Delayed Coker Safe Sampling Tar or Spalled Coke

Similar documents
Low Coking Temperatures & Recent Site Experience

Delayed Coker Coke Drum Top Head Safety

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

TechTalk. Purging for Delayed Coking. Understanding purging system design in heavy-fouling applications. Outline

Operating Instructions

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA. Q= Cv S

Installation Operation Maintenance

Delayed Coker Automation & Interlocks

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

API Piping Plan 62: A Reliable Quench System

System Pressure Manager Standard & System Pressure Manager Plus

Temperature Controllers

Cutting Derrick Collapse

Mechanical Seal Piping Plans

FAQs about Directive 017

9.0 Equipment Cleaning and Repair

Delayed Coker Coke Drum Winch and Cables

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

ENSURING AN ACCURATE RESULT IN AN ANALYTICAL INSTRUMENTATION SYSTEM PART 1: UNDERSTANDING AND MEASURING TIME DELAY

Installation, operating and maintenance Instructions for Seemag bypass level indicator

SECTION PRESSURE TESTING OF PIPING

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

HEAT EXCHANGE AND TRANSFER, INC. 500 Superior Street Carnegie, PA (412) Fax: (412)

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

TECHNICAL DATA. than the water inlet pressure to the concentrate

Mechanical Seal Piping Plans

Hydraulic Reliability & Preventive Maintenance Report

Installation, Operation & Maintenance Manual

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA CAUTION

FIELD TROUBLESHOOTING COMMON MECHANICAL SEAL PIPING PLANS. Michael Huebner Principal Engineer Flowserve Corporation Pasadena, TX USA

Anti-flood device Model B-1

FAQs about Directive PNG017: Measurement Requirements for Oil and Gas Operations

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Bermad Pressure Reducing. Model: 42T

Installation and commissioning instructions 255 series and 256 series

Cutting Derrick Collapse

HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised

Title/Description: Fuel Cell Fill Procedure

Standard: NFPA 86 Process Ovens and Furnaces. NFPA 85 Boiler and Combustion Systems Hazards Code

Wet pipe low flow foam/water system

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

Mechanical Seal Piping Plans

Installation, Operation, and Maintenance Manual. Welker Constant Pressure Cylinder With Solid Indicator (Non-mixer) Model CP-30SI

Inert Air (N2) Systems Manual

Model VR6 System. Installation, Operation & Maintenance

WARNING: READ THE GENERAL INFORMATION MANUAL INCLUDED FOR OPERATING AND SAFETY PRECAUTIONS AND OTHER IMPORTANT INFORMATION.

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware

Installation, Operation, & Maintenance Manual NX Seal Cooler

TECHNICAL DATA. Q = C v P S

Bulletin TCR-104 & 109 Filling and adding to the Glycol pressure system

2 Sentry MCL Installation, Operation & Maintenance

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

SAMPLING SYSTEMS FOR LIQUIDS AND GASES FOR ALL TYPES OF APPLICATIONS

GREIG FILTERS, INC. OPERATION MANUAL

Serie ECO 3F. Flanged back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection

Serie ECO 3T. Threaded end back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection E U R O P E

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS

v. Size shall be specified on drawings.

TABLE OF CONTENT

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual

TECHNICAL DATA. Q = C v P S

Detector Carrier Gas Comments Detector anode purge or reference gas. Electron Capture Nitrogen Maximum sensitivity Nitrogen Argon/Methane

Air Eliminators and Combination Air Eliminators Strainers

VOC Process Equipment Clearing, Cleaning, and Routine Maintenance. Individual Unit Function: Environmental Procedure No.: PA Page: 1 of 10

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

Oxygen Usage Best Practice Guide

4400 TwinHybrid Gas Seal

PROCEDURES FOR REPAIRS TO ASME NV STAMPED PRESSURE RELIEF DEVICES OF NUCLEAR SAFETY RELATED PRESSURE RELIEF VALVES

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

San Antonio Water System Standard Specifications for Construction ITEM NO. 841 HYDROSTATIC TESTING OPERATIONS

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Instruction Manual Updated 7/26/2011 Ver. 2.2

PRESSURISED PAINT CONTAINER

Backflow What is it? City Water. Boiler. Make-Up Water Line

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

TECHNICAL DATA. Q = C v P S

Installation Instructions

T004.BioTector TOC Analyzer Pressure and Flow Test failure analysis

Engineered solutions for complex pressure situations

WHP Operations and Methods { July William M. Smethie, Jr. Lamont Doherty Geological Observatory Palisades, New York U.S.A.

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

Improving distillation tower operation

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

STANDARD OPERATING PROCEDURE

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

SCA Series Inverted Bucket Steam Traps

TECHNICAL BULLETIN DESIGNING A FUNCTIONAL COMPRESSED AIR SYSTEM

OPERATING PROCEDURES

Transcription:

Delayed Coker Safe Sampling Tar or Spalled Coke Presented by Mitch Moloney of ExxonMobil mitchell.j.moloney@exxonmobil.com @ Galveston TX coking.com May-2013 a MJ Moloney - ExxonMobil May-2012 coking.com 0

Topics: Safe Sampling Tar or Spalled Coke (1) Reasons for Sampling Resid (2) Background Review => Systems on various coker sites => Types employed (3) Sampling Resid - Our Practice (4) On-Line Analyzer Experience (5) Sampling Furnace Effluent during On-Line Spalling => Used at one site MJ Moloney - ExxonMobil May-2013 coking.com 1

Reasons for Sampling Resid: Validate CCR or Vis levels are in line with blend plan projections Material Balance Validation Performance testing New feed trials Unit Monitoring & Optimization Pilot plant feed gathering MJ Moloney - ExxonMobil May-2013 coking.com 2

Background: Most cokers originally cooled the hot tar by passing the tar through a ¾ coil immersed in a bucket of flowing water. => The tar line in & out was steam traced & insulated (maybe) => Disposable tubing may have been used as well => The flowing tar was -> either diluted with oil and sent to the oily water sewer (back in the day) -> or directed to a barrel, diluted with light oil and then loaded into a vacuum slop truck -> or returned to a lower pressure location in the process -> or piped to a slop oil system MJ Moloney - ExxonMobil May-2013 coking.com 3

Resid Tar Does Not Flow When Cool: MJ Moloney - ExxonMobil May-2013 coking.com 4

Background: Many of the old resid sample systems used a simple water cooler, which creates a low resid film temperature, high viscosity and plugging. Additionally, resid foulant reduces heat transfer and the ability of the cooler to properly cool the sample. MJ Moloney - ExxonMobil May-2013 coking.com 5

Site-1: Hot Tar Safe Sampling Original Tar Sampler Absorbent Foam Oily Water Drain Sample Container no longer fit Later Storm Water Drain Closed off with Cement to protect the API Separator Oily Water Drain MJ Moloney - ExxonMobil May-2013 coking.com 6

Site-1: Hot Tar Safe Sampling Tar Sampler Absorbent Foam Oily Water Drain Vacuum Truck Ground MJ Moloney - ExxonMobil May-2013 coking.com 7

Background: Site-2 The Simplest Design Water Cool & Flush It worked for many years where they obtained a daily sample => Main Disadvantage Created slop oil for disposal/handling => Eventually it was not flushed and plugged several times creating additional work and more safety risk MJ Moloney - ExxonMobil May-2013 coking.com 8

Site-3 Sample Cooler on Fast Loop MJ Moloney - ExxonMobil May-2013 coking.com 9

Background: Site-3 Water Cooled Design Sample Cooler Sample Station Enclosure MJ Moloney - ExxonMobil May-2013 coking.com 10

Background: Site-3 Water Cooled Design Facing the Sample Enclosure Warning Sign on Valve Operations Pressure gauge to detect plugging Air to Aspirated Vent to remove fumes MJ Moloney - ExxonMobil May-2013 coking.com 11

Background: Site-3 Water Cooled Design Disposable Plexiglas ¼-Turn Block Valve ¼-Turn Sample Valve Sample Can MJ Moloney - ExxonMobil May-2013 coking.com 12

Background: Site-4 Good on Paper, NOT in Practice Pump out of service and system gets plugged without proper flushing and steaming Flow control was problematic Required purging dead leg MJ Moloney - ExxonMobil May-2013 coking.com 13

Site-5 Hot Resid Sampler (650 F) We do not recommend taking a sample at this temperature due to flashing & spitting MJ Moloney - ExxonMobil May-2013 coking.com 14

Site-5 Hot Resid Sampler Removing the disposable plastic shield MJ Moloney - ExxonMobil May-2013 coking.com 15

Our Practice: Hot Tar Safe Sampling Use of a Strahman valve, close-coupled to the sample line. => A "regular" normal-body Strahman design should be used in the fast-loop piping. => Extended body Strahman valves used in heavy-wall-piping can distort and leak through the packing. => It is also important to have the valve piping well supported to avoid any torque on the Strahman body. Installation of sample valve as a take-off on a fast loop line installed in parallel with a flow control valve or other pressure drop device. If the sample point temperature is > 475 F (246 C), consider a steam or tempered-water cooler to lower the temperature to <475 F => The cooler should be installed in the fast loop line rather than in a separate take-off line that requires flushing after each sample. MJ Moloney - ExxonMobil May-2013 coking.com 16

Our Practice (cont d): Hot Tar Safe Sampling Use of steam tracing or jacketing and insulation to prevent line pluggage. Flushing connections and isolation valves around the sample valve to allow the sample valve to be taken out of service for maintenance (these would normally be provided on the fast loop sample line). The capability to fill one gallon (or 1 quart if desired), 5 gallon and 55 gallon sample containers. => The sample container should be rated for the sample temperature and allow safe handling in the field and the laboratory. => Proper shielding to protect the sample taker => Adequate lighting and proper sample station ingress/egress Use of a drilled gate valve downstream of the sample to allow control of the sample line flow. Optional Depending on the sample temperature, an aspirated vent in the sample box can be employed MJ Moloney - ExxonMobil May-2013 coking.com 17

Our Arrangement Hot Tar Safe Sampling Piping steam traced & insulated of nominal 2-inch diameter High Point Vent Hot Resid @ 450 F (246 C) CSC Flushing Oil Concentrically Drilled Gate Valve CSO Steam Hose connection CSO Low point drain Sample Table Sample Can Protected by a disposable plastic shield Process Control Valve Minimum Distance Threaded, retractable plug sample valve The table should be ~3 ft (0.9 m) high Proper Procedures are Essential no matter how good the facilities Current New MJ Moloney - ExxonMobil May-2013 coking.com 18

Layout in the Field Hot Tar Safe Sampling MJ Moloney - ExxonMobil May-2013 coking.com 19

Strahman Valve: Hot Tar Safe Sampling Sealing system uses a range of material combinations to create a differential hardness between the body and plunger seat. These valves do not allow any fluid flow until they are opened 9 turns, and the flow increases with each extra turn open. August 29, 2009 Brochure MJ Moloney - ExxonMobil May-2013 coking.com 20

Strahman Valve Half Coupling: Use of Half-Coupling Design reduces chance of seal leakage due to torque on the plunger. MJ Moloney - ExxonMobil May-2013 coking.com 21

Our practice requires only one Sample Can: Eliminates need for Sample Purge Can MJ Moloney - ExxonMobil May-2013 coking.com 22

There should be no need for this: Eliminates need for Sample Can Holder MJ Moloney - ExxonMobil May-2013 coking.com 23

Still Need to Wear Proper PPE: MJ Moloney - ExxonMobil May-2013 coking.com 24

Spalled Coke Safe Sampling Sample Take-Off and Return Sample Take-Off & Return piping around Control Valve MJ Moloney - ExxonMobil May-2013 coking.com 25

Open Sample Box Hot Tar Safe Sampling MJ Moloney - ExxonMobil May-2013 coking.com 26

Spalled Coke Safe Sampling Sample Box Sample Outlet & Fume Vent MJ Moloney - ExxonMobil May-2013 coking.com 27

Vent Aspirator Controls Spalled Coke Safe Sampling MJ Moloney - ExxonMobil May-2013 coking.com 28

Experience with On-Line Hot Tar Analyzers An On-Line Flow-Through Viscometer was used successfully for many years at a formerly-owned site. => Expensive Installation => High Maintenance & Frequent Calibration Recently installed an On-Line Gravity Analyzer => Nuclear-based instrument => Non-intrusive, low maintenance MJ Moloney - ExxonMobil May-2013 coking.com 29

Spalled Coke Safe Sampling Continual Sampling of Furnace Pass During On-Line Spalling allows tracking of Coke Removal Effectiveness during the Spall A slipstream of furnace pass outlet flow (steam and coke) was passed through a coil in a counter-flow water bath. Samples are taken into calibrated beakers, allowed to settle and effectiveness of the spall could be gauged as time progressed MJ Moloney - ExxonMobil May-2013 coking.com 30

Spalled Coke Safe Sampling Close-Up photos of the water and sample piping Sample inlet & outlet piping from furnace Water outlet & inlet piping from furnace MJ Moloney - ExxonMobil May-2013 coking.com 31

Fluid Coker Hot Coke Safe Sampling Incident (Tuesday Oct 3, 2000) A Field Technician was preparing to catch a normal Hot Coke sample. Prior to catching the sample he walked over to the sample box and opened both exterior and inner doors to obtain the sample pot which rested on the grid. He then walked over to the forklift/chunky cart, located just East of the heater chunky chute, and emptied the contents of the pot into the cart. He walked back to the sample box, replaced the sample pot and closed both doors. He then operated the forklift and positioned it under the heater chunky chute at which time he heard a popping sound coming from the direction of the Hot Coke Sample Box then a small fire coming out of the sample box, extending upward about 2-3 feet. After reporting the fire, he & another technician put out the fire using a fire hose. Upon further inspection they noticed an accumulation of coke below the "grid" of the sample box and determined that the box was partially plugged. They connected a nitrogen hose to the sample box and proceeded to clear the vacuum line. Investigation Conclusion: The vacuum line from the sample box was partially plugged allowing hot (1000 F) coke from a previous sample to accumulate in the bottom section of the sample box. When the technician opened the box to remove the sample pot, air was introduced to the smoldering coke. The location of this sample point is at ground level under the heater structure and the lighting in this area is less than adequate. The technician did not notice that there was an accumulation of coke in the cone part of the sample box. MJ Moloney - ExxonMobil May-2013 coking.com 32