Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Similar documents
Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

Tightness controls TC 1 3 and TC 4

Tightness control TC. Product brochure GB 3 Edition AGA

Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Safety. Operating instructions Filter module VMF Measuring orifice VMO Fine-adjusting valve VMV DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION Elster GmbH Edition 01.15

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves single-stage atmospheric operating mode GB-(LEP) 057 D01

Old documentation - Only for your information! Product is not available any more!

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Integrated gas-air system GB-GD 057 D01

Safety DANGER WARNING CAUTION. Contents. Changes to edition Elster GmbH Edition Please read and keep in a safe place

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Old documentation - Only for your information! Product is not available anymore!

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 055 D01

Old documentation - Only for your information! Product is not available any more!

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure DMV-ZRD/612 Series DMV-ZRDLE/612 Series

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 07.

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure. DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

WhirlWind Combined fully integrated gas/air control and safety system GB-WND 055 D01

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 04.

Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition 02.12

Safety. Operating instructions Burners for gas ZIO 165, ZIO 200 DANGER. Contents WARNING CAUTION Edition 11.11

Safety. Operating instructions Burners for gas BIO, BIOA DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition Edition 08.

Dual Modular Safety Shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

GM Series Dual-Block Multi-Function Gas Control Valves

VMR VMR-OTN VMR 6 bar

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

Dual Modular Safety Shutoff Valves with Proof of Closure. DMV-D/622 Series DMV-DLE/622 Series

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S02

pressure regulator Zero pressure regulator Proportional pressure regulator Compressed air-controlled

Dual Solenoid Gas Valve Installation

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

4/2 way Pneumatic Solenoid Valve

VGG... VGF... VGH... Gas Valves. Siemens Building Technologies HVAC Products VGG... VGF... VGH...

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

GasMultiBloc Combined regulating and safety valve Infinitely variable air/gas ratio control mode MB-VEF B01

Ratio Regulator Zero Governor. FRG/6 Series

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

Dual Modular Safety Shutoff Valve with NEMA 4x Enclosure. DMV-D/604L Series DMV-DLE/604L Series

Dual Modular Safety shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

Gas Pressure Regulator HON 300

North American Orifice Metering System

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Compact pressure switches for gas and air

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Gas Pressure Regulator HON 200

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

SKPx5.xxxUx Gas Valve Actuator with Safety Shutoff Function. SKP15.xxxUx SKP25.xxxUx SKP55.xxxUx SKP75.xxxUx

Pressure Switch for gas and air

SAV. Safety Shut-off Valve. Safety Shut-off Valve Type SAV

Pressure Switch for gas and air GGAO-A4

SKPx5.xxxUx Gas Valve Actuator with Safety Shutoff Function. SKP15.xxxUx SKP25.xxxUx SKP55.xxxUx SKP75.xxxUx

Pilot valves for pilot operated servo valves

Pressure Switch for gas and air

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

BGA158 Series CE Approved Class B Shutoff Gas Valve

Dual Modular Safety Shutoff Valves with NEMA 4x Enclosure DMV-D 704/604 DMV-DLE 704/604

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Pressure switch for gas and air

Safety Shutoff Valves MVD/6 Series MVDLE/6 Series

BGA158 Series CE Approved Class A Shutoff Gas Valve

GM-7000 Series CE Approved Gas Control Valve

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

Mass Flow Controller (MFC) for Gases

2/2-Way Solenoid Control Valve

VGD40.../VGD41... Double gas valves. Building Technologies Division Infrastructure & Cities Sector

PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION

Safety 0 50 Please read and keep in a safe place Operating instructions Solenoid valve for gas VAS 1, double solenoid valve VCS 1

VRB00 Series CLASS B SERVO REGULATED COMBINATION VALVES

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Gas Pressure Switch for DMV safety shutoff valves

Gas Pressure Switch for DMV safety shutoff valves

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

Indicates possible material damage. Contents. All interventions may only be carried out by qualified Pressure regulators with solenoid valve

Mass Flow Controller (MFC) for Gases

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

Transcription:

C US Pressure regulator with solenoid valve Air/gas ratio control with solenoid valve All-purpose servo regulator for gaseous media with integrated safety valve Suitable for a max. inlet pressure of 500 mbar (7 psig) Outlet pressure up to 100 mbar (40 "WC) Suitable for intermittent operation Minimum installation effort: no external impulse line required Check indication by blue LED High control quality Setting options from two sides EC type-tested and certified FM and CSA approved 3.1.0.4 Edition 10.06 GB

Application Pressure regulator and air/gas ratio control incorporating servo technology for shut-off and precise control of the gas supply to gas burners and gas appliances. For use in gas control and safety systems in all sectors of the iron, steel, glass and ceramics industries, also in commercial heat generation, such as the packaging, paper and foodstuffs industries. : Constant pressure governor, Class A, with high control accuracy, for excess air burners, atmospheric burners or single-stage force draught burners. Pressure preset via setpoint spring. : Air/gas ratio control, Class A, for maintaining a constant air/gas pressure ratio for modulating-controlled burners or with 1 bypass valve for stage-controlled burners. Pressure preset by the air control line. The can also be used as a zero governor for gas engines. Easy-to-service measuring connections. : Gas outlet pressure p G : Also air control pressure p L Regulator on excess air burners in the ceramics industry Air/gas ratio control on melting furnace for ensuring stoichiometric combustion over the entire capacity range Aluminium age-hardening furnace with air/ gas ratio controls for air deficiency cut-out 2

Application examples Constant pressure control The pressure regulator with solenoid valve maintains the set gas outlet pressure p G constant when subject to differing flow rates. If a second solenoid valve is used upstream of the, this complies with the requirements of EN 746-2 for two Classe A valves connected in series. Constant pressure control with two solenoid valves The pressure regulator with solenoid valve maintains the set gas outlet pressure p G constant when subject to differing flow rates. The gas line is two Class A shut-off valves connected in series, in accordance with the requirements of EN 746-2. min. max. Constant pressure control with max. pressure switch In this example, the minimum inlet pressure p e and the maximum outlet pressure p G are monitored with the pressure switches. The simple attachment of the pressure switch module makes installation easier. min. max. Constant pressure control with noncontrolled pilot gas outlet In this application, the pilot burner is supplied with a high inlet pressure via the pilot gas outlet. Here as well, the simple attachment of the bypass valve module makes installation easier. The minimum inlet pressure p e and the maximum outlet pressure p G are monitored with the pressure switches. 1 3

IC M p L Modulating control The gas outlet pressure p G is controlled via the air/gas ratio control with solenoid valve. The gas outlet pressure p G follows the changing air control pressure p L. The ratio of gas pressure to air pressure remains constant. The is suitable for a control range up to 10:1. If a second solenoid valve is used upstream of the, this complies with the requirements of EN 746-2 for two Class A valves connected in series. BVA IC M p L Modulating control with two solenoid valves The gas outlet pressure p G is controlled via the air/gas ratio control with solenoid valve. The gas outlet pressure p G follows the changing air control pressure p L. The ratio of gas pressure to air pressure remains constant. The is suitable for a control range up to 10:1. The gas line is two Class A shut-off valves connected in series, in accordance with the requirements of EN 746-2. BVA min. Modulating control with two solenoid valves and inlet pressure switch In this case, the minimum inlet pressure p e is monitored by the pressure switch DG.. C. The simple attachment of the pressure switch module makes installation easier. p L IC M BVA min. 1 p L High/Low control At high fire, the gas outlet pressure p G follows the air control pressure p L. The ratio of gas pressure to air pressure remains constant. Low fire is determined via the bypass valve. Here as well, the simple attachment of the bypass valve module makes installation easier. IC 40 M BVA 4

Replacement possibility for MODULINE pressure regulators with solenoid valve GVS, GVI and GVIB are to be replaced by, and + Type Flange Type GVS Pressure regulator with solenoid valve Pressure regulator with solenoid valve GVI Air/gas ratio control with solenoid valve Air/gas ratio control with solenoid valve GVIB 115 125 115 125 115 125 115 125 232 240 232 240 3 /8" ½" ¾" 1" 1" 1½" Air/gas ratio control with solenoid valve and bypass valve Size 115 Size 125 Size 115 Size 125 Size 115 Size 125 Size 115 Size 125 Size 232 Size 240 Size 232 Size 240 Air/gas ratio control with solenoid valve and bypass valve on request + Size 1 DN 15 115 Size 1 DN 20 120 Size 1 DN 25 125 on request Size 2 DN 40 240 350 1½" Size 350 on request 350 2" Size 350 Size 3 DN 50 350 ML MODULINE + connection flanges Rp internal thread Rp internal thread R TML MODULINE + connection flanges NPT internal thread NPT internal thread N 01 p e max. : 100 mbar (1.5 psig) p e max. : 500 mbar (7 psig) 02 200 mbar (3 psig) 500 mbar (7 psig) Quick opening Quick opening /N K Mains voltage: 24 V DC Mains voltage: 24 V DC K Q 120 V AC 120 V AC Q T 220/240 V AC 230 V AC W 3 Electrical connection via terminals Electrical connection via terminals 6 Electrical connection via socket Electrical connection via socket 9 Metal terminal connection box Electrical connection via terminals S Position indicator G Position indicator with gold contacts M Suitable for biologically produced methane Suitable for biologically produced methane Pressure test point at the inlet Pressure test point at the inlet and outlet* Outlet pressure p G : 2.5 25 mbar (1 10 "WC) -25 Outlet pressure p G : 2 90 mbar (0.8 36 "WC) 5 50 mbar (2 20 "WC) -50 10 100 mbar (4 40 "WC) -100 Standard seat A GVS 350ML01T3 with Rp 2 connection flanges Example Example 350R/NW-100A with test points = standard, = available * Pressure test points may be attached at the left and/or right-hand side. 5

Selection Pressure regulators with solenoid valve, EC type-tested and certified..t (T-product), FM and CSA approved 10 15 20 25 32 40 50 65 /15 /20 /25 /40 /50 R N /N K Q W -25-50 -100 A B 1 2 3 1T 2T 3T Inlet flange nominal size = no inlet flange Outlet flange nominal size Specification may be omitted if outlet = inlet Rp internal thread = R NPT internal thread = N Quick opening, quick closing = /N Mains voltage: 24 V DC = K 120 V AC; 50/60 Hz = Q 230 V AC; 50/60 Hz = W Electrical connection: M20 cable gland Plug with socket Plug without socket Fitted to the left side of connection box Fitted to the right side of connection box Max. outlet pressure p G max. for : 2.5 25 mbar (1 10 "WC) = -25 5.0 50 mbar (2 20 "WC) = -50 10 100 mbar (4 40 "WC) = -100 Standard valve seat = A Reduced valve seat = B Cont. 1 Order example 2 240R/NW-100A 3 Electrical connection via M20 cable 1T gland, enclosed, 2T 2 screw plugs attached at the 3T right-hand side, Accessories attached at the right-hand side: 2 screw plugs 2 test points p e and p G Gas pressure switch DG../VC (DG../VT) at the inlet Gas pressure switch DG../VC (DG../VT) at the outlet Reserved for bypass valve 1 Bypass or pilot gas valve VBY Accessories attached at the left-hand side: 2 screw plugs 2 test points p e and p G Gas pressure switch D G../VC (DG../VT) at the inlet Gas pressure switch DG../VC (DG../VT) at the outlet Reserved for bypass valve 1 Bypass or pilot gas valve VBY = standard = available 2 test points attached at the left-hand side Gas pressure switch DG../VC for / Gas pressure switch DG../VT for..t,..t Type Adjusting range [mbar] Type Adjusting range ["WC] DG 17/VC 2 17 DG 17/VT 0.8 6.8 DG 40/VC 5 40 DG 40/VT 2 16 DG 110/VC 30 110 DG 110/VT 12 44 DG 300/VC 100 300 DG 300/VT 40 120 6

Selection Air/gas ratio controls with solenoid valve, EC type-tested and certified..t (T-product), FM and CSA approved 10 15 20 25 32 40 50 65 /15 /20 /25 /40 /50 R N /N K Q W A B K E A N 1 2 3 1T 2T 3T Inlet flange nominal size = no inlet flange Outlet flange nominal size Specification may be omitted if outlet = inlet Rp internal thread = R NPT internal thread = N Quick opening, quick closing = /N Mains voltage: 24 V DC = K 120 V AC, 50/60 Hz = Q 230 V AC, 50/60 Hz = W Electrical connection: M20 cable gland Plug with socket Plug without socket Fitted to the left side of connection box Fitted to the right side of connection box Standard valve seat = A Reduced valve seat = B Connection kit for air control pressure p L : 1 plastic hose coupling, 2 screw plugs = K 1 compression fitting, 2 test points p G and p L = E 1 NPT 1/4 adapter, 2 test points p G and p L = A Zero governor = N Cont. 1 Order example 2 240R/NWAE 3 Electrical connection via M20 cable 1T gland, enclosed, 2T 2 screw plugs attached at the right-hand 3T side Accessories attached at the right-hand side: 2 screw plugs 2 test points p e and p G Gas pressure switch DG../VC (DG../VT) at the inlet Gas pressure switch DG../VC (DG../VT) at the outlet reserved for bypass valve 1 Bypass or pilot gas valve VBY Accessories attached at the left-hand side: 2 screw plugs 2 test points p e and p G Gas pressure switch DG../VC (DG../VT) at the inlet Gas pressure switch DG../VC (DG../VT) at the outlet Reserved for bypass valve 1 Bypass or pilot gas valve VBY = standard = available 2 test points attached at the left-hand side 7

Technical data Types of gas: Natural gas, town gas, LPG (gaseous), biologically produced methane (max. 0.1 %-by-vol. H 2 S); other gases on request. The gas must be dry in all temperature conditions and must not contain condense. Inlet pressure range p e : 10 500 mbar (4 200 "WC), FM: max inlet pressure p e (valve remains closed): 700 mbar (10 psig). Opening time of the solenoid valve: Quick opening: 0.5 s. Closing time: Quick closing: < 1 s. Ambient temperature: -20 +60 C (-4 +140 F), no condensation permitted, Storage temperature: 0 +40 C (32 104 F). Safety valve: Class A to EN 161, Factory Mutual Research Class: 7410 and 7411, ANSI Z21.21 and CSA 6.5, ANSI Z21.18 and CSA 6.3. Control class A to EN 88. Control range: up to 10:1. Mains voltage: 230 V AC, +10/-15%, 50/60 Hz; 120 V AC, +10/-15%, 50/60 Hz; 24 V DC, +20/-20%. Enclosure: IP 65. Duty cycle: 100%. Power consumption: Type 24 V= 120 V~ 230 V~ [W] [W] [W] / 1 28 30 30 / 2 46 54 53 / 3 58 63 63 Outlet pressure p G : 2.5 25 mbar (1 10 "WC), 5.0 50 mbar (2 20 "WC), 10 100 mbar (4 40 "WC). Outlet pressure p G : 0.5 100 mbar (0.2 40 "WC). Adjusting range at low fire: ±5 mbar (±2 "WC). Transmission ratio of gas to air: 1:1 The inlet pressure must always be higher than the air control pressure p L + 3 mbar (1.2 "WC). Connection of the air control pressure p L :..K: 1 1/8" coupling for plastic hose (internal dia. 3.9, external dia. 6.1) or..e: 1 compression fitting for tube 6x1 or..a: 1 NPT 1/4 adapter or..n: Zero governor with breathing orifice. Maintenance cycles Once per year, twice per year in the case of biologically produced methane. If the flow rate drops, clean the strainer. Certification EC type-tested and certified pursuant to Gas Appliances Directive (90/396/EEC) in conjunction with EN 161, EN 88 and EN 126, Machinery Directive (98/37/EC), Low Voltage Directive (73/23/EEC) in conjunction with the relevant standards, EMC Directive (89/336/EEC) in conjunction with EN 55014. FM approved Factory Mutual Research Class: 7410 and 7411 Safety overpressure slam shut valves. Designed for applications pursuant to NFPA 85 and NFPA 86. CSA approved Canadian Standards Association - ANSI Z21.21 and CSA 6.5 ANSI Z21.18 and CSA 6.3 UL approval In preparation. C US Detailed information on this product www.valvario.com Contact www.kromschroeder.com Sales We reserve the right to make technical modifications in the interests of progress. Elster Kromschröder uses environment-friendly production methods. Please send away for our Environment Report. Elster Kromschröder GmbH Postfach 2809 D-49018 Osnabrück Tel. +49 (0)541 1214-0 Fax +49 (0)541 1214-370 info@kromschroeder.com www.kromschroeder.com 03250373 F.T 09.03 2.000 8