TECHNICAL DATA 36 GALLON FOAM BLADDER TANK FOAM HOSE STATION 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS

Similar documents
SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

TECHNICAL DATA OBSOLETE

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

Horizontal Bladder Tanks

Vertical Bladder Tanks

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

OBSOLETE. Wet pipe low flow manifold system

VERTICAL BLADDER TANK

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Wet pipe low flow foam/water system

Model MTB-ASME Vertical Bladder Tanks

HORIZONTAL BLADDER TANK

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA Q= C. Table 1 - Specifications

FOAM TANK (1/2) DATA SHEET

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA CAUTION

TECHNICAL DATA OBSOLETE

Anti-flood device Model B-1

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Q = C v P S

Vertical and Horizontal Bladder Tanks

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q = C v P S

FOAM TANK (1/2) DATA SHEET

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

Bladder Tank Installation & System Design Information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA OBSOLETE

TECHNICAL DATA CAUTION

TECHNICAL DATA. Table 1 - Specifications

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:

Pipe Thread Connection 1/2 inch NPT. Friction Loss Refer to Figure 3

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Bermad Pressure Reducing. Model: 42T

End Connection. Thread x Thread N/A N/A N/A N/A Flange x Flange N/A

TECHNICAL DATA. Trimpac 257a. September 16, 2013

Model: 43T. Bermad Pressure Relief Valve

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA ACCELERATOR MODEL E-1

TECHNICAL DATA NOTICE

BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

FIREFIGHTING EQUIPMENT

SEMI FIXED/PORTABLE LINE PROPORTIONERS SLP NPR270

TECHNICAL DATA. Deluge Valves 211a. November 30, 2007 DELUGE VALVE MODEL E-1 ANGLE STYLE 3 (DN80), 4 (DN100) & 6 (DN150)

FIREFIGHTING EQUIPMENT

Bermad Model:

Model 420-HY Pressure Regulating Hydrant Valve

1805 Series Relief Valves

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Deluge Valves 218a. November 30, 2007 DELUGE VALVE MODEL F-1 STRAIGHT THROUGH STYLE 2-1/2 (DN65) - 8 (DN200)

AIR FOAM CHAMBER DATA SHEET

Speed control assembly model A-1

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

CASH VALVE TYPE KP BACK PRESSURE VALVES

GREIG FILTERS, INC. OPERATION MANUAL

LINE PROPORTIONERS LP NPR260 Approvals: UL, ULC

SECTION BUTTERFLY VALVES

TECHNICAL DATA OBSOLETE

1 Exam Prep. Tabs and Highlights

WW-730. Pressure Sustaining/Relief Control Valve

PRO SINK -R 1 and 2. Dilution system CONTENTS

MANUAL. Sesame. Thermoplastic Tank Technologies

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

BALANCED PRESSURE PROPORTIONERS

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

29 SERIES - SAFETY VALVE

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Transcription:

Page 1 of 8 1. GENERAL DESCRIPTION The Bladder Tank Foam Hose Station is an effective and compact method of supplying a supplementary hose line as required by NFPA 409. It is particularly useful for applications where there are low or fluctuating flows and pressures that make eductor based stations problematic. The bladder tank together with a ratio controller forms a balanced pressure proportioning system used to mix water and firefighting foam concentrate together to produce an effective extinguishing medium. The bladder tank technology is a dependable and precise mixing method that is widespread in the fixed fire protection market and requires no external power supply. This method gives a stable water/foam ratio by adjusting automatically to the variable flow rate and pressure conditions that occur during system operation. This feature makes bladder tanks particularly suitable to low or fluctuating water inlet pressure where eductor systems are deemed unsuitable. The bladder tank is a carbon steel pressure vessel containing an elastomeric bladder between the water and foam concentrate. The bladder permits water pressure to be transferred to the foam concentrate without the two fluids mixing together. For further information, please contact the appropriate Viking sales office in Section 5 Availability or refer to the technical documentation. The contents of this publication are subject to modifications without notice. 2. LISTINGS AND APPROVALS Photographs are for illustration purposes only. Refer to drawings for actual design details. The Bladder Tank Station is a pre-assembled collection of components and carries no approvals as a completed assembly. The bladder tank is FM Approved and/or UL Listed as part of a fire extinguishing system combining designated foam concentrates and ratio controllers. Pistol Grip Nozzle is FM Approved only. Approved and Listed system components can be found at www.approvalguide.com and www.database.ul.com FM Approved Low Expansion Foam Systems (FM5130) UL Listed Guide GFGV & GHXV (ul162) Manufactured according to ASME Sec. VIII Div.1. NOTE: Other international approval certificates may be available upon request. Replaces Form No. 011618 Rev 18.1 (Added P65 Warning.)

Page 2 of 8 3. 3.1 Construction Features 3.1.1 Bladder Tank Approved design pressure of 175PSI (12.1bar) 100% pressure tested according to the applied design code Lockable corrosion resistant brass tank trim/service ball valves (UL Listed / FM Approved) Machine welded circumferential and longitudinal seams for maximum quality and durability Safety valve on water side of bladder to prevent slow overpressure and relieve thermal fluctuations Bladder equipped with cast rubber caps to ensure water & foam integrity under constant pressure Bladder specifically tested for compatibility with foams shown in FM Approval and UL Listing Oversized to permit concentrate thermal expansion (volume expansion allowance) Tank equipped with inside protection at any opening to ensure no damage to the bladder Internal PVC foam concentrate distribution pipe ensures optimal foam concentrate usage Internal water distribution channel to equalize water pressure avoiding damage to the bladder Internal water distribution channel to facilitate quick draining during service and maintenance Nameplate holder to avoid undetected corrosion on the tank s shell behind the plate Sight level indicator tube External epoxy zinc rich primer with aliphatic polyurethane finish. FM/UL for corrosive atmosphere (salt fog) 3.1.2 Ratio Controller 2 (DN50) grooved ratio controller integrated into foam bladder tank station Nickel Aluminium Bronze construction for superior corrosion protection Operating pressure from 30PSI (2.07bar) to 145PSI (10bar) AFFF proportioning range from 50GPM (189 l/min) to 311 GPM (1177 l/min) FM Approved and/or UL Listed for use with specific Viking Foam Concentrates For use with Fresh or Salt Water Identification tag plate 3.1.3 Hose Reel Hose reel with water supply through center of reel Hose 38 mm: Semi-rigid hose with 10 bar working pressure Hose length 30M NST connection Hose connection: Goose-neck with hose nipple Hand crank for rewind with gearing device Hose guide Hose reel made of galvanized steel Waterways made of brass Epoxy/polyester powder coating 3.1.4 Pistol Grip Nozzle 1.5 NST Connection Selectable gallonage pistol grip nozzle (30-60-95-125 US GPM) Horseshoe shut off handle for straight stream or fog pattern Stainless steel filter mesh on nozzle inlet Heavy duty chrome plated shut-off ball 3.1.5 Base Frame Skid Constructed from carbon steel profile Access slots for fork trucks. Four lifting lugs Coated RAL3000 Flame Red Complete plug and play solution

Page 3 of 8 3.2 Standard Design Specifications Table 3.2.1 - Standard Materials Bladder tank shell and heads ASTM A516 Gr. 70 Bladder material Trim valves Safety thermal relief valve Paint Standard color Pipework Ratio controller Foam orifice Hose Hose reel Hose reel internal pipework Nozzle Polyester reinforced hypalon-neoprene polymers Brass Brass Epoxy zinc rich primer with aliphatic polyurethane finish Flame Red RAL3000 Carbon & Stainless Steel Nickel Aluminium Bronze UNS C95800 ASTM B148 UNS-C36000 Non Collapsible Galvanized Steel Brass Brass 3.3 Standard Design Specifications Table 3.3.1 - Standard Design Specifications Station design pressure 145PSI (10bar) Station operating pressure range 30PSI (2.07bar) to 145PSI (10bar) Operating temperature range 35 F to 120 F (1.7 C to 49 C) Capacity 36 US Gallon (136 litres) Approximate shipping weight 560 lbs (255kg) Proportioning range (AFFF1%, 3%) 50GPM (189 l/min) to 311 GPM (1177 l/min) Hose length 30 Metres Hose diameter 38mm (1.5 ) 3.4 Ordering Information Part Number VFS0036HA VFS0036HB Table 3.4.1 - Ordering Information Description 36 USG (136L) Foam Station with Hose for 1% AFFF S 36 USG (136L) Foam Station with Hose for 3% AFFF S 4. SCOPE OF DELIVERY Ensure that all components are complete and in good condition. The Bladder Tank Station is supplied in a shipping crate in the horizontal position. All Bladder Tanks Stations have lifting slots in the base to allow safe maneuverability on site. Bladder Tank is supplied empty with pre-installed bladder. Small trim valves and contents level device are supplied pre-assembled to the tank as standard. Safety relief valve supplied as standard according to design code selected. Anchor fixing bolts are not part of our supply scope.

Page 4 of 8 5. AVAILABILITY Please contact your local Viking sales office for further information. The product is available directly from Viking and official distributors only. EMEA: Viking SA, ZI Haneboesch, L-4562 Differdange / Niederkorn, Tel.: +352 58 37 37-1, Fax: +352 38 37 36, vikinglux@viking-emea.com Americas: The Viking Corporation, 210 N. Industrial Park Drive, Hastings,Michigan 49058, Toll free phone: (800) 968-9501 APAC: The Viking Corporation (Far East) Pte. Ltd., 69 Tuas View Square, Westlink Techpark, Singapore 637621 Tel: (+65) 6 278 4061, Fax: (+65) 6 278 4609, Email: vikingsingapore@vikingcorp.com 6. PRODUCT VARIANTS 6.1 Options Available for use with Viking AFFF 1%S C6 or AFFF 3%S C6 Foam Concentrate Factory acceptance test, notified body or third party inspections Special sea freight and fumigated packaging Removable Hose reel protective PVC cover in Red Low expansion Foam branch pipe Galvanization of skid frame prior to painting 6.2 General Bladder Tank Station Layout 6 3 1 ~72.8 inches ~1850 mm 7 14 9 8 11 15 35.4 inches 900 mm 2 12 ~25.6 inches ~650 mm 10 65 inches 1650 mm 13 4 5 Figure 6.2.3 Table 6.2.2 - General Bladder Tank Layout and P&ID Item Description Item Description 1 Bladder tank 9 Ratio Controller 2 Bladder tank thermal relief valve 10 Hose Reel on/off valve 3 Bladder tank quick-fill inlet 11 Hose Reel 4 Bladder tank drain valve 12 Pistol Grip Nozzle 5 Bladder tank level indicator valve 13 Skid 6 Bladder tank level indicator sight tube 14 System water inlet 7 Bladder tank water shut-off valve 15 Hose guide 8 Bladder tank foam shut-off valve -- --

Page 5 of 8 7. PERFORMANCE DATA 7.1 Nozzle Operating Flows and Pressures The Bladder Tank Station is factory set to give a flowrate of 95 US GPM (360 LPM) based on a nozzle inlet pressure of 100 PSI (7 Bar). Consideration should be given to the pressure losses coming from the pipework and hose itself. Actual inlet pressure requirements and performance data is shown in the table below. Nozzle Pressure Nozzle Flow Setting Actual Nozzle Flow Table 7.1.1 - Performanace Data Required Station Inlet Pressure Straight Stream Reach Fully Wound Fully Unwound Effective Overall PSI Bar GPM LPM GPM LPM PSI Bar PSI Bar Feet Meters Feet Meters 75 5 100 7 125 8.5 30 115 26 98 - - - - 80 24 90 27 60 230 52 197 - - - - 100 30 110 34 95 360 82 310 109 7.5 102 7 120 36 130 39 125 475 108 409 - - - - 130 40 140 42 30 115 30 115 - - - - 85 26 95 29 60 230 60 230 - - - - 105 30 115 35 95 360 95 360 148 10.2 139 9.6 125 38 135 41 125 475 125 475 - - - - 140 42 150 45 30 115 34 129 - - - - 90 27 100 30 60 230 67 254 - - - - 110 34 120 36 95 360 107 401 177 12.2 168 11.6 125 38 130 41 125 475 140 530 - - - - 135 41 145 44 8. INSTALLATION Refer to appropriate Installation Standards (i.e. NFPA, VdS, LPCB, etc.) and / or FM applicable FM Global Property Loss Prevention Data Sheets such as 4-12, Foam-Water Sprinkler Systems. The Viking Installation, Operation and Maintenance Bladder Tank Manual shall also be referenced. NOTICE When designing a bladder tank station into your fire protection system, please give consideration to future maintenance activities. Ensure that adequate clearance above the bladder tank is allowed. For further guidance contact us. The Bladder Tank Hose Station should be fixed to the floor using the pre-drilled anchor point. The water supply should be connected to 14 System water inlet. It is advisable to install a shut-off valve upstream of this point to facilitate isolation of the Bladder Tank Station for commissioning and future maintenance. 9. OPERATION 9.1 Overview 1. The bladder tank stores foam concentrate inside the bladder. When used in conjunction with the Viking Ratio Controller it proportions the foam concentrate accurately into the water stream. 2. During system activation, the outer side of the bladder tank is pressurized by the system water supply which forces foam concentrate into the ratio controller. 3. Simultaneously, as water flows through the venturi area of the ratio controller, a metered pressure drop also draws foam concentrate into the system water creating a foam solution mixed to the appropriate ratio. 4. The foam solution flows through the hose reel system and out of the open nozzle (or optional branch pipe). 5. As the foam concentrate continues to flow from the inside of the bladder, system water enters the bladder tank on the outside of the bladder keeping a balanced pressure system. 6. If water discharge only is required, the pre-installed foam shut-off valve (8) should be closed.

Page 6 of 8 9.2 Bladder Tank Refer to Bladder Tank Manual for Filling and Operational requirements. NOTICE All installation, commissioning, operation and maintenance activities must be carried out by personnel who are qualified and authorized by the system s owner or manager. The personnel responsible for these activities must proceed only after reading and fully understanding the Bladder Tank Manual for Filling and Operational requirements. As the bladder tanks manufactured by Viking have been designed, tested and approved by third party organizations including the durability and performance of the original accessories installed - only original spare parts and consumables must be used when replacements are required. The use of non-original spare parts may result in an unsafe or poor performance of the bladder tank and decrease its overall lifetime usage. Use of non-original spare parts automatically expires the warranty clause of the supplied equipment. This prescription applies, in particular, to the separation bladder between water and foam concentrate and to the foam concentrate itself. 9.3 Ratio Controller The Ratio Controller is supplied pre-assembled on the Bladder Tank Station skid respecting the installation requirements given in data page F_031416 TD1.3.2.1. 9.4 Hose Reel NOTICE Rubber is a natural compound and will wear down over time based on a natural degradation rate if the product is installed in specific installation conditions and locations. The natural degradation rate is increased significantly in conditions such as direct sunlight and Ozone polluted areas. We strognly recommend installing the hose reel in a location where it is not exposed to direct Sunlight/Ultraviolet Radiation and where there is no Ozone present. The hose reel is unwound by securely griping and pulling the end of hose to the desired area of operation. Care should be taken to ensure that the hose is correctly threaded through the hose guide. After use, the hose reel on/off valve (10) should be closed and pressure should be relieved from the hose reel by opening the nozzle (12). The hose can then be re-wound using the hand crank provided. 9.5 Pistol Grip Nozzle WARNING An inadequate supply of nozzle pressure and/or flow will cause an ineffective stream and can result in injury, death or loss of property. Failure to restrain nozzle reaction can cause firefighter injury from loss of footing and/or stream protection. Nozzle reaction will vary as supply conditions change: such as opening or closing other nozzles, hose line kinks, changes in pump settings, etc. Changes in spray pattern or flushing will also affect nozzle reaction. The nozzle operator must always be positioned to restrain the nozzle reaction in the event of those changes. Injury from whipping can occur. If nozzle gets out of control or away from operator, retreat from nozzle immediately. Do not attempt to regain control of nozzle while flowing water. Fire streams are capable of injury and damage. Do not direct water stream to cause injury or damage to persons or property. There are a wide variety of foam concentrates. Each user is responsible for verifying that any foam concentrate chosen to be used with this unit has been tested to assure that the foam obtained is suitable for the purpose intended. 1. Open and close the shutoff slowly at all times. 2. To open the nozzle pull the D handle towards the inlet. 3. To close the nozzle push the D handle towards the outlet. 4. Do not keep the shutoff handle in half-way position, as when the ball valve is partially open, it will cause turbulence and adversely affects stream quality. 5. To change the spray pattern: rotate the bumper clockwise (right) for a straight stream and counter clockwise (left) for a wide homogenous fog pattern. 6. Rotate the flow selection ring to adjust flow setting to the desired flow. The nozzle will flow the rated amount when the pressure at the nozzle is 100 PSI (7 bar). 7. To remove trapped debris in the nozzle, rotate the flow selection ring to the FLUSH position to open up the nozzle, allowing debris to pass through. 8. Large amounts or pieces of debris may be unflushable and can cause reduced flow and compromise nozzle performance. F_011618 In 18.03.29 the event Rev of a 18.1 blockage, TD1.3.9.1/06122018/en retreat to a safe area and uncouple the nozzle to remove Form No. debris.

Page 7 of 8 10. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly. 11. INSPECTIONS, TESTS, AND MAINTENANCE NOTICE The owner is responsible for maintaining the fire protection system and devices in proper operating condition. WARNING Any system maintenance that involves placing a control valve or detection system out of service may eliminate the fire protection capabilities of that system. Prior to proceeding, notify all Authorities Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected areas. Refer to respective requirements, according to the relevant standards for Inspection, Testing and Maintenance such as NFPA 11 and NFPA 14. In addition, the Authority Having Jurisdiction (AHJ) may have additional maintenance, testing and inspection requirements that must be followed. 11.1 Bladder Tank Refer to the Bladder Tank Manual for Maintenance Requirements. 11.2 Ratio Controller - Not applicable 11.3 Hose Reel In addition to the relevant Standard requirements for the Maintenance of hose reels with semi-rigid hose and systems with lay-flat hose it is recommended to follow this procedure: The firewater hose reel is part of the safety equipment. As such, it will not be in continuous use. This means that the performance and condition of the hose reel will not continuously reveal itself. Furthermore, long periods of inactivity of the system will tend to increase the risk of getting parts of the system clogged or stuck. Therefore, regular maintenance is vital in order to ensure that the firewater hose reel works safely when needed in case of fire. We recommend a schedule of maintenance intervals as follows: Monthly Isolation valve - The isolation valve (10) should be inspected every month to verify that the valve handle is operating freely, and that no leakage has occurred. Check that all isolation valves are in the right position (normally closed). Hose reel - Check that hose reel turns easily without leakage in connection & swiveling parts. Every three months Execute the monthly maintenance, in addition to the following: Isolation valve - The isolating inlet valve should be inspected to verify that ball is operating freely, and that valve body and handle is undamaged and that no leakages have occurred. Hose reel bearing - These parts shall be greased through the grease nipple. Black Molly or equivalent grease shall be used. 11.4 Pistol Grip Nozzle 1. Nozzles should be inspected before and after each use to ensure all parts are in a satisfactory working condition. 2. If any one of the following problems are encountered while in use the nozzle should be withdrawn from service and repaired: (A) Controls that are inoperable or difficult to operate (B) Excessive wear (C) Water leakage from joints (D) Broken spinning teeth (E) Loose or missing screws 3. Periodically flushing the nozzle with clean water and remove any build up of dirt from the exterior of the nozzle.

Page 8 of 8 4. Factory lubrication applied to the nozzle during production is sufficient and the lubricant used has excellent washout resistance and long term performance. Regularly check the moving parts of the nozzle for smooth and free operation, and signs of damage. If the nozzle is operating correctly, then no additional lubrication is required. Any nozzle that is not operating correctly should be immediately removed from service. 5. Regularly check any external screws for tightness, tighten as required with the addition of a good quality thread locker (i.e. Loctite262). 12. DISPOSAL At end of use the product described here should be disposed of via the national recycling system. Upon request, the manufacturer can take back and properly dispose any electrical equipment and electronic devices, if applicable. 13. ACCESSORIES AND SPARE PARTS Table 12.1.1 - Optional / Standard Spare Parts Part Number Description Material Connection B10C12.1 Standard Safety Valve Brass 1/2ʺ HYDROMETER Hydrometer Level Gauge Stainless Steel 316 1/2ʺ FILLDEVICE Filling Device with KPA Gauge Carbon Steel 1ʺ Contact us. Replacement Bladder Hypalon-Neoprene Contact us. Table 12.2.1 - Bladder Tank Manual Part Number Description Part Number Description F032216-EN English F032216-NL Dutch F032216-DE German F032216-PL Polish F032216-ES Spanish F032216-SV Swedish F032216-FR French F032216-TR Turkish F032216-IT Italian -- - 14. DECLARATION OF CONFORMITY If required Contact the appropriate sales office in Section 5 Availability for further assistance. Replaces Form No. 011618 Rev 18.1 (Added P65 Warning.)