S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Similar documents
S Surge Arresters

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

Effective March 2015 Supersedes S August 2002

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

DAI630TB2669 Dead Front Arrester Installation Instruction

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Inspection Recommendations

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

Single-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA

Selection of Electrical PPE Tables

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

ELECTRIC OPERATING PROCEDURES Date: 11/01/06

Erection, maintenance and disposal Inverted installation. Zinc oxide silicone-housed surge arresters PEXLIM R-X, Q-X and P-X

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Original Date of Issue: 04/09

User Instructions 1789 Parapet Wall Anchor

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION & MAINTENANCE INSTRUCTION

Residential Swimming pools

INSTRUCTIONS FOR USE

Figure 1 - Parts Identification. Copyright 2002, DB Industries, Inc.

SPECIFICATIONS ATTENTION

WARNING! DO NOT THROW AWAY THESE INSTRUCTIONS! READ AND UNDERSTAND BEFORE USING EQUIPMENT!

Installation, Operation and Maintenance Manual for Back Pressure Regulator

GAS FUEL VALVE FORM AGV5 OM 8-03

Operating instructions. Surge arrester Type MVR

GATOR Battery-powered Pistol Grip Cable Cutters

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

Installation Instructions

Effective May 2017 Supersedes August 2005 (S )

Rubber Dock Hose care, Use & Maintenance

Welding With Arc Welding Equipment

User Instruction Manual For Davit Rescue System

Electrical. Version 1.0

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

INSTRUCTION MANUAL Pressure Relief Device LPT

POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

Made in the USA. For Fall Protection Only. SafeLok Part Description

Check with local zoning official for property line distance requirements.

User Instructions 1790 Rail Anchor

Type BBS-03, BBS-05, BBS-06, BBS-25

INSTRUCTIONS FOR USE

MODEL 154XST INSTALLATION AND SERVICE INSTRUCTIONS FOR MODEL 154XST STROBE LIGHT FOR USE IN HARSH ENVIRONMENTS/ HAZARDOUS LOCATIONS

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

Installation. S&C Vista Underground Distribution Switchgear. UnderCover, Vault-Mounted, and Pad-Mounted Styles. Instruction Sheet

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

Ground Fault Circuit Interrupter(GFCI) Policy

Definitions found in several locations:

Pressure Dump Valve Service Kit for Series 2300 Units

User Instruction Manual Fixed Beam Anchor

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

Operating Instructions

3/4 SafeClaw Anchorage Connectors

2000 lb manual winch

Service Instructions. Syntron Control Model: CSCR-1-B (115V)

Fall Protection Checklist. Guardrail System

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

INSTRUCTION BOOK CARE AND MAINTENANCE OF OIL-IMMERSED (R-TEMP-OR SILICONE IMMERSED) TRANSFORMERS

LIFTING MAGNETS ERIEZ MAGNETICS

Distribution Transformer Instruction Manual

Spectrum AquaLight (SAL ) Color Underwater Light Owner s Manual

Sub-Base Assembly For Type-ML 32 & VR-1 Step Voltage Regulator Single-Phase Liquid-Filled Part # GEK 35171

MODEL SWH10 1,000 LB CAPACITY SWIVEL HOIST

Transcription:

Surge Arresters VariSTAR Type AZF Intermediate lass Installation and Maintenance Instructions Service Information S235-70-1 ontents Product Information.......................... 1 General Application Recommendations.......... 1 Safety for Life............................... 2 Identification................................ 3 Assembly................................... 4 Installation................................. 4 Electrical onnections........................ 7 Maintenance................................ 8 PRODUT INFORMATION Introduction The ooper Power Systems VariSTAR AZF intermediate class arrester incorporates the latest in metal-oxide varistor (MOV) technology. Designed without series or parallel gaps, the MOV disks in the type AZF are stacked in a single column. The Type AZF arrester utilizes a pressure venting system unparalleled in the industry for intermediate class arresters. The metal top AZF arrester has achieved a 40 ka station class arrester pressure relief capability extending its application range to include installations where increased fault current levels exist. Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Acceptance and Initial Inspection The factory take special precautions to ship arresters in well-designed containers that prevent damage which may occur during transit. arefully inspect the porcelain for chips or cracks. In case of improper handling or shipping dame, immediately file a claim with the carrier and promptly notify ooper Power Systems or your distributor. Handling and Storage Be careful during handling and storage of this arrester to minimize the possibility of damage. Always handle VariSTAR arresters carefully. Dropping or jarring an arrester may cause serious damage to the porcelain and/or internal parts. If the arrester is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001:2000 ertified Quality Management System AUTION: Never open an arrester. The arrester s internal components may be under spring compression and could be expelled with such force as to cause personal injury. AUTION: Mark all electrical connections ground and line so that no mechanical stress is applied to the surge arrester. Mechanical stress may damage the arrester in such a manner that its service life is shortened significantly. AUTION: Before performing any test on an arrester, contact your ooper Power Systems sales engineer. Some test procedures may damage the arrester externally and/or internally, making it incapable of protecting the apparatus or the circuit on which it is installed or shortening its service life significantly. WARNING: Always consider an arrester to be energized until both the line and the ground leads have been disconnected from the circuit. GENERAL APPLIATION REOMMENDATIONS The rating of an arrester is the power-frequency line-toground voltage at which the arrester is designed to pass an operating duty-cycle test. Table 1 provides a general application guide for the selection of the proper arrester rating for a given system voltage. May 2007 Supersedes 11/04 Printed in USA 1

VariSTAR Type AZF Intermediate lass Arrester ooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all ooper Power Systems employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission. The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. INFORMATION Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER: Hazardous voltage. ontact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result In death or serious injury. AUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. AUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING: Power distribution equipment must be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain this equipment can result in death, severe personal injury, and equipment damage. 2

S235-70-1 ooper Power Systems application engineers are available to make application recommendations. The following information is normally required: 1. System maximum operating voltage. 2. System grounding conditions. For three-wire circuits, grounding conditions depend upon whether the system is solidly grounded at the source, grounded through neutral impedance at the source, grounded through transformers, or ungrounded. Where unusual conditions exist (high ground resistance, high capacitive load, arc-welding equipment, etc.) the following supplementary information is necessary: A. A general description of the unusual condition. B. Type of construction, phase spacing, length of line, conductor size.. BIL of equipment and line insulation. D. Phase-sequence components of impedances on the source side of the arrester location. The impedance of the transformer and the impedance and grounding of supply to the substation affect the voltage during faults. 3. Available fault current. 4. Maximum line-to-ground voltage during faults and overvoltage duration. 5. Unusual environmental conditions (temperature and contamination). IDENTIFIATION Nameplates (Figure 1) are attached to the lower base casting of each arrester unit. An additional stacking nameplate (Figure 2) is supplied for arresters composed of two or more units. Figures 1 and 2 show the information that is listed on the nameplates. Attach the stacking nameplate shown in Figure 2 to a mounting bolt between the two lower arresters. TABLE 1 Recommended Arrester Applications for the Type AZF Arrester System Voltage (kv) Line to Recommended Arrester Rating (kv) Line Nominal Maximum Three Wire or Four Wire Wye Delta and Ungrounded Wye Solidly Grounded Neutral 2.40 2.25 3/4.5 3/4.5 4.16 4.37 3/4.5 6/7.5 4.80 5.04 3/4.5 6/7.5 6.90 7.24 6/7.5 6/7.5 8.32 8.74 6/7.5 9/10 12.00 12.70 9/10 12 15 12.47 13.20 9/10* 15 12 13.20 14.00 9/10* 15 12 13.80 14.50 9/10* 15 12 20.78 21.80 15* 24 21 22.90 24.20 18* 21 24* 27 24.90 26.40 18* 21 24 27* 34.50 36.50 27* 30 36* 39 46.00 48.30 36* 39 45 48* 51 69.00 72.50 54* 60 69 72* 115.00 121.00 90* 96 108 120* 138.00 145.00 108* 120 161.00 169.00 120 * Preferred arrester rating for this system voltage. RATING OF STAK ALTITUDE RATING Type AZF VariSTAR INTERMEDIATE ARRESTER RATED PRES RELIEF kv DATE POWER SYSTEMS DIV OLEAN, NY U.S.A. MOV ka DATE OF MANUFATURE MAXIMUM ONTINUOUS OPERATING VOLTAGE NO. OF UNITS kv TYPE AZF ARSR ONSISTS OF THE FOLLOWING TYPE AZF UNITS STAKED AND AND kv ARRESTERS kv ARRESTERS kv ARRESTERS POWER SYSTEMS DIV OLEAN, NY U.S.A. RATINGS OF STAKED UNITS KV-RATING Figure 1. Lower base nameplate. PRESSURE-RELIEF RATING NOTE: BEND TAB UP 90 AT TIME OF INSTALLATION AND ATTAH TO BOTTOM OF LOWEST UNIT WITH ONE OF THE MOUNTING BOLTS. Figure 2. Stacking nameplate. 3

VariSTAR Type AZF Intermediate lass Arrester Assemble Nut on Inside as Shown Assemble Strap on Outside and Nut on Inside as Shown Figure 3. Stacking nameplate. Apply Fargolene or Similar ompound to Terminal Before Making onnection ASSEMBLY The 3/4.5 through 39-kV arresters are shipped ready for installation. The 45 through 72-kV arresters require the assembly of two units stacked in series; the 90 through 120-kV arresters require the assembly of a grading ring supplied with complete unit. To allow for closer mounting spacing in enclosures, the top L-shaped terminal assembly and reinforcing plate is removable on all porcelain-top VariSTAR Type AZF arresters. For these applications, the Type AZF can easily be converted to a cubicle mount design. Grading rings are supplied with arresters rated 90, 96, 108, and 120 kv. Figure 3 illustrates the assembly of these rings. In addition to ooper Power Systems standard terminal clamps, the top castings or the grading-ring assemblies are provided with two.562 (1.43 cm) diameter holes on 1.75 (4.44 cm) vertical centers. These holes accommodate twohole terminal connectors per NEMA Standard SG1-4.03. Follow the identifi cation instructions described previously. When stacking two or three units in series, the vent ports must be aligned to facilitate proper venting of each unit in the arrester stack. INSTALLATION ubicle Mounting The porcelain-top arrester rated 3/4.5 through 27 kv can be installed outdoors or in any enclosure, such as those housing NX fusing, load transfer, oil or vacuum switching, or metal-clad switchgear equipment. Refer to Figure 4 for base-mounting-bolt locations. The minimum phase-to-ground (Dimension B) and minimum phase-to-phase (Dimension ) clearances are shown in Figure 5 and 6. These values are shown in Table 2. Figure 7 shows the porcelain-top arrester height (Dimension A). Outdoor Mounting hoose a permanent location so that the arresters will be installed as close as possible (electrically) to the equipment being protected. Minimum clearance distance between any line potential surface of an arrester and ground or another plane is listed in Table 2 as minimum phase-to-ground (Dimension B) and minimum phase-to-phase (Dimension ) and illustrated in Figures 5 and 6. Figures 8, 9, and 10 show the metal-top arrester height (Dimension A). AUTION: The values show in Table 2 are the minimum clearances recommended by ooper Power Systems. These clearances may be revised to meet local or system requirements for spacing or energized equipment. However, safe operating practices must always be followed. Base or Foundation Mounting Extend all pier footings below the frost line. Elevate the foundation sufficiently above the ground line to prevent contamination from ground splash, drifting snow, flood water, or other contaminating conditions. If the top of the foundation is not level, shims may be required for leveling. Lay out mounting studs on the foundation as shown in Figure 4. Arresters rated 90 through 120 kv should be foundation mounted; however, they can be mounted on a steel structure if this structure is rigid. AUTION: The vent port in the base must be directed away from the equipment being protected to prevent ionized gases from damaging equipment in the unlikely event of an arrester failure. Bracket or Structure Mounting When mounting arresters on brackets or bolting them directly to structures, make the assembly rigid enough to prevent arrester movement. Suspension Mounting Arresters rated through 72 kv can be suspension mounted. Either the top or bottom of suspension-mounted arresters can be connected to the line. AUTION: Prevent strains in arrester stacks by suspending them freely from a non-rigid suspension. Make flexible connections to line and ground terminals. 4

S235-70-1 TABLE 2 Dimensional Information Arrester Rating (kv) Mounting Figure Normal Number of Units in Stacks Dimension A Arrester Height in. (cm)* Dimension B Minimum Phase-to-Ground in. (cm)** Dimension Minimum Phase-to-Phase in. (cm)** 3/4.5 ubicle 7 1 12.3 (31.2) 5.2 (13.2) 9.0 (22.9) 6/7.5 ubicle 7 1 12.3 (31.2) 5.2 (13.2) 9.0 (22.9) 9/10 ubicle 7 1 12.3 (31.2) 5.2 (13.2) 9.0 (22.9) Outdoor 8 1 17.7 (45.0) 8.0 (20.3) 12.0 (30.5) 12 ubicle 7 1 13.6 (34.5) 5.2 (13.2) 9.0 (22.9) Outdoor 8 1 17.7 (45.0) 10.0 (25.4) 14.0 (35.6) 15 ubicle 7 1 13.6 (34.5) 7.2 (18.3) 9.0 (22.9) Outdoor 8 1 22.7 (57.6) 10.0 (25.4) 14.0 (35.6) 18 ubicle 7 1 14.9 (37.8) 8.0 (20.3) 9.0 (22.9) Outdoor 8 1 22.7 (57.6) 15.0 (38.1) 19.0 (48.3) 21 ubicle 7 1 16.8 (42.7) 9.2 (23.4) 11.5 (29.2) Outdoor 8 1 22.7 (57.6) 16.0 (40.6) 20.0 (50.8) 24 ubicle 7 1 18.8 (47.8) 10.0 (25.4) 12.5 (31.8) Outdoor 8 1 26.4 (67.0) 18.0 (45.7) 22.0 (55.9) 27 ubicle 7 1 18.8 (47.8) 10.0 (25.4) 12.5 (31.8) 30 Outdoor 8 1 26.4 (67.0) 18.0 (45.7) 22.0 (55.9) 33 Outdoor 8 1 26.4 (67.0) 18.0 (45.7) 22.0 (55.9) 36 Outdoor 8 1 31.4 (79.8) 20.0 (50.8) 25.0 (63.5) 39 Outdoor 8 1 31.4 (79.8) 21.0 (53.3) 26.0 (66.0) 45 Outdoor 9 2 49.1 (124.7) 23.0 (58.4) 28.0 (71.1) 48 Outdoor 9 2 52.9 (134.3) 24.0 (61.0) 29.0 (73.7) 60 Outdoor 9 2 52.9 (134.3) 29.0 (73.7) 34.0 (86.4) 72 Outdoor 9 2 62.9 (159.7) 33.0 (83.8) 38.0 (96.5) 90 Outdoor 10 3 79.3 (201.4) 51.0 (129.5) 68.0 (172.7) 96 Outdoor 10 3 84.3 (214.1) 53.0 (134.6) 70.0 (177.8) 108 Outdoor 10 3 94.3 (239.5) 58.0 (147.3) 74.0 (188.0) 120 Outdoor 10 3 94.3 (239.5) 62.0 (157.5) 79.0 (200.7) * See Figures 7-10. ** See Figures 5 and 6. Minimum phase-to-ground spacing from metal portion of top terminal is 2.4 (6.1 cm). Minimum phase-to-ground spacing from metal portion of top terminal is 3.6 (9.1 cm). 5

VariSTAR Type AZF Intermediate lass Arrester B 60 8.75" (22.22 cm) DIA. BOLT ENTER B VENT PORT Figure 6. Three-phase in-line mounting. 120 Figure 4. Mounting bolt locations. 0.625" (1.59 cm) DIA. (3 HOLES) /2 0.866 VENT PORT Figure 5. Three-phase triangle mounting. Figure 7. Type AZF arrester rated 3/4.5 through 27 kv.. Figure 8. Type AZF arrester rated 9/10 through 39 kv. Figure 9. Type AZF arrester rated 45 through 72 kv. Figure 10. Type AZF arrester rated 90 through 120 kv. 6

S235-70-1 ELETRIAL ONNETIONS AUTION: Make electrical connections so that no mechanical stress is applied to the arrester. Install the arrester as close as possible (electrically) to the apparatus being protected. Line and ground connections should be short and direct. Make the ground connection to a solid, effective and permanent low-resistance ground. NOTE: Equipment protection may be improved by interconnecting the arrester ground connections with the transformer tank and system neutral whenever possible. Two L-shaped electrical connectors, one ground and one line terminal, are supplied with arresters rated 3/4.5 through 72 kv. See Figure 11. The ground terminal connector is also used on arresters rated 90 kv through 120 kv, while the line terminal (top) connector on these arresters is an integral part of the top cap on the grounding-ring assembly as illustrated in Figures 3 and 12. The line and ground terminals include connector clamps that accommodate No. 6 solid through 500 mcm stranded copper or aluminum conductor. To allow for closer mounting spacing in enclosures, the top L-shaped terminal assembly and reinforcing plate shown in Figure 13 is removable on all porcelain-top VariSTAR Type AZF arresters rated 3/4.5 through 27 kv. For these applications, a separate U-shaped line lead terminal clamp accommodating conductor sizes from No. 6 solid through no. 1/0 stranded is supplied. On arresters rated 72 kv and below, line and ground leads may be brought in either vertically or horizontally. Line leads should be brought in from above the arrester and ground leads from below. On arresters rated 90 through 120 kv, the ground lead may be brought in vertically or horizontally; however, the line lead must be brought in vertically using the clamp provided. Figure 7. Type AZF arrester rated 3/4.5 through 27 kv.. Figure 7. Type AZF arrester rated 3/4.5 through 27 kv.. Figure 13 Installation of U -shaped line terminal clamp. 7

Surge Arrester/Type L Fuse utout ombination Installation Instructions MAINTENANE WARNING: Before working on an arrester, disconnect all line leaks. onsider any part of an arrester dangerous when connected to the line, including a base not solidly grounded VariSTAR Type AZF arresters require no special maintenance under normal conditions. If the arrester is installed in an area of severe contamination, keep the arrester housing, reasonably clean by washing periodically. Keep line and ground connections tight. WARNING: It is recommended that arresters should be de-energized before washing. 2007 ooper Power Systems, Inc., or its affi liates UltraSIL is a trademark of ooper Power Systems, Inc., or its affi liates ANSI is a registered trademark of the American National Standards Institute 1045 Hickory Street Pewaukee, WI 53072 USA www.cooperpower.com