SERIES (1, 2, 3, 4 Burner Units)

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

For *G7 / *GC2 & GUH* / GDD* Series Furnaces & Appliances Using Honeywell Gas Valves

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F23, F24, F25, F26, F38, F39, F40 & F41

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0347

Installation Instructions

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

Installation Instructions

Installation Instructions

Propane Conversion Kit Instructions

Operator: Save these instructions for future use!

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Propane Conversion Kit Instruction

INSTALLATION INSTRUCTIONS

Gas Conversion Kits Push Through (Positive Pressure) Tube Heater Models

Propane Conversion Kit Instruction

Operator: Save these instructions for future use!

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

VR8205S,T Direct Ignition Combination Gas Controls

Operator: Save these instructions for future use!

G96 Series BASOTROL Dual Operator Valve

Propane Conversion Kit Instruction

Instructions for High Altitude Conversion

Installation Instructions

36H SERIES Combination Gas Valve

Operator: Save these instructions for future use!

Conversion instructions from natural gas to propane

VR8305 Direct Ignition Combination Gas Control

Natural Gas Conversion Kit

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

INSTALLATION GUIDE Gas Rangetops

SL G3. Warning

DANGER WARNING IMPORTANT

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

Operator: Save these instructions for future use!

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

INSTALLATION INSTRUCTIONS

VR8105, VR8205, and VR8305 Direct Ignition Combination Gas Controls

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

BGA158 Series CE Approved Class A Shutoff Gas Valve

VR8200A Continuous Pilot Combination Gas Controls

Natural Gas Conversion Kit

BGA158 Series CE Approved Class B Shutoff Gas Valve

GM-7000 Series CE Approved Gas Control Valve

WARNING IMPORTANT H Identifying the Model, Control Code and Date of Manufacture

USER S INFORMATION MANUAL

WARNING: FOR OUTDOOR USE ONLY

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

SPECIFICATIONS ATTENTION

VS8420 Millivolt Gas Valve

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

GAS SUPPLY APPLICATION GUIDE

Dual Solenoid Gas Valve Installation

Transcription:

INSTALLATI INSTRUCTIS For Natural Gas to Propane Conversion Kit Model No: NAHA001LP or Part No. (1172958) CVERT Series BTUH N8MPN/L B 50, 75, 100, 125 *8MPN/L B 50, 75, 100, 125 *8MPN B 150 *8DNL B 50, 75, 100, 125 H8UH5, MUF, HL C 50, 75, 100, 125, 140 N9MPD A 50, 75, 100, 125 *9MPD C 50, 75, 100, 125 NOT FOR USE BTUH N9MP1 C 40, 60, 80 N9MP2 C 80 N9MPD A 40, 60, 80 *9MPD C 80 *9UHX A 60, 80, 100 use NAHA003LP (1174906) * Denotes Brand (T, H or C) SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment. Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached to or shipped with the furnace and other safety precautions that may apply. Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) ANSI Z223.1-2006/NFPA 54-2006. In Canada, refer to the National Standard of Canada Natural Gas and Propane Installation Code (NSCNGPIC) CAN/CGA -B149.1 and.2-05. Wear safety glasses and work gloves. Have fire extinguisher available during Start -up, Adjustment steps, and service calls. Recognize safety information. This is the safety -alert symbol!. When you see this symbol on the furnace and in instruction manuals be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, or CAUTI. These words are used with the safety -alert symbol. DANGER identifies the most serious hazards, those that will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or death. CAUTI is used to identify unsafe practices that may result in minor personal injury or product and property damage. Note is used to highlight suggestions that will result in enhanced installation, reliability, or operation. This conversion kit shall be installed by a qualified service agency. Please read these instructions completely before attempting installation. Consult gas supplier and tables in National Fuel Gas Code NFPA 54/ANSI Z223.1, 2006 or latest edition. In Canada, the National Standard CAN/CGA B149.1 and B149.2--05 Parts List Description Part# Qty. Burner Orifice #54 1011376 6 Honeywell Conv. Kit #396221 1172953 1 Switch, Low (LGPS) 1008801 1 Fitting Asy. 1009775 1 Wire Asy. 1173071 1 Label, Field Conversion 1009678 1 Label, Propane Conversion 1172956 1 Label, Derate 2505235 1 Instructions 441 06 1066 03 1 Orifices for 40k, 60k, 80k & *9UHX and alternate input unit conversion. (Not included in kit) Burner Orifice #55 1011354 as required Orifices for High Altitude Conversion (Not included in kit) (Refer to Table 2 - for required orifice) (Refer to Table 3 - for Alternate Input or 80,000 BTUH required orifice) (Refer to Table 4 - for 140,000 BTUH required orifice) Burner Orifice #55 Burner Orifice #56 1011354 as required 1011355 as required! WARNING FIRE, EXPLOSI, ELECTRIC SHOCK, AND CARB MOXIDE HAZARD. This conversion kit shall be installed by a qualified service technician in accordance with the Manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide could result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit. AVERTISSMENT Cette trousse de conversion doit être installée par un service d entretien, selon les instructions du fabricqualifiéant et selon toutes les exigences et tous les codes pertinents de l autorité compétente. Assurezvous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d incendie, d explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le service d entreien qualifié estresponsable de l installation de cette trousse. L installation n est pas adéquate ni compléte tant que le bon fonctionnement de l appareil convertin a pas été vérifié selon les instructions du fabricant fournies avec la trousse. 441 06 1066 03 June 2007

General Information This kit is for conversion of furnaces equipped with Honeywell VR8205S Series single stage gas valves certified for use with Natural Gas (and so marked) to units functionally the same as the certified furnace for use with Propane Gas. Before the furnace can be operated with Propane Gas, the low pressure switch must be installed. A gas valve conversion kit must be installed and main burner orifices must be replaced with orifices in this kit or with properly sized orifices for high altitude or alternate input ordered separately. The orifices provided in this kit are stamped to indicate the size (twist drill number) and are sized for commercially pure propane gas LY. Do NOT use them with butane or a mixture of butane and propane gas. The parts list specifies the size orifices supplied in the kit. Compare the size marking on the orifices with the sizes as listed in the parts list. Make sure you have the correct main burner orifices. Extreme care is used to assure that this kit contains the proper orifices. Oversized orifices could result in hazardous conditions, especially if the venting is inadequate. For that reason, we recommend that the installer check the size of the orifice with a new twist drill of the correct size. This procedure assures that the orifices provided are the correct size. Installation! WARNING ELECTRIC SHOCK, FIRE AND EXPLOSI HAZARD. Failure to follow this warning could result in personal injury, death, equipment damage, and/or property damage. Turn gas supply at manual gas valve before turning electric power supply and starting conversion. Turn electric power supply at disconnect switch or service panel before starting conversion. Disassembly Refer to Figure 1 and the following steps. 1. After disconnecting power and gas supply to the furnace, remove the access door, exposing gas valve and burner compartment. 2. Disconnect gas line from gas valve so manifold assembly can be removed. 3. Disconnect wiring at gas valve. Be sure to note the proper location of any and all electrical wiring disconnected. 4. Remove the four (4) screws holding the manifold and gas valve to the manifold supports. Do Not discard any screws. 5. Carefully remove the manifold assembly. 6. For *8MPL, N8MPL and *8DNL furnaces remove screws (1 per heat exchanger) that secure the NOx inserts and discard inserts. (Figure 2) Re--install screws. Note: It is very important to re--install the NOx insert mounting screws.! WARNING CARB MOXIDE HAZARD. Failure to follow this warning could result in personal injury, death, and/or property damage. NOx inserts for use with Natural Gas units LY. If Propane Gas is required, NOx inserts must be removed. Figure 1 Disassembly N9MP1, N9MP2 N9MPD&*9MPD N8MPN, N8MPL *8MPN, * 8MPL & *8DNL 441 06 1066 03 2

Figure 2 N8MPL, *8MPL & *8DNL Main Burner Orifices Removing NOx inserts 25-40-03 1. Remove the Natural gas (brass) burner orifices from the manifold assembly and replace them with the appropriate Propane (silver) orifices furnished in the conversion kit unless converting an alternate input or high altitude unit, then see Table 2 or Table 3 for appropriate orifices. (Figure 3) Figure 3 Remove Orifices 25-21 -00 2. Tighten the orifices so they are seated and gas tight about 1 1 / 8 from the face of the orifice to the back of the manifold pipe (Figure 4). Make sure orifice is installed straight so that it forms a right angle (90 ) to the manifold. Figure 4 1.11 (28.2mm) 1.21 (30.8mm) Changing Orifices Measure from face of orifice to the back side of the manifold. High Altitude Installation Gas input rate on the furnace rating plate is for installation at up to 2000. The #54 burner orifices supplied in this kit are sized for Propane Gas at full rate LY, for use between 0--2000 elevation. Do not use them above 2000 (except when noted by Table 2 or Table 3). Orifices for conversion at high altitude and alternate input must be ordered from Service Parts. Standard Input: Units may be installed at full input rating (25,000 BTUH per heat exchanger) when installed at altitudes up to 2000. 80,000 BTUH model and Alternate Input (Conversions): See unit instructions to determine if model may be converted to alternate input. Units may be installed at full input rating (20,000 BTUH per heat exchanger) when installed at altitudes up to 5000. In the USA, for furnaces fired on standard rate, the input rating for altitudes above 2000 (5,000 for 80,000 BTUH and alternate input) must be derated by 4% for each 1000 above sea level (see Table 2 and Table 3) In Canada, the input rating for altitudes above 2000 (5,000 for 80,000 BTUH) must be reduced by 10% for altitudes of 2000 to 4500 above sea level. Use the 2001 to 3000 column in Table 2 and Table 3. Alternate BTUH Input Ratings (USA Only) The input rating of these furnaces can be changed from the standard input rating to the alternate input rating shown in Table 1, by changing the main burner orifices. Changing of burner orifices MUST be done by a qualified service technician. See section on changing orifices. CAUTI: See unit instructions to determine if model may be converted to alternate input. Table 1 BTUH Standard Rating Alternate Input Ratings, USA LY. BTUH Alternate Rating Propane Gas Orifice* 50,000 40,000 #55 75,000 60,000 #55 100,000 80,000 #55 125,000 100,000 #55 *See Table 3 for High Altitude 3 441 06 1066 03

MANIFOLD PRESSURE AND ORIFICE SIZE FOR HIGH ALTITUDE APPLICATIS Table 2 HEATING VALUE at ALTITUDE BTU/CU. FT. PROPANE GAS MANIFOLD PRESSURE (in wc) 25,000 BTUH per burner EXCEPT FOR THE 90% 40k, 60k, 80k BTUH MODELS, 50 Hz 140,000 BTUH MODELS AND ALTERNATE INPUT RATINGS 0to 2000 2001 to 3000 MEAN ELEVATI FEET ABOVE SEA LEVEL 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 2500 10.0 10.0 9.0 10.0 9.4 8.5 10.0 Orifice Size #54 #54 #54 #55 #55 #55 #56 Conversion:1inwc=.25kPa Table 3 HEATING VALUE at ALTITUDE BTU/CU. FT. PROPANE GAS MANIFOLD PRESSURE (in wc) 20,000 BTUH per burner FOR THE 90% 40k, 60k, 80k BTUH MODELS AND ALTERNATE INPUT RATINGS 0to 2000 2001 to 3000 MEAN ELEVATI FEET ABOVE SEA LEVEL 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 2500 10.0 8.9 8.4 10.0 10.0 10.0 10.0 Orifice Size #55 #55 #55 #56 #56 #56 #56 Conversion:1inwc=.25kPa Table 4 HEATING VALUE at ALTITUDE BTU/CU. FT. PROPANE GAS MANIFOLD PRESSURE (in wc) 50 Hz 140,000 BTUH MODELS 0to 2000 2001 to 3000 MEAN ELEVATI FEET ABOVE SEA LEVEL 3001 to 4000 2500 10.0 8.7 9.9 9.0 8.5 10.0 10.0 Orifice Size #54 #54 #55 #55 #55 #56 #56 Conversion:1inwc=.25kPa NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1-2006/NFPA 54-2006 or National Standard Of Canada, Natural Gas And Propane Installation Code CSA B149.1-05. NOTE: Unshaded orifice size box indicates factory shipped size. NOTE: In the USA, for furnaces fired on standard rate, the input rating for altitudes above 2000 (5,000 for 80,000 BTUH and alternate input) must be derated by 4% for each 1000 above sea level (see Table 2 and Table 3) In Canada, the input rating for altitudes above 2000 (5,000 for 80,000 BTUH) must be reduced by 10% for altitudes of 2000 to 4500 above sea level. Use the 2001 to 3000 column in Table 2 and Table 3. Gas Valve Conversion Conversion of Honeywell VR8205S Gas Valve using Propane Gas Conversion Kit # 396221. 1. Remove the cap screw and pressure regulator adjusting screw. (See Figure 5 or Figure 6) 4001 to 5000 Figure 5 INLET Regulator Adjustment Under Cap 5001 to 6000 6001 to 7000 Typical Gas Control Valve V T HEYWEL L 7001 to 8000 7001 to 8000 7001 to 8000 Outlet Tap 1 / 8 NPT 2. Remove the existing regulator spring from the regulator housing. 3. Insert the replacement spring (red color) contained in this kit into regulator housing. 4. Install the pressure regulator adjusting screw and give it eleven (11) full clockwise turns. This will set the manifold pressure close to required setting for normal operation. Inlet Tap 1 / 8 NPT Regulator Adjustment Under Cap OUTLET 25-24-98a Outlet Tap 1 / 8 NPT 5. Replace the regulator cap screw. 6. Attach the Yellow Attention Label contained in the kit to the Gas Valve where it can be readily seen. INLET Inlet Tap 1 / 8 NPT IN HEYWELL OUTLET 441 06 1066 03 4

Figure 6 Spring Typical Regulator Assembly Regulator Adjusting Screws Manifold Assembly -- Be sure to engage the main burner orifices in the proper openings in the burners. Verify the ignitor is in the correct location. (See Figure 7) Testing for leaks -- After reassembly, turn the gas on and check all joints for gas leaks using a soapy solution. All leaks must be repaired immediately. Figure 7 Ignitor Location in(mm) 2 1/ 16(52.39) 5 / 16 (8) 1 / 4 (6.4) Propane Gas Color Code For Natural Gas Regulator Black Black Adjusting Screw Spring Red Stainless Steel Propane Low Switch (Required) 1. Using pipe joint compound that is resistant to Propane gas, tighten the fitting assembly into the inlet side of the gas valve. (Figure 9, Figure 10 or Figure 11). Position fitting assembly as shown. 2. Screw the Propane pressure switch into the bushing. Use pipe dope on connection. Tighten securely. Note: Do not block inlet port of pressure switch with pipe dope. Switch will not operate if inlet port is blocked. 3. Remove one yellow wire from the air pressure switch. Connect this wire to the male insulated yellow wire in the wire harness provided. 4. Connect the other yellow wire in the harness to the open termination on the air pressure switch. 5. Connect the other end of the wire harness to the two terminals on the Propane switch. Note: Propane switch is factory set to open if Propane gas supply pressure falls below 6 in wc. Note: See Furnace Wiring Label. Reassembly Reassemble all parts in reverse order as removed. Attach Propane Conversion Label next to the furnace rating plate or to the front exterior of the furnace. NOTE: Flame sensor has a different orientation in all 050 Figure 8 Gas Main Burner Burner Face 10-10 -78 Refer to the furnace rating plate for the approved gas input rating. Gas input to burners MUST NOT exceed the rated input shownonratingplate. Do NOT allow minimum gas supply pressure to vary downward. Doing so will decrease input to furnace. Refer to Table 5 for gas supply and manifold pressures. Table 5 Gas Type Gas s (in wc) Supply Recommended Max. Min. Manifold Propane 11 14 11 10 * * See Table 2, Table 3 or Table 4 conversion: 1 in wc =.25 kpa 5 441 06 1066 03

Figure 9 Typical Gas Piping and Adding Propane Low Switch N9MP1, N9MP2, N9MPD or *9MPD N9MP1, N9MP2, N9MPD or *9MPD Manual shut- off valve Right pipe entry 1 close nipple Propane Low Switch Detail Left pipe entry Drip Leg & Union # OF Alternative installation Use elbows and 1 (25mm) close nipple to connect valve to piping when using right side gas pipe entry. # Union should be outside cabinet except when clearances disallow, then it may be installed inside the cabinet. Manual shut- off valve MUST be upstream of dripleg, union, and furnace. L Figure 10 Typical Gas Piping and Adding Propane Low Switch *8MPN/L & *8DNL *8MPN/L & *8DNL Propane Low pressure switch. Left pipe entry Manual shut- off valve Right pipe entry Left Hand gas pipe entry detail Drip Leg & Union # OF Alternative installation Use elbows and 3 pipe nipple to connect valve to piping when using right side gas pipe entry. Propane Low Switch Detail # Union should be outside cabinet except when clearances disallow, then it may be installed inside the cabinet. Manual shut- off valve MUST be upstream of dripleg, union, and furnace. 25-25-53 Right Hand gas pipe entry detail 25-25 -51 441 06 1066 03 6

Figure 11 Typical Gas Piping and Adding Propane Low Switch N8MPN/L N8MPN/L Left pipe entry Manual shut- off valve For the LEFT side installation the LPGS is installed behind the gas valve with the wire terminals facing towards the front door of the furnace. A10 long gas pipe is used for the LEFT side installation. The gas pipe rests on top of the burner box assembly. Drip Leg & Union # Alternative installation Left Hand gas pipe entry detail 1 1 / 2 close nipple, 1 / 2 ID dia. pipe. 90 1 / 2 fitting 1 close nipple, 1 / 2 ID dia. pipe. 25--24--86 # Union should be outside cabinet except when clearances disallow, then it may be installed inside the cabinet. Manual shut- off valve MUST be upstream of dripleg, union, and furnace. TheLPGSinstalledin the RIGHT side position. It is attached to the INLET side of the gas valve. 1 1 / 2 close nipple, 1 / 2 ID dia. pipe. Right pipe entry Start -up and Check -out 1. Remove the plug from the Inlet Tap on gas valve and install a manometer. (Figure 5) 2. Open manual gas line valve to unit. Check for gas leaks and correct as necessary. Check supply pressure, 11 in wc recommended, 11 in wc minimum, 14 in wc maximum. If not within these limitations DO NOT OPERATE FURNACE, contact gas supplier. 3. Close manual gas line valve to unit, remove manometer and replace inlet pressure tap plug. Gas Valve Adjustment 1. With the gas valve knob or switch in the position, remove the pressure tap plug from the outlet end of the valve, and connect a U tube manometer to the pressure port. (See Figure 5) 2. Turn the gas valve knob or switch to the position and restore electrical power to unit. Cycle the main burner on and off several times to stabilize the pressure regulator diaphragm. This MUST be done before an accurate pressure reading can be obtained. 3. With the main burner on, read the pressure gauge. For appropriate reading see Table 2 or Table 3. Turn pressure regulator adjusting screw clockwise to increase or counterclockwise to decrease manifold pressure. Burner Input must not exceed nameplate rating. Refer to Section Checking Input Rate. 4. Turn gas valve to. Remove the pressure gauge and replace the pressure tap plug and pressure regulator cap screw. 5.. Start the main burners and check pressure tap plug for gas leaks. 6. With gas valve on, observe furnace through two or more complete cycles to be sure all controls are operating. Altitude Multiplier - Input Rate *High Altitude Input Rate = Nameplate Sea Level Input Rate x (Multiplier) Elevation High Altitude Multiplier Propane Gas* Standard Input and 140,000 BTUH Input Models High Altitude Multiplier Propane Gas* 80,000 BTUH Input Model High Altitude Multiplier Propane Gas* Alternate Input 0-2000 1.00 1.00 0.80 2001-3000 0.90 1.00 0.80 3001-4000 0.86 1.00 0.80 4001-5000 0.82 1.00 0.80 5001-6000 0.78 0.97 0.78 6001-7000 0.74 0.93 0.74 7001-8000 0.70 0.88 0.70 * Based on mid--range of elevation. 7 441 06 1066 03

Main Burner Flame Check Check for the following: (See Figure 8) Stable and blue flames. Dust may cause orange tips or wisps of yellow, but flames MUST NOT have solid, yellow tips. Flames extending directly from burner into heat exchanger. Flames do NOT touch sides of heat exchanger If any problems with main burner flames are noted, it may be necessary to adjust gas pressures or check for drafts. High Altitude Derated Unit Label The derated label supplied with the conversion kit must be completed and affixed to the furnace near the rating plate. Fill in the manifold pressure, orifice size and revised input rate. Refer to Table 2 or Table 3 provided to determine the proper orifice part numbers for ordering purposes. Verify System Operation Upon completion of all conversion procedures, perform the following steps to attach the appropriate labels and verify the system operation. 1. Locate the Propane Conversion Label next to the furnace rating plate. 2. Fill out and attach the Field Conversion Label near the furnace rating plate or to the front exterior of the furnace. 3. Turn the thermostat to its lowest temperature setting or to if equipped with a System Select Switch. 4. Turn the gas valve control knob or switch to. 5. Reinstall all access panels. 6. Turn all electrical power to the unit. 7. Set the thermostat to the desired temperature and the System Select Switch to HEAT. 8. Observe unit operation through two (2) complete heating cycles. See Sequence of Operation in furnace installation instructions. 441 06 1066 03 8