+)) Lower Churchill Project RIPRAP DESIGN FOR WIND-GENERATED WAVES SNC LAVALIN. SLI Document No HER

Similar documents
TABLE OF CONTENTS EXECUTIVE SUMMARY 1

REVETMENTS. Purposes and Operational Constraints. Purposes Erosion control o o. Revetment Design 4/5/2016. CE A676 Coastal Engineering

Plan B Dam Breach Assessment

Lower Churchill Management Corporation. Nalcor Doc. No. MFA-PT-MD-0000-EN-PL

Annex E Bridge Pier Protection Plan

ANSWERS TO QUESTIONS IN THE NOTES AUTUMN 2018

A: Formalities. DELOS WP 1.1 Inventory on LCS, questionnaire, detailed description, revision D AUTH GR. Participant code and who to contact.

CHAPTER 68. RANDOM BREAKING WAVES HORIZONTAL SEABED 2 HANS PETER RIEDEl. & ANTHONY PAUL BYRNE

APPENDIX C VEGETATED EMERGENCY SPILLWAY. VERSION 1.0 March 1, 2011

LABORATORY EXPERIMENTS FOR WAVE RUN-UP ON THE TETRAPOD ARMOURED RUBBLE MOUND STRUCTURE WITH A STEEP FRONT SLOPE

Present Practices in Design of Rubblemound Breakwaters for Coastal Harbours-A Review

CHAPTER 132. Roundhead Stability of Berm Breakwaters

COASTAL EROSION: INVESTIGATIONS IN THE SOUTHWEST COAST OF SRI LANKA

COST EFFECTIVE STORAGE CAPACITY INCREASE FOR ALUMINA TAILINGS DISPOSAL AREA THROUGH SPILLWAY OPTIMISATION

Ermenek Dam and HEPP: Spillway Test & 3D Numeric-Hydraulic Analysis of Jet Collision

Appendix E Cat Island Borrow Area Analysis

MEMORANDUM. TNC Fisher Slough Final Design and Permitting Subject: DRAFT Technical Memorandum: Levee Emergency Spillway Design

Steven A. Hughes. Ph.D., P.E. David R. Basco. Ph.D., P.E.

NUMERICAL AND PHYSICAL MODELING

Technical Report Culvert A Hydraulic Analysis

Model Test Setup and Program for Experimental Estimation of Surface Loads of the SSG Kvitsøy Pilot Plant from Extreme Wave Conditions

Australian Journal of Basic and Applied Sciences

RISK AND STANDARDS BASED APPROACH TO RIP RAP DESIGN ALTERNATIVES FOR GRAHAMSTOWN DAM STAGE 2 AUGMENTATION

Design and Installation of two Permanent Booms at La Romaine-2 to resist Ice, retain Debris and serve as Safety Booms.

Variation of Pressure with Depth in a Fluid *

INCLINOMETER DEVICE FOR SHIP STABILITY EVALUATION

Large-scale Field Test

WOODFIBRE LNG VESSEL WAKE ASSESSMENT

Chapter Capacity and LOS Analysis of a Signalized I/S Overview Methodology Scope Limitation

Regional Analysis of Extremal Wave Height Variability Oregon Coast, USA. Heidi P. Moritz and Hans R. Moritz

HYDROSPHERE, OCEANS AND TIDES

WAVE OVERTOPPING OF RUBBLE MOUND BREAKWATERS

Rock Ramp Design Guidelines. David Mooney MS Chris Holmquist-Johnson MS Drew Baird Ph.D. P.E. Kent Collins P.E.

Technical Brief - Wave Uprush Analysis Island Harbour Club, Gananoque, Ontario

UNIT 15 WATER HAMMER AND SURGE TANKS

Technical Brief - Wave Uprush Analysis 129 South Street, Gananoque

IN-PLACE DENSITY AND MOISTURE CONTENT OF SOIL AND SOIL- AGGREGATE BY NUCLEAR METHODS (SHALLOW DEPTH) FOP FOR AASHTO T 310

TRAFFIC IMPACT STUDY CRITERIA

Flow in a shock tube

Advanced Hydraulics Prof. Dr. Suresh A. Kartha Department of Civil Engineering Indian Institute of Technology, Guwahati

Investigation on 3-D Wing of commercial Aeroplane with Aerofoil NACA 2415 Using CFD Fluent

BRRAKING WAVE FORCES ON WALLS

Physical Modelling of A-Jacks Units in Wave Flume Stage 2

PHASE 1 WIND STUDIES REPORT

JAR-23 Normal, Utility, Aerobatic, and Commuter Category Aeroplanes \ Issued 11 March 1994 \ Section 1- Requirements \ Subpart C - Structure \ General

PENNDRAIN.rep. HEC-RAS Version May 2005 U.S. Army Corp of Engineers Hydrologic Engineering Center 609 Second Street Davis, California

Driveway Design Criteria

Experimental Investigation of Clear-Water Local Scour at Pile Groups

Technical Note AN EMPIRICAL. METHOD FOR DESIGN OF BREAKWATERS AS SHORE PROTECTION STRUCTURES

CHAPTER 25 AKMON ARMOUR UNIT FOR COVER LAYERS OF RUBBLE MOUND BREAKWATERS. A. Paape and A.W. Walther

Shoreline Evolution Due to Oblique Waves in Presence of Submerged Breakwaters. Nima Zakeri (Corresponding Author), Mojtaba Tajziehchi

SUBPART C - STRUCTURE

HURRICANE SANDY LIMITED REEVALUATION REPORT UNION BEACH, NEW JERSEY DRAFT ENGINEERING APPENDIX SUB APPENDIX D SBEACH MODELING

THE LIGHTS GO OUT The Ultimate Protection Technology for Protecting Submarine Cables

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Chapter 5 5. INTERSECTIONS 5.1. INTRODUCTION

E 158 E 198 E 248. Tank top mounting Connection up to G11 / 4 Nominal flow rate up to 250 l/min e d

2. Water levels and wave conditions. 2.1 Introduction

Quality Planning for Software Development

INTERIM GUIDELINES FOR DETERMINING MINIMUM PROPULSION POWER TO MAINTAIN THE MANOEUVRABILITY OF SHIPS IN ADVERSE CONDITIONS

Stability of Cubipod Armoured Roundheads in Short Crested Waves Burcharth, Hans Falk; Andersen, Thomas Lykke; Medina, Josep R.

DISTRIBUTION: Electronic Recipients List TRANSMITTAL LETTER NO. (13-01) MINNESOTA DEPARTMENT OF TRANSPORTATION. MANUAL: Road Design English Manual

DESIGN OPTIMIZATION FOR A PASSIVE MESH SCREEN WAVE ABSORBER FOR THE CCOB

PARAMETRIZATION OF WAVE TRANSFORMATION ABOVE SUBMERGED BAR BASED ON PHYSICAL AND NUMERICAL TESTS

Broadly speaking, there are four different types of structures, each with its own particular function:

SPILLWAY REPLACEMENT PROJECT NUMERICAL AND PHYSICAL MODELING. Kara Hurtig, Water Resources Engineer, Northwest Hydraulic Consultants, BC, Canada

MF ER

Draft Indian Standard WIRE ROPE SLINGS AND SLING LEGS- SPECIFICATION (Second Revision) ICS ;

CHAPTER 5 CULVERT DESIGN

The Challenge of Wave Scouring Design for the Confederation Bridge

E 328 E 498 Tank top mounting Connection up to G1½ / -24 SAE and SAE 2 Nominal flow rate up to 600 l/min / gpm

Task 16: Impact on Lummi Cultural Properties

U S F O S B u o y a n c y And Hydrodynamic M a s s

APPENDIX A Hydrodynamic Model Qualicum Beach Waterfront Master Plan

KM/ Stainless steel air bellows Single acting Ø 220 to 400 mm

Introduction to Roadway Design

Aalborg Universitet. Published in: Proceedings of Offshore Wind 2007 Conference & Exhibition. Publication date: 2007

E 328 E 498 Tank top mounting Connection up to G1½ and SAE 2 Nominal flow rate up to 600 l/min

Wave Load Pattern Definition

Wave Assessment on Loch Ericht

Laboratory studies of water column separation

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Implementing Provisions for Art. 411 of the ICR Ski Jumping

OECS Regional Engineering Workshop September 29 October 3, 2014

COASTAL PROTECTION AGAINST WIND-WAVE INDUCED EROSION USING SOFT AND POROUS STRUCTURES: A CASE STUDY AT LAKE BIEL, SWITZERLAND

Hand-operated regulating valves in stainless steel Types REG-SA SS and REG-SB SS

CHAPTER 1 STANDARD PRACTICES

4.3 Oblique Shocks and Expansions Fans: The Supercritical Marine Layer.

CHAPTER 131. Breakwater Stability under Regular and Irregular Wave Attack

CHAPTER 4 SPALDING COUNTY, GEORGIA 4.0 CULVERT DESIGN

Modelling of Extreme Waves Related to Stability Research

Hours / 100 Marks Seat No.

Tension Cracks. Topics Covered. Tension crack boundaries Tension crack depth Query slice data Thrust line Sensitivity analysis.

RESILIENCE THROUGH RESTORATION

Period of Record from No data was available from 1955 to 1962, but the remaining 57 years of data was available. 2

Geometric Design Tables

Overflow valves Type OFV REFRIGERATION AND AIR CONDITIONING. Technical leaflet

The Hydraulic Design of an Arced Labyrinth Weir at Isabella Dam

3. GRADUALLY-VARIED FLOW (GVF) AUTUMN 2018

Ship Stability. Ch. 8 Curves of Stability and Stability Criteria. Spring Myung-Il Roh

Transcription:

+)) SNC LAVALIN Lower Churchill Project RIPRAP DESIGN FOR SLI Document No. 505573-3001-4HER-0011-00 Nalcor Reference No. MFA-SN-CD-0000-CV-RP-0006-01 Rev. 81 Date: 07 -Dec-2012 Prepared by: Checked by: Daniel Damov Senior Hydraulics Engineer Approved by: Approved by:

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 i REVISION LIST N o By Chec Appr. Appr. Date Remarks 00 SW DD GS NB 07-Dec-2012 Issued for use. PB SW DD GS NB 20-Nov-2012 Issued for initial client review and comment. PA SW DD GS NB 14-Nov-2012 Issued for internal review. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 ii TABLE OF CONTENTS PAGE EXECUTIVE SUMMARY... 1 1 INTRODUCTION... 2 2 OBJECTIVES... 4 3 SCOPE... 5 4 METHODOLOGY... 6 4.1 Minimum Riprap Mass... 6 4.2 Required Gradation... 7 4.3 Riprap Size & Quarry Selection... 7 4.4 Thickness of the Riprap Layer... 8 4.5 Extent of Riprap Protection Below Minimum Water Level (WL min )... 9 4.5.1 Toe Berm Protection... 9 4.5.2 Breaking Wave Criteria... 11 5 RESULTS... 13 5.1 North Spur Upstream Shore... 13 5.2 North Spur Downstream Shore... 15 5.3 Upstream Cofferdam... 16 5.4 Intake Cofferdam... 17 5.5 South Dam... 18 5.6 Downstream Cofferdam... 19 5.7 Summary of Results... 20 6 RECOMMENDATIONS... 23 Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 iii LIST OF FIGURES Figure 1-1: Muskrat Falls Hydroelectric Project Layout... 3 Figure 4-1: Gneiss Located in Quarry Q6 on the North Bank of the Churchill River Near Muskrat Falls (Left) Compared to Regular Bands of Schist (Right)... 8 Figure 4-2: Lower boundary of N s -values associated with acceptable toe berm stability (Ref. 4)... 10 Figure 4-3: Riprap toe berm for slope stability... 10 Figure 4-4: Riprap toe berm for slope stability... 11 Figure 5-1: Riprap Protection Showing Thickness of Layer and Extent Below Minimum Water Level... 20 Figure 5-2: Riprap Protection Showing Toe Berm... 20 Figure 5-3: Project Layout with Calculated D 50 for Studied Structures... 21 Figure 6-1: Final Recommended D 50 and Protection Elevation Extents for Studied Structures. 24 LIST OF TABLES Table 5-1: Riprap Design Results North Spur - Upstream Shore - Construction... 13 Table 5-2: Riprap Design Results North Spur - Upstream Shore - Operation... 14 Table 5-3: Riprap Design Results North Spur - Downstream Shore... 15 Table 5-4: Riprap Design Results Upstream Cofferdam... 16 Table 5-5: Riprap Design Results Intake Cofferdam... 17 Table 5-6: Riprap Design Results South Dam... 18 Table 5-7: Riprap Design Results Downstream Cofferdam... 19 Table 5-8: Summary of Results... 22 Table 6-1: Riprap Gradations to Be Considered for Design... 23 Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 iv Ref. No. REFERENCES 1 Étienne P.D. Mansard et al, 1996, "Model Study of Reservoir Riprap Stability", Chapter 136, Proceeding of 25 th ICCE, Orlando, Florida 2 Jean-Pierre Tournier et al, 1996, "An Improved Design Method for the Riprap of Earthfill Dams of Large Reservoirs", Chapter 163, Proceeding of 25 th ICCE, Orlando, Florida 3 CERC (US), 1984, "Shore Protection Manual", U.S. Army Corps of Engineers, Coastal Engineering Research Center, Fort Belvoir, Virginia, 3 Volumes, 1984 edition 4 U.S. Army Corps of Engineers, 2006, "Coastal Engineering Manual", Engineer Manual 1110-2-1100, U.S. Army Corps of Engineers, Washington, D.C. (in 6 Volumes) 5, 2012, "Lower Churchill Project, Wind-Generated Wave Study", prepared for Nalcor, SLI No. 505573-3001-4HER-0001-00, Nalcor No. MFA-SN-CD- 0000-CV-RP-0010-01, 12 September 2012 6, 2011, Lower Churchill Project - Design Criteria Hydraulic, prepared for Nalcor, SLI No. 505573-300A-4HEC-0001-PC, Nalcor No. M FA-SN- CD-0000-CV-DC-0001-01, 15 November 2011 Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 1 EXECUTIVE SUMMARY The following report highlights the methodology and results for the design of riprap protection with respect to wind-generated waves. The methods of the Société d Énergie de la Baie James and the U.S. Army Corps of Engineers as highlighted in various references have been utilized. The studied structures include the North Spur (upstream and downstream shores), Upstream Cofferdam, Intake Cofferdam, South Dam and Downstream Cofferdam. For the upstream shore of the North Spur, riprap should range in size from 450 to 800 mm. For all other structures, riprap should range in size from 350 to 600 mm. Detailed results are highlighted in Section 5.7 - Summary of Results. It should be noted that the results and the recommendations are with respect to wind-generated waves. Currently, SLI is carrying out a separate study with regards to riprap design based on ice conditions (SLI No. 505573-3006-40ER-0102, Nalcor No. MFA-SN-CD-0000-CV-RP-0008-01) and the results of that study may take precedence over the impact of wave action on riprap design. Therefore, the results of that study should be reviewed prior to finalizing the design of riprap structures. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 2 1 INTRODUCTION has signed an agreement with Nalcor Energy (the Client) to deliver engineering, procurement and construction management services for the Lower Churchill Project (LCP) in Newfoundland and Labrador, Canada. As part of the LCP, the Muskrat Falls Hydroelectric Development is located on the Churchill River, about 291 km downstream of the Churchill Falls Hydroelectric Development, which was developed in the early 1970 s. The installed capacity of the project will be 824 MW (4 units of 206 MW each). Riprap protection at different locations must be designed such that it can withstand the wave forces at each of the locations listed below. The following report highlights the methodology and results for the design of riprap protection with respect to wind-generated waves only. The methods described will then be applied to: North Spur (upstream and downstream shores); Upstream Cofferdam; Intake Cofferdam; South Dam; and Downstream Cofferdam. Figure 1-1 shows the project layout and the locations of the studied structures. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 3 Figure 1-1: Muskrat Falls Hydroelectric Project Layout Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 4 2 OBJECTIVES The objectives of this report are to: Present the methodology for the design of riprap protection with regards to wind-generated waves; Present the results of the analysis for each structure considered; and Make recommendations based on the analysis. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 5 3 SCOPE The scope of this report is to document the methodology for the design of riprap protection with respect to forces by wind-generated waves for various structures of the Muskrat Falls Hydroelectric Project and present the results of the analysis. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 6 4 METHODOLOGY The following methodogy is to be followed when designing riprap protection for structures of the Muskrat Falls Hydroelectric Project. These methods follow the procedures of the Société d Énergie de la Baie James and the U.S. Army Corps of Engineers as highlighted in various references (see Reference List). 4.1 MINIMUM RIPRAP MASS The Hudson formula is used to evaluate the riprap mass that should resist a certain wave height for specific conditions such as embankment slope and rockfill characteristics. The minimum riprap mass needed to sustain the significant wave is estimated with the following equation (Ref. 2): Where, 1 cot M min H s cot α ρ s ρ w K minimum mass of a single riprap unit (kg) significant wave height (m) cotangent of the angle of the slope with the horizontal mass density of riprap (2,650 kg/m³) mass density of water (1,000 kg/m³) stability coefficient It is recommended to estimate the minimum riprap mass (M min ) based on a significant wave for a specific period of recurrence and a stability coefficient (K) equal to 3.5 (Ref. 2). A significant wave with a period of recurrence of 1:1,000 years will be used for all permanent structures (Operation). A significant wave with a period of recurrence of 1:20 years will be used for all temporary structures (Construction). Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 7 4.2 REQUIRED GRADATION The size of the riprap is defined by the minimum and maximum mass. The ratio of the maximum mass to the minimum mass,, should theoretically not exceed 3.0, however, in the field it is difficult to achieve such a ratio (Ref. 2). In practice, a ratio of 4.0 to 6.0 can be readily achieved and is found to be acceptable, therefore a ratio of 5.0 is used to carry out the computations (Ref. 2). Where, 5.0 M max maximum mass of a single riprap unit for design (kg) 4.3 RIPRAP SIZE & QUARRY SELECTION The dimensions of the riprap are estimated with the following equation (Ref. 2): 1,000 Where, D n C f riprap size corresponding to the n th percentage passing (mm) form coefficient The minimum and maximum riprap dimensions are calculated based on the minimum and maximum masses. The value of the shape coefficient should be 0.6 (Ref. 2). D 50 is calculated by taking the average of the maximum and minimum dimensions. The above formula can then be rearranged to determine M 50. Riprap specifications are typically determined by laboratory tests which include density, shape, hardness and durability. The riprap will most likely be selected from gneissic rock formations. Gneiss is a rock with irregular banding which has little tendency to split along planes in contrast with Schist. The rock fragments to be used for riprap shall be selected based on the quality and dimensions of each unit. Fragments should be durable, abrasion resistant and free from seams, cracks and cleavage planes. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 8 Figure 4-1: Gneiss Located in Quarry Q6 on the North Bank of the Churchill River Near Muskrat Falls (Left) Compared to Regular Bands of Schist (Right) 4.4 THICKNESS OF THE RIPRAP LAYER The thickness of the riprap layer is the greater of 0.30 m (Ref. 3, Ref. 4), or: Where, 2.0 or 1.25 d c thickness of the riprap layer (m) The design layer thickness is determined by whichever of the above three conditions yields the greatest riprap layer thickness. The specified layer thickness should be increased by 50% for riprap placed underwater. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 9 4.5 EXTENT OF RIPRAP PROTECTION BELOW MINIMUM WATER LEVEL (WL MIN ) Typically, riprap protection should extend twice the significant wave height below the WL min (Ref. 2). If this is not possible because the water is too shallow, then appropriate toe berm protection must be put in place. 4.5.1 Toe Berm Protection The function of a toe berm is to support the main riprap layer and to prevent damage resulting from scour. Riprap displaced from the layer may come to rest on the toe berm, thus increasing toe berm stability. Lamberti (1995) showed that moderate toe berm damage has almost no influence on riprap layer stability. Therefore, in practice it is economical to design toe protection berms that allow for moderate damage. Practical toe berm stability formulas for waves based on small-scale physical model tests for regular, head-on and oblique waves are as follows (Ref. 4): Where, N s H stability number wave height in front of the structure, which in this case is equal to H D (m). H D is the design wave height and is equivalent to the average of the highest 10% of all waves. This is found by multiplying the significant wave height by 1.27. (ρ s /ρ w )-1 ρ s ρ w D n50 mass density of riprap (2,650 kg/m³) mass density of water (1,000 kg/m³) equivalent cube length of toe berm median riprap (m) The curve in Figure 4-2 below shows the lower boundary of N s -values associated with acceptable toe berm stability. Some riprap movement would occur; however, the amount of movement is minor and acceptable. This shows that the toe berm isn t overdesigned. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 10 Min design stability number (Ns 3 ) 100 10 1 0 0.2 0.4 0.6 0.8 Depth ratio h b /h s Figure 4-2: Lower boundary of N s -values associated with acceptable toe berm stability (Ref. 4) Figure 4-3 is a sketch of a typical cross-section of a riprap toe berm with the parameters defined and is followed by the equation to calculate B. Figure 4-3: Riprap toe berm for slope stability Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 11 3 Where, B W 50 ρ s h b h s length of toe berm (m) average mass of a single riprap unit (kg) mass density of riprap (2,650 kg/m³) height of the water from the water surface to the top of the toe berm (m) height of the water from the water surface to the bottom of the water body (m) Figure 4-4 is a sketch of the cross-section of a riprap toe berm on the downstream shore of the North Spur. Figure 4-4: Riprap toe berm for slope stability 4.5.2 Breaking Wave Criteria Design wave conditions for structural stability as well as for functional performance should be chosen based on whether the structure is subjected to the attack of nonbreaking, breaking or broken waves, as well as on the geometrical and porosity characteristics of the structure (Ref. 4). For nonbreaking waves, the design wave height is selected from a statistical distribution and depends on whether the structure is defined as rigid, semirigid, or flexible. For flexible structures, such as riprap structures, the design wave height usually ranges from H e (the equivalent wave height at the end of the fetch) to H s (the significant wave height). To determine whether a wave is breaking or nonbreaking, the following formula is applied (Ref. 3): Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 12 0.78 Where, H h s wave height in front of the structure, which in this case is equal to H D (m) water depth at the toe of the structure (m) If is greater than 0.78, then the wave is breaking. If it is less than or equal to 0.78, the wave is nonbreaking. The methodology presented is applicable for non-breaking waves except for the design of the toe berm. Therefore, a verification of the conditions is carried out to confirm the applicability of the method. For the locations with shallow water, a toe berm is considered even for non-breaking conditions. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 13 5 RESULTS A detailed study on wind-generated waves had been previously carried out (Ref. 5). The results of this study have been extracted for use in the calculations for riprap design. 5.1 NORTH SPUR UPSTREAM SHORE The significant wave height from the previous wind-generated wave study (Ref. 5) used in the following calculations for the 1,000-year return period is 1.33 m. The 1:20-year return period is used for design during construction and the significant wave height is 0.98 m. This needs to be considered since during construction a headpond will be created at El. 24 m during the open water season. The slope of the shoreline on the upstream side of the North Spur varies and calculations were carried out for slopes of 2.5H:1V, 3H:1V, 3.5H:1V, 4H:1V and 5H:1V for the permanent installation. Calculations were carried out for a slope of 2H:1V for the construction phase (1:20-year return period for design). The results of the analysis are: Table 5-1: Riprap Design Results North Spur - Upstream Shore - Construction Mass (kg) Slope M min M 50 M max 2H:1V 79 197 397 Dimensions (mm) Slope D min D 50 D max 2H:1V 368 499 629 Thickness of Layer (m) Slope d c d c, underwater 2H:1V 0.8 1.3 Slope Extent of Protection Below WL min (m) 2H:1V 2.0 Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 14 Table 5-2: Riprap Design Results North Spur - Upstream Shore - Operation Mass (kg) Slope M min M 50 M max 2.5H:1V 159 395 793 3H:1V 132 329 661 3.5H:1V 113 282 566 4H:1V 99 247 496 5H:1V 79 197 397 Dimensions (mm) Slope D min D 50 D max 2.5H:1V 464 628 793 3H:1V 436 591 746 3.5H:1V 415 562 709 4H:1V 397 537 678 5H:1V 368 499 629 Slope Thickness of Layer (m) d c d c, underwater 2.5H:1V 1.1 1.6 3H:1V 1.0 1.5 3.5H:1V 0.9 1.4 4H:1V 0.9 1.4 5H:1V 0.8 1.3 Slope Extent of Protection Below WL min (m) 2.5H:1V 2.7 3H:1V 2.7 3.5H:1V 2.7 4H:1V 2.7 5H:1V 2.7 The criteria for breaking waves is less than 0.78 for all slopes and waves impacting the upstream shore of the North Spur. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 15 5.2 NORTH SPUR DOWNSTREAM SHORE The significant wave height from the previous wind-generated wave study used in the following calculations for the 1,000-year return period is 1.05 m. The slope of the shoreline on the downstream side of the North Spur was taken as 3H:1V. The results of the analysis are: Table 5-3: Riprap Design Results North Spur - Downstream Shore Mass (kg) M min M 50 M max 65 162 325 Dimensions (mm) D min D 50 D max 345 467 589 Thickness of Layer (m) d c d c, underwater 0.8 1.2 Extent of Protection Below WL min (m) N/A The extent of protection below the water level is not applicable in this case since the water depth at the toe is only about 4.0 meters under spring flood with 1:2 year recurrence. Moreover, in winter ice will come into play and a toe berm would protect the stability of the riprap layer. The details for the toe berm protection are as follows: = 10 D n50 = 380 mm B = 1.2 m The criteria for breaking waves is less than 0.78 for waves impacting the downstream shore of the North Spur. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 16 5.3 UPSTREAM COFFERDAM The significant wave height from the previous wind-generated wave study used in the following calculations for the 20-year return period is 0.70 m. The slope of the Upstream Cofferdam was taken as 1.6H:1V. The results of the analysis are: Table 5-4: Riprap Design Results Upstream Cofferdam Mass (kg) M min M 50 M max 36 90 181 Dimensions (mm) D min D 50 D max 283 384 484 Thickness of Layer (m) d c d c, underwater 0.6 1.0 Extent of Protection Below WL min (m) 1.4 The criteria for breaking waves is less than 0.78 for waves impacting the Upstream Cofferdam. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 17 5.4 INTAKE COFFERDAM The significant wave height from the previous wind-generated wave study used in the following calculations for the 20-year return period is 0.70 m. The slope of the Intake Cofferdam was taken as 1.6H:1V. The results of the analysis are: Table 5-5: Riprap Design Results Intake Cofferdam Mass (kg) M min M 50 M max 36 90 181 Dimensions (mm) D min D 50 D max 283 384 484 Thickness of Layer (m) d c d c, underwater 0.6 1.0 Extent of Protection Below WL min (m) 1.4 The criteria for breaking waves is less than 0.78 for waves impacting the Intake Cofferdam. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 18 5.5 SOUTH DAM The significant wave height from the previous wind-generated wave study used in the following calculations for the 1,000-year return period is 0.95 m. The slope of the South Dam was taken as 1.7H:1V. The results of the analysis are: Table 5-6: Riprap Design Results South Dam Mass (kg) M min M 50 M max 85 211 425 Dimensions (mm) D min D 50 D max 377 510 644 Thickness of Layer (m) d c d c, underwater 0.9 1.3 Extent of Protection Below WL min (m) 1.9 The criteria for breaking waves is less than 0.78 for waves impacting the South Dam. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 19 5.6 DOWNSTREAM COFFERDAM The significant wave height from the previous wind-generated wave study used in the following calculations for the 20-year return period is 0.91 m. The slope of the Downstream Cofferdam is 2H:1V. The results of the analysis are: Table 5-7: Riprap Design Results Downstream Cofferdam Mass (kg) M min M 50 M max 64 158 318 Dimensions (mm) D min D 50 D max 342 463 585 Thickness of Layer (m) d c d c, underwater 0.8 1.2 Extent of Protection Below WL min (m) N/A The extent of protection below the water level is not applicable in this case since the water depth at the toe is only 2.0 meters at construction design spring flood with 1:20 year return period. Moreover, in winter ice will come into play and a toe berm will provide stability to the riprap layer. The details for the toe protection berm are as follows: = 10 D n50 = 330 mm B = 1.2 m The criteria for breaking waves is less than 0.78 for waves impacting the Downstream Cofferdam. Therefore the waves are nonbreaking and the methodology is applicable. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 20 5.7 SUMMARY OF RESULTS Table 5-8 summarizes the results of the calculations for the studied structures. Figure 5-1 and Figure 5-2 illustrate the terms described in Table 5-8. Figure 5-3 shows the project layout with the calculated D 50 for each structure. Figure 5-1: Riprap Protection Showing Thickness of Layer and Extent Below Minimum Water Level Figure 5-2: Riprap Protection Showing Toe Berm Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 21 Figure 5-3: Project Layout with Calculated D 50 for Studied Structures Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 22 H s (m) cot(α) North Spur Upstream Shore D min (mm) D 50 (mm) D max (mm) Required Thickness d c (m) Table 5-8: Summary of Results Required Underwater Thickness d c (m) Extent of Protection Below WL min (m) WL min (m) Required Riprap Upper El. (m) Required Riprap Lower El. (m) Depth at Toe, h s (m) Required Toe Berm El. (m) Operation 1.33 2.5 460 630 790 1.1 1.6 2.7 38.5 42.9 35.8 34.0 N/A N/A N/A Operation 1.33 3.0 440 590 750 1.0 1.5 2.7 38.5 42.9 35.8 34.0 N/A N/A N/A Operation 1.33 3.5 420 560 710 0.9 1.4 2.7 38.5 42.9 35.8 34.0 N/A N/A N/A Operation 1.33 4.0 400 540 680 0.9 1.4 2.7 38.5 42.9 35.8 34.0 N/A N/A N/A Operation 1.33 5.0 370 500 630 0.8 1.3 2.7 38.5 42.9 35.8 34.0 N/A N/A N/A D 50, Toe (mm) B (m) Construction 0.98 2.0 370 500 630 0.8 1.3 2.0 24.0 26.5 22.0 20.0 N/A N/A N/A North Spur Downstream Shore Operation 1.05 3.0 350 470 590 0.8 1.2 N/A 1.3 7.5 N/A 4.0 3.0 380 1.2 Upstream Cofferdam Construction 0.70 1.6 280 380 480 0.6 1.0 1.4 24.0 26.0 22.6 20.0 N/A N/A N/A Intake Cofferdam Construction 0.70 1.6 280 380 480 0.6 1.0 1.4 24.0 26.0 22.6 20.0 N/A N/A N/A South Dam Operation 0.95 1.7 380 510 640 0.9 1.3 1.9 38.5 46.3 36.6 34.0 N/A N/A N/A Downstream Cofferdam Construction 0.91 2.0 340 460 590 0.8 1.2 N/A 1.3 7.9 N/A 2.0 5.0 330 1.2 Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 23 6 RECOMMENDATIONS Based on the results, two gradations of riprap can be considered for design and are shown in Table 6-1. The required D 50 and riprap protection extents for each location is shown on Figure 6-1. It should be noted that the results and the recommendations are with respect to wind-generated waves only. Currently, SLI is carrying out a separate study with regards to riprap design based on ice conditions (SLI No. 505573-3006-40ER-0102, Nalcor No. MFA-SN-CD-0000-CV-RP-0008-01) and the results of that study may take precedence over the impact of wave action on riprap. The results of that study should be reviewed prior to finalizing structure design. Riprap Gradation Size (mm) 280 480 350 600 380 640 Table 6-1: Riprap Gradations to Be Considered for Design Structure Upstream Cofferdam - Construction Intake Cofferdam - Construction North Spur (D/S Shore) Construction & Operation Downstream Cofferdam - Construction North Spur (U/S Shore) Construction South Dam - Operation 460-800 North Spur (U/S Shore) Operation Recommendation D min = 400 mm D max = 600 mm d c = 0.9 m B = 1.3 m* D 50, Toe = 500 mm* D min = 400 mm D max = 800 mm d c = 1.2 m *Only if a toe berm is required. This is applicable for only the Downstream Cofferdam and downstream shore of the North Spur. Form Number F-0000-31AF-I-0015 01

SLI Doc. No. 505573-3001-4HER-0011 00 07-Dec-2012 24 Figure 6-1: Final Recommended D 50 and Protection Elevation Extents for Studied Structures Form Number F-0000-31AF-I-0015 01