Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Similar documents
Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition 02.12

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition Edition 08.

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Filter module VMF Measuring orifice VMO Fine-adjusting valve VMV DANGER. Contents WARNING CAUTION

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 06.

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 03.

Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION Elster GmbH Edition 01.15

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Motorized valve for gas VK DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 06.

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Tightness control TC. Product brochure GB 3 Edition AGA

OPERATING INSTRUCTIONS

Safety. Operating instructions Pressure switches for gas DG..H, DG..N Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 07.

Tightness controls TC 1 3 and TC 4

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 04.

Safety. Operating instructions. White meters BK V2 to BK V12. (component of a diaphragm gas meter) DANGER. Contents WARNING CAUTION

J48 Gas Pressure Regulator. Technical Bulletin

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Safety. Operating instructions Burners for gas ZIO 165, ZIO 200 DANGER. Contents WARNING CAUTION Edition 11.11

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Gas Pressure Regulator R 51

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

Safety Relief Valve HON 832

pressure regulator Zero pressure regulator Proportional pressure regulator Compressed air-controlled

Safety. Operating instructions Burners for gas BIO, BIOA DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Integrated gas-air system GB-GD 057 D01

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Pressure Reducing Valve for Steam Type 2333 A

GM-7000 Series CE Approved Gas Control Valve

Safety shut-off valve S 50. Product information

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves single-stage atmospheric operating mode GB-(LEP) 057 D01

Old documentation - Only for your information! Product is not available any more!

Safety shut-off valve S 100. Product information

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Dual Solenoid Gas Valve Installation

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 055 D01

Old documentation - Only for your information! Product is not available any more!

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Gas Pressure Regulator HON 300

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Old documentation - Only for your information! Product is not available anymore!

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

WhirlWind Combined fully integrated gas/air control and safety system GB-WND 055 D01

Pressure regulator FRS

Mounting and Operating Instructions EB 2555 EN. Self-operated Pressure Regulators. Pressure Reducing Valves Type 50 ES Type 50 EM.

Pressure relief valve

Pressure relief valve

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

DN 50 REGULATOR SUTON 5000A1 REGULATOR SUTON 5000D1

Control Valve with ZK Radial Stage Nozzle ZK 210. Original Installation Instructions English

BGA158 Series CE Approved Class A Shutoff Gas Valve

Commonwealth of Massachusetts Approved Product Approval code G

SAV. Safety Shut-off Valve. Safety Shut-off Valve Type SAV

Gas Pressure Regulator HON 200

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

Flowmeter. Original operating manual DFM

6301 TYPE CAST IRON SAFETY VALVES

BGA158 Series CE Approved Class B Shutoff Gas Valve

Filling valves AL, ALM Series Automatic filling units ALOMDIW, ALOMDNW Series

Slam Shut Valves SCN

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

Performance Literature for J78. Gas Pressure Regulators ½, ¾ and 1 Sizes. Catalogue

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Bermad Model:

BGC258 Series BASOTROL Gas Valve

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

Declaration of Conformity as per Directive 97/23/EC

Pressure Reducing Valve DMV 750

1200B2 Series Service Regulators. Instruction Manual

Operating instructions - Translation of the original -

Declaration of Conformity as per Directive 97/23/EC

RTG 311 pressure regulators are included within the direct acting and balanced valve regulator class.

Gas Filters DN15 DN300. elektrogas.com EE151 06/13

Safety Relief Valve HON 835

VGF... VGH... Building Technologies Division Infrastructure & Cities Sector VGG... VGF... VGH...

HON 219 Pressure Reducer (D119a)

Transcription:

... Edition.0 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions Gas pressure regulators 0DJ, J78R, GDJ Translation from the German 008 009 Elster GmbH Contents Gas pressure regulators 0DJ, J78R, GDJ.. Contents.............................. Safety................................. Checking the usage..................... Intended use........................... Type code 0DJ......................... Type code J78R......................... Type code GDJ.......................... Part designations........................ Installation............................ Tightness test.......................... 3 Changing the outlet pressure p a.............. 3 Maintenance........................... 3 Replacing the spring on J78R, GDJ........ Replacing the diaphragms on J78R, GDJ... Technical data.......................... Declaration of conformity............... Spring table............................ 7 Contact............................... 8 Safety Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. These instructions can also be found at www.docuthek.com. Explanation of symbols,,,... = Action = Instruction Liability We will not be held liable for damages resulting from non-observance of the instructions and noncompliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb. CAUTION Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Transport On receipt of the product, check that the delivery is complete (see Part designations). Report any transport damage immediately. Storage Store the product in a dry place. Ambient temperature: see Technical data. GB GB-

GB Checking the usage Intended use Gas pressure regulators 0DJ, J78R and GDJ serve to maintain a constant outlet pressure p a despite changing gas flow rates and inlet pressures p e in gas pipelines. This function is only guaranteed when used within the specified limits see [Technical data p. ]. Any other use is considered as non-compliant. Type code 0DJ Code 0DJ L Z Description Gas pressure regulator For air only (without approval) Set to 80 mbar Type code J78R Code Description J78R Gas pressure regulator 0 Without measuring connection Screw plug at the inlet -L For air only (without approval) Type code GDJ Code Description GDJ Gas pressure regulator 0 Nominal size R Rp internal thread 0 p e max. 00 mbar -0 - Without measuring connection Pressure test nipple at the inlet L For air only (without approval) Part designations 0DJ J78R, GDJ 3 3 GDJ 0 0 7 3 Cover cap and adjusting screw Type label 3 Breather orifice Inlet Outlet Arrow of direction of flow 7 Measuring connection for inlet pressure p e Inlet pressure p e, outlet pressure p a and adjusting range: see type label. Installation www.kromschroeder.com D-908 Osnabrück, Germany GDJ CAUTION Please observe the following to ensure that the gas pressure regulator is not damaged during installation: Install the unit free of mechanical stress. Sealing material, cuttings and other impurities must not be allowed to get into the regulator housing. The installation location must be dry. Do not install the unit in the open air. Installation in the vertical or horizontal position, never upside down. The outlet pressure p a is set at the factory with the spring dome pointing vertically upwards. If the gas pressure regulator is installed with the spring dome in the horizontal position, check and adjust the outlet pressure p a, see [Changing the outlet pressure pa p. 3]. Install a filter upstream of the unit, in order to protect it against impurities in the pipe. The housing must not be in contact with masonry, minimum distance 0 mm. Remove the screw caps. 7 Note direction of flow: see arrow on the housing. 3 Install using approved sealing material. Use an appropriate spanner do not used the spring dome as a lever. GB-

Tightness test Also after maintenance. Block the pipeline at the inlet and outlet. 0DJ Slowly apply inlet pressure p e max. 00 mbar. To apply pressure, use a hand pump at the measuring connection of a neighbouring device. Since the 0DJ does not have zero shut-off, the outlet pressure does not need to be applied separately. 3 Changing the outlet pressure p a Measure the outlet pressure p a. Remove the cover cap. 3 Turn the setpoint adjuster: 0DJ, J78R, GDJ GB GDJ 0 0 3 mm 7 Relieve the inlet pressure p e. J78R, GDJ Slowly apply inlet pressure p e. (p e :. p e max., see type label) 3 Slowly apply outlet pressure p a. (p a :. p a max., see type label) To apply pressure, use a hand pump at the measuring connections of the pressure regulator or at the measuring connections of neighbouring devices. CAUTION First apply the inlet pressure p e then the outlet pressure p a. The inlet pressure p e must always be equal to or higher than the outlet pressure p a. In the event of non-compliance with the sequence, the compensation diaphragm will reverse. 8 Relieve the outlet pressure p a. 9 Relieve the inlet pressure p e. 7 Clockwise: higher outlet pressure, anti-clockwise: lower outlet pressure. Clearly mark the adjusted value on the regulator. If the required outlet pressure p a cannot be adjusted on J78R or GDJ, see [Replacing the spring on J78R, GDJ p. ]. No other springs are available for the 0DJ. Replace the cover cap. Maintenance In order to ensure smooth operation: check the function annually, or every six months if operated with biologically produced methane. Request different outputs on the burner in order to change the flow rate. Close the manual valve at the inlet a little in order to change the inlet pressure p e. Despite changing flow rates and inlet pressures p e (within the capacity range of the pressure regulator), the outlet pressure p a must remain constant (± %). J78R, GDJ only 3 Reduce the capacity to low-fire rate and close the valve downstream of the pressure regulator. Approx. 30 seconds after the valve has been closed, the outlet pressure p a should not increase significantly. All types Check the tightness of the pressure regulator during operation to detect possible leaks due to hardened rubber materials. GB-3

GB If a leak is found, replace the rubber materials see [Replacing the diaphragms on J78R, GDJ p. ]. 7 Then check for tightness once again. Replacing the spring on J78R, GDJ Various outlet pressure ranges can be reached by using different springs on J78R and GDJ: Choose a spring according to the outlet pressure range see [Spring table p. 7]. Remove the cover cap. J78R, GDJ 3 Replacing the diaphragms on J78R, GDJ Diaphragms and seals are subject to ageing, especially in the case of long-term use in the upper ambient temperature range. Spare parts can be found on the PartDetective DVD. On the 0DJ, replace the complete pressure regulator. Shut off the gas supply. J78R, GDJ 3 7 GDJ 0 0 WARNING The taut spring can pop out when opening the spring dome and lead to injury. Therefore, decompress the spring as far as it will go before opening. Then turn back x to relax the spring counter bearing. 3 3 mm x 8 0 9 GDJ 3 7 8 Insert new spring. 9 Follow the reverse procedure when reassembling. All types 0 Set the outlet pressure see [Changing the outlet pressure pa p. 3]. Replace the cover cap. After inserting the spring, take the spring s label from the packaging and stick it below the type label on the pressure regulator. 3 Clearly mark the adjusted value of the outlet pressure p a on the type label. Replace all diaphragms and sealing elements, except the valve seat. 7 Follow the reverse procedure when reassembling. GB-

GDJ 0 0 3 8 3 mm 7 9 7 0 3 8 Replace all diaphragms and sealing elements. 9 Follow the reverse procedure when reassembling. All types 0 Check tightness and function see [Maintenance p. 3]. Set the outlet pressure see [Changing the outlet pressure pa p. 3]. Replace the cover cap. x Technical data Types of gas: town gas, natural gas, LPG (gaseous) and biologically produced methane, 0DJ L, J78R..L and GDJ..L for air only. Pressure regulator to EN 88, Class A, Group Ambient temperature: -0 to +0 C. Housing: aluminium, diaphragms: Perbunan. 0DJ Z Inlet pressure p e : max. 00 mbar. Outlet pressure p a : 3 90 mbar, set to 80 mbar. Weight: 0. kg. Connecting thread: Rp / to ISO 7-, DN 8. Valve seat: POM, valve disc: POM. J78R Measuring connection with screw plug Rp /8 at the inlet on the right-hand side (option). Inlet pressure p e : up to 00 mbar. Outlet pressure p a : mbar. The outlet pressure p a is adjusted by inserting different springs, see [Spring table p. 7]. It is pre-set at the factory to 0 mbar (black spring). Weight: 0. kg. Connecting thread: Rp / to ISO 7-, DN. Valve seat: Perbunan, valve disc: POM. GDJ Inlet pressure p e : up to 00 mbar. Outlet pressure ranges: GDJ : mbar, GDJ 0 to 0: 0 mbar, GDJ 0: 00 mbar. The outlet pressure range is reached through the use of different springs, see [Spring table p. 7]. The regulators are pre-set at the factory to 0 mbar. Control range: 0:. Connecting thread: Rp to ISO 7-. Valve seat: aluminium, valve disc: Perbunan. Service life The Pressure Equipment Directive (PED) and the Energy Performance of Buildings Directive (EPBD) demand regular checks on and maintenance of heating systems, in order to ensure a high level of use in the long term, a clean method of operation and safe function. The service life on which the construction is based, hereinafter referred to simply as the service life, is compiled from the relevant standards. You can find further explanations in the applicable rules and regulations and on the afecor website (www.afecor. org). This information on service life is based on using the product in accordance with these operating instructions. GB GB-

GB The product must be serviced at regular intervals. Once the specified service life has been reached, the safety-related functions must be checked in accordance with the section entitled [Maintenance p. 3]. If the product passes the aforementioned function tests, you can continue to use it until the next scheduled maintenance operation. At this point, these tests must be repeated. If the product fails one of the aforementioned tests, it must be replaced immediately. This procedure applies to heating systems. For thermoprocessing equipment, observe national regulations. Service life (based on date of manufacture) in accordance with EN 3 and EN 88 for 0DJ, J78R and GDJ: years. Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life (please contact manufacturer). Declaration of conformity We, the manufacturer, hereby declare that the products 0DJ, marked with product ID No. C87AO7, J78R, marked with product ID No. C87AO, and GDJ, marked with the product ID No. CE-0087AO, comply with the requirements of the listed Directives and Standards. Directives: 90/39/EEC Standards: EN 88 The relevant products correspond to the type tested by the notified body 0087. The air pressure regulators 0DJ L, J78R..L and GDJ..L are not subjected to this Directive. The production is subject to the surveillance procedure pursuant to DIN EN ISO 900 according to annex II, paragraph 3 of Directive 90/39/EEC. Elster GmbH Scan of the Declaration of conformity (D, GB) see www.docuthek.com GB-

Spring table Outlet pressure p a [mbar] Marking D [mm] d [mm] L [mm] Coils Order No. J78R 9 green/red.8. 0. 030890 9 7 yellow.8. 0 030890 3* black... 0308903 3 orange.8. 030890 3 brown.0.3 0. 030890 light green/light blue 0.9. 0. 0308907 GDJ yellow.8. 0 0308907 0 0 black... 0308907 8* orange.. 03089077 0 brown.0.3 0. 03089078 0 light green/light blue 0.9. 0. 03089079 GDJ 0, GDJ yellow 3... 0308908. * black 3.0.0 7 0308909. 3 orange 3.8.8 99 9.7 0308900 7 yellow/black 3.8.3 8. 030890 70 00 pink/gold 3.0. 80 7 030890 90 0 yellow/orange 3.3.8 7. 03089080 GDJ 0 red/yellow 3.. 8. 0308903. * red/black 3.3.3 89 0. 030890. 3 red/orange 3.3.3 9 030890 7 yellow/orange 3.3.8 7. 030890 70 00 pink/silver 3..8 00 7 0308907 90 0 grey/gold 3. 3. 98.7 0308908 GDJ 0 dark blue/yellow 3.. 80 0. 0308908. * dark blue/black 3.. 90 0 0308909. 3 dark blue/orange 3.. 8 0308900 7 yellow/dark green 3. 3.0 87.8 030890 70 00 grey/gold 3. 3. 98.7 030890 * Standard spring GB GB-7

GB Contact If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from Elster GmbH. We reserve the right to make technical modifications in the interests of progress. GB-8 Elster GmbH Postfach 8 09, D-908 Osnabrück Strotheweg, D-90 Lotte (Büren) T +9-0 F +9-370 info@kromschroeder.com, www.kromschroeder.com