A PILOT STUDY ON HYPOXIC AIR PERFORMANCE AT THE INTERFACE OF FIRE PREVENTION AND FIRE SUPPRESSION

Similar documents
Effects of low oxygen concentration on ignition and combustion

Ventilation Effects on Compartment Fire Characterization

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany

Ignition Sensitivity of Nonmetallic Materials in Oxygen-Enriched Air NITROX : A Never Ending Story in SCUBA Diving?

Dust explosion severity characteristics of Indonesian Sebuku coal in oxy-fuel atmospheres

Fire and Safety for Offshore drilling and production Ajey Walavalkar ANSYS Inc.

BASIC FIRE SCHOOL VENTILATION, SALVAGE & OVERHAUL

Fires and Explosions: What You Need to Know to Prevent Them

6-5 Maintenance Manual

Active Fire Prevention by Oxygen Reduction Systems

BASF Flash Fire FRC Assessment Tool

Influence of Initial Temperature on Explosion Severity Parameters of Methanol/Air Hybrid Mixture Measured in 1-m 3 Vessel

Fire test of ventilated and unventilated wooden façades

2018 STATEMENTS OF FACT MINE RESCUE. 1. To test for methane, use a methane detector or chemical analysis.

I.CHEM.E. SYMPOSIUM SERIES NO. 97 THE FLASH-BACK HAZARD IN STACKS DISCHARGING FLAMMABLE GASES

CALMO

Professor of Clinical Anesthesiology, state University of New York, Health Science Center at Brooklyn, 450 Clarkson Avenue, Box 6, Brooklyn, NY

Opposed-Flow Flame Spread in a Narrow Channel Apparatus over Thin PMMA Sheets

THE MITIGATION OF HYDROGEN EXPLOSIONS USING WATER FOG, NITROGEN DILUTION AND CHEMICAL ADDITIVES

WHITEPAPER: ATEX IN PRACTICE (EXPLOSION PROTECTION)

TEST REPORT. Expanded Polystyrene Nominal Mass per Unit Area/Density : Nominal Thickness : 75mm

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ?

Absorption - The process of contacting a vapor and gas stream with an absorbing liquid to remove specific materials from the gas stream.

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels

Engineering Models for Vented Lean Hydrogen Deflagrations

HYPOXIC AIR FIRE PREVENTION SYSTEM TECHNICAL SPECIFICATION

Burner Management System DEMO Operating instructions

NIOSH Flowback Study. William G. Burket, CFPS

The Influence Of The Burning Process At The Thermoelectric Power Station On Ecology And The Ways Of Reducing The Harmful Wastes Into The Atmosphere

WP2 Fire test for toxicity of fire effluents

Applications Note: Use of "pentane equivalent" calibration gas mixtures

FLAME SPREAD BEHAVIOR OVER COMBINED FABRIC OF COTTON/POLYESTER

Experimental Study of the Fire Mass Loss Rate in Confined and Mechanically Ventilated Multi-Room Scenarios

Guidance on room integrity testing and its interpretation

SIMULATIONS OF HYDROGEN RELEASES FROM A STORAGE TANKS: DISPERSION AND CONSEQUENCES OF IGNITION

BS EN ISO : 1999

1.0 Scope and Application. 2.0 Definitions. Cal Poly Risk Management Confined Space Program Page 1

Insulation. SOLKANE 365 SOLKANE 365/227 Flammability characteristics and handling. Solvay Special Chemicals

HYDROGEN RISK ANALYSIS FOR A GENERIC NUCLEAR CONTAINMENT VENTILATION SYSTEM

PROTEGO Braunschweiger Flammenfilter GmbH

OS2 F R A M E S E R I E S

USER S INFORMATION MANUAL

An investigation of horizontal opening effect on pool fire behavior in a confined compartment: A study based on global equivalence ratio

Wagner Fire Safety Management Consultants

Experimental Fire Tower Studies on Mechanical Pressurization to Control Smoke Movement Caused by Fire Pressures

the Fire Tetrahedron Identify the relationship of the concentration of

ARCHIVED. Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source. Prepared by the Department of Building and Housing

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS

Safety Data Sheet. Zero Air 1 PRODUCT AND COMPANY IDENTIFICATION. Manufacturer NorLab a division of Norco 898 W. Gowen Rd.

mass of container full of air = g mass of container with extra air = g volume of air released = cm 3

CONFINED SPACE PROGRAM

CONFINED SPACE ENTRY PROGRAM

MATERIAL SAFETY DATA SHEET

NGN Series nitrogen generator

Explosion Isolation. No matter what happens - nothing happens. / RICO Slide Valve RSV-D, RSV-G, RSV-P

Safetygram #33 The Hazards of Oxygen and Oxygen- Enriched Mixtures

High-Pressure Boiler Inspection Procedures: A Complete Checklist

EFFECTS OF WATER SPRAYS AND SCRUBBER EXHAUST ON FACE METHANE CONCENTRATIONS

1. Add a new Annex B.8 to read as follows:

LABORATORY EXPERIMENTS ON WAVE OVERTOPPING OVER SMOOTH AND STEPPED GENTLE SLOPE SEAWALLS

Smoke and gas tightness of Hilti Firestop products

Analysis of Foot Pressure Variation with Change in Stride Length

Deborah Houssin-Agbomson, Jean-Yves Letellier, Philippe Renault, Simon Jallais

The analysis of complex multicomponent

Study on Intensity of Blast Wave Generated from Vessel Bursting by Gas Explosion

Measurement of Representative Landfill Gas Migration Samples at Landfill Perimeters: A Case Study

Safe Use Instructions Sheet * Revised: 11 April 2016 Printed: 11 April 2016 Page 1 / Identification of the Substance or Mixture and the Company

Hot Work Permits. Why are we here? Every year fires occur, which could have been prevented had employees used appropriate fire prevention measures.

ICHEME SYMPOSIUM SERIES NO. 144

Practical Modelling & Hazard Assessment of LPG & LNG Spills

Temperature Influence on the Flammability Limits of Heat Treating Atmospheres

SAFETY DATA SHEET Product Name: Monk Disinfectant Wipes

Confined Spaces OSHA 1926 AA

FIRE FIGHTER II JPR: FFII-1A

Usage Policies Notebook for NanoFurnace Furnace (EasyTube 3000 System)

Lesson 2C - Weather 2C-1-S190-EP

Wind Directional Effect on a Single Storey House Using Educational Wind Tunnel

Material Safety Data Sheet: PVC Suspension Resin

Technical Manual. Sensepoint XCD Gas Detector

Gas Accumulation Potential & Leak Detection when Converting to Gas

Figure 1 Schematic of opposing air bearing concept

Australian Wool Testing Authority Ltd - trading as AWTA Product Testing A.B.N

OUS31. Technical Information

Page: 1 Rev. Date 08/07/97 GENERIC SPUNBOND FABRIC (NO SURFACTANT) ESAPCO, 1395 JOHN FITCH BLVD, SOUTH WINDSOR, CT, 06074,

Health and Safety Executive/Local Authorities Enforcement Liaison Committee (HELA)

The Effect of Von Karman Vortex Street on Building Ventilation

ICE INDENTATION TEST ON CONSOLIDATED LAYER MODEL MADE OF SALINE AND FRESHWATER ICE BLOCKS

Numerical Modelling of Unchannelled Balcony Spill Plumes using FDS 5

MANY REQUIREMENTS - ONE SOLUTION: SCENTY control

Oxygen Flue Gas Analyzer BA 2000

Session #: Selection of Explosion Protected Equipment for Hazardous Locations

SONO 600 High-Temperature Ultrasonic Couplant

Dip Tanks Containing Flammable or Combustible Liquids Self-Inspection Checklist

Exploring the Properties of Gases

SAFETY DATA SHEET (SDS)

DYPLAST PRODUCTS UNFACED RIGID POLYISOCYANURATE FOAM SAFETY DATA SHEET DYPLAST PRODUCTS, LLC NW 38TH AVENUE MIAMI, FLORIDA 33054

Safety Data Sheet. according to Regulation (EC) No 1907/2006. Freezer BR

Material Safety Data Sheet Tungsten Metal Powder

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised

Transcription:

Stefano Chiti A PILOT STUDY ON HYPOXIC AIR PERFORMANCE AT THE INTERFACE OF FIRE PREVENTION AND FIRE SUPPRESSION The Science of Suppression November 9 th 2011 Edinburgh, Scotland, UK 1 Stefano Chiti

Contents What is Hypoxic Air Technology (HAT)? Effects of low O2 concentration on the ignition and combustion processes. Ignition property test method. Flame spread test method. Results and discussion of the test series to assess the performance of hypoxic air. Conclusions and future development. 2 Stefano Chiti

Hypoxic Air Technology (HAT): what is it? Hypoxic Air Technology: Fire prevention technology based on a continuous reduction of O 2 in the protected volumes. When even fire suppression is not acceptable. Typically 14-15 vol% O 2, 85-84 vol% N2 for fire prevention. Lower O 2 concentrations for fire suppression (consistent with gas extinguishing systems). HYPOXIC AIR 3 Stefano Chiti

Effects of low O 2 concentration on ignition and combustion Minimum Oxygen Concentration (MOC) : below MOC no combustion depends on the diluent used to reduce O2 if diluent is N2 : 4.77 C st where LFL is the Lower Flammable Limit, C st is the stoichiometric oxygen/fuel concentration 1 100 MOC = LFL 1 similar relationship also for dust clouds MOC for fire prevention is not the same as for fire suppression 4 Stefano Chiti

Effects of low O 2 concentration on ignition and combustion Ignition time: increases when lowering O2 concentration Mc. Alevy et. al.: t ign m 2/3 O 2 Kumar and Hermance: t ign m O 2 n Mikkola, Hirsch, Hsieh: PVC: +300% ignition time in O 2 = 15 vol% PMMA: + 24% ignition time in O 2 = 15 vol% Silicone elastomers: drastic increase FR PUR foam: drastic increase But it is not investigated what happens after ignition 5 Stefano Chiti

Effects of low O 2 concentration on ignition and combustion Autoignition time (AIT): increases when lowering O2 concentration Kashiwagi: 15 vol% limiting O 2 value for successful autoignition Experiments on AIT for gases: Alvares: AIT 0.25 P O 2 AIT = e E / RT [ O ] n 2 Minimum Ignition Energy (MIE): rises when decreasing O2 concentration Experiment on gases: MIE OI where Oxygen Index OI=O 2 /(O 2+ N 2 ); n = 4 (Chinn) or n = 2.5 (Von Elbe) n 6 Stefano Chiti

Effects of low O 2 concentration on ignition and combustion Flame spread velocity (V): decreases at low O2 concentrations Studies reported by Babrauskas: where n = 2 or n = 1 V m O 2 n Mass loss rate (MLR): decreases at low O2 concentrations Santo and Tewarson: MLR - 30% in O2 = 18 vol% (PMMA) Babrauskas reports: MLR'' = a m oxygen b where MLR'' is the MLR per unit of surface area, a and b are constant Heat release rate (HRR): decreases drastically if O2 concentration is low Mulholland: The heat peak decreases drastically if O2 is lowered, and this effect is greater when approaching the lowest O2 concentration at which combustion can be sustained. 7 Stefano Chiti

Effects of low O 2 concentration on ignition and combustion - discussion Hypoxic air, by lowering O 2 concentration in the air, has several benefits regarding to the ignition and combustion processes: longer ignition time higher MIE lower flame spread velocity reduced MLR Oxygen concentration <= 15vol% can prevent ignition for most solid materials (hypoxic air for fire prevention). Oxygen concentration must be consistent with the values for gas suppression systems if hypoxic air is used in suppression mode (O 2 = 12 13 vol%). 8 Stefano Chiti

Test method to assess hypoxic air performance aim 1. Investigate the ignition limiting properties of hypoxic air for fire prevention for different material configurations. 2. Investigate fire spread at different O2 concentrations (vertical material configuration - worst case). 9 Stefano Chiti

Test method to assess hypoxic air performance test room V = 10.35 m 3 H = 2.3 m Airtight room with adjoining air lock Door and observation windows. Smoke extractor fan 10 Stefano Chiti

Test method to assess hypoxic air performance equipment Nitrogen generator. O 2 sensors. Oxyacetylene premixed pilot flame. Calibrated scale. Support frame. Common specimens. 11 Stefano Chiti

Ignition test - procedure 1. Horizontal/vertical arrangement of the test specimen, flame direction. 2. Reduce O 2 concentration in the test room (O 2 constant throughout the test) 3. Regulate pilot flame. 4. The pilot flame hit the test specimen for 180 s (FET, Flame Exposure Time). 5. Remove the pilot flame and observe the test specimen response for at least 60 s (PET, Post Exposure Time). Data on test specimen mass, O2 concentration are continuously recorded during FET and PET. Consistent with BSI PAS 95, VdS 3527 12 Stefano Chiti

Flame spread test - procedure 1. Vertical array of test specimens. 2. Reduce O 2 concentration in the test room. 3. Regulate pilot flame. 4. The pilot flame hit the bottom test specimen for 180 s. 5. Observe if flames spread to the other two specimens. Data on test specimens mass, O2 concentration continuously recorded. 13 Stefano Chiti

Ignition test results Polypropylene (PP) : horizontal configuration test. Test specimen: PP box (37x25x12 cm) Ignition limiting O 2 threshold: 16.0 vol% (VdS 3527) 14 Stefano Chiti

Ignition test results Polypropylene (PP) : vertical configuration test. Test specimen: PP lid for box 15 Stefano Chiti

Ignition test results Paper: horizontal configuration test. Test specimen: rolled newspaper Ignition limiting O 2 threshold: 14.1 vol% 16 Stefano Chiti

Ignition test results ISO wood crib: horizontal configuration test. Test specimen: ISO wood crib, mini crib type, 5 layers each crib, 2 members each layer, total volume 78 cm 3. Test specimen moistened with pure alcohol. Ignition limiting O 2 threshold: 17.0 vol% (untreated wood, VdS 3527) 17 Stefano Chiti

Ignition test results Before test O 2 =15.0 vol% O 2 = 16.0 vol% O 2 = 17.0 vol% 18 Stefano Chiti

Ignition test an example O 2 = 14.9 vol% O 2 = 20.9 vol% 19 Stefano Chiti

Fire spread test - results Test specimen: two wicker boards and a newspaper arranged in a vertical array. 20 Stefano Chiti

Fire spread test - results O 2 = 15.9 vol% O 2 = 20.9 vol% 10s 60s 300s 21 Stefano Chiti

Test series - discussion Most test specimens did not ignite during the test performed at the lowest O 2 concentration (PP, paper). Exception: wood crib (note: extremely severe heat source, alcohol). Difficult to ignite between 16.0 vol% and 17.0 vol% of O 2 concentration, flame and burning self-extinguished during PET, reduction in mass loss. No flame spread in the test performed at O 2 = 15.9 vol%. For the majority of the materials tested there is a sort of a response threshold in terms of burning between 17.0 vol% and 18.0 vol% of O 2 concentration. 22 Stefano Chiti

Conclusions 14.5 O 2 15.0 vol% : hypoxic air limits ignition, prevents flame spread for all investigated materials. 16.0 O 2 17.0 vol%: hypoxic air does not fully prevent ignition but does lessen fire damages. Accurate assessment of materials, configuration and hazards to determine the correct O 2 concentration. More research to exploit and optimize further the potential of Hypoxic Air Technology. 23 Stefano Chiti

Acknowledgments Prof. Paolo Tartarini, University of Modena and Reggio Emilia, Department of Mechanical and Civil Engineering. Mr. Geir Jensen, COWI AS Thank you for your attention! 24 Stefano Chiti