COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

Similar documents
COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

S Surge Arresters

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

Effective May 2017 Supersedes August 2005 (S )

S Loadbreak Apparatus Connectors WARNING: WARNING:

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Inspection Recommendations

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

Norrsken Family Booklet

Permanent Roof Anchors

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

BS Series Basket Strainer

Model No Product Name Handpiece Only Complete System

FLANGED TWO-PIECE BALL VALVES

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

FLANGED TWO-PIECE BALL VALVES

Accu-Tab Systems 1000 Series by Axiall Corporation

USER MANUAL FLOW SELECTOR PM1000 SAVE THESE INSTRUCTIONS. Federal (USA) law restricts this device to sale by or on the order of a physician.

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

This document to be used with Hurley traditional Davits

TITAN FLOW CONTROL, INC.

Retractable Hose Reel with 3/8" x 50' PVC Hose

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

Model ASSEMBLY and OPERATING INSTRUCTIONS

Installation and Operation Manual

2000 lb manual winch

Accu-Tab Systems 2000 P Series by Axiall Corporation

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-400. Club Volleyball Gear

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

Hygienic Bubble Trap Installation and Operations Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-300. Club Volleyball Gear. For fixed-height Basketball Hoop Systems

Yoke Block Instruction Manual

RGC-IR Remote Gas Calibrator for IR400

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

COMPACT METAL bender 99826

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Bimini Top, Bimini Top Plus for Jeep Wrangler Vehicles Items # , # and #

OPERATOR'S & PARTS MANUAL

Mini Pod Press. #78H-M2 Mini Pod Press Manual-R1

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

U S E R M A N U A L CAUTION. SAVE THESE INSTRUCTIONS Federal (USA) law restricts this device to sale by or on the order of a physician.

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

6 digital caliper with case

USER INSTRUCTION MANUAL CONCRETE BOLT ANCHORAGE CONNECTOR

Accu-Tab PowerBase 3012AT by Axiall Corporation

Triple Tine Mechanical Grapple

MAVERICK FOOSBALL TABLE

Installation, Operation and Maintenance Manual

Installation and Service Manual

Installation, Operation and Maintenance Manual. TSV Temperature Shut-off Valve SPD Rev. 6 10/07

GETZ EQUIPMENT INNOVATORS PART No. 4G59678 CARBON DIOXIDE MINI PUMP FOR EXTINGUISHER SERVICE (Revised )

Coiling Tube with Twist-Proof Fitting

Transcription:

Fusing Equipment MN132023EN Effective November 2016 Supersedes June 2010 (S240-70-1) EL Bay-O-Net Current-Limiting Fuse Installation Instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... ii SAFETY FOR LIFE... iv SAFETY INFORMATION... iv Safety instructions...iv PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Acceptance and Initial Inspection...1 Handling and Storage...1 Quality Standards...1 Additional Information...1 Fuse Application...1 INSTALLATION INSTRUCTIONS.... 2 OPERATION INSPECTION.... 2 iii

EL Bay-O-Net Current-Limiting Fuse! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.2 iv

EL Bay-O-Net Current-Limiting Fuse Product information Introduction Eaton s Cooper Power Series EL Bay-O-Net Current-limiting fuse assembly is designed to be used to mount the ELS current-limiting fuse in fluid-filled distribution apparatus. The fuse assembly provides the operating convenience of Eaton s Cooper Power Series versatile Bay-O-Net expulsion fuse with the energy-limiting capabilities of the currentlimiting fuse. 5.0 4.25 45 LOCKNUT TANK WALL GASKET MAX. OIL LEVEL 0.75.156R 4.625 DIA. HOLE DETAIL Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. 5.88 2.5 C MIN. OIL LEVEL 2.5 DIA. Acceptance and Initial Inspection Each fuse is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the fuse and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. A B 3.44 Handling and Storage Be careful during handling and storage of the fuse to minimize the possibility of damage. If the fuse is to be stored for any length of time prior to installation, provide a clean, dry storage area. Quality Standards ISO 9001Certified Quality Management System. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Figure 1. Bay-O-Net assembly shows application fluid level and dimensional information. Fuse Application When selecting the proper EL Bay-O-Net for each installation, the voltage rating, continuous current, and dimensions must be taken into account. Select the proper Bay-O-Net specifications based on Table 1. Table 1. Specifications for EL Bay-O-Net Fuse Assembly Voltage Rating (kv) Catalog Number Use Fuse Number Dimensions Inches (mm) A B C Continuous Current Rating (A) Live Spacing to Ground 8.3 4004697B01M 3533--M11 8.22 10.73 10.91 100 2 in. 15.5 4004697B03M 3534--M11 16.29 16.41 16.66 100 3 in. 23 4004697B03M 3535--M11 16.29 16.41 16.66 100 4 in. 1

EL Bay-O-Net Current-Limiting Fuse Installation Instructions The fuse assembly is mounted through the transformer tank wall for sidewall mount. A 4-5/8 hole with keyed slot for use in sidewall underoil application is gasketed on the inside of the tank with an external locking nut. All inner gasket surfaces of the tank must be free of burrs. The fuse assembly is designed for use in maximum operating temperatures of (in oil) at 140 C, and (air exposure) at 65 C. IMPORTANT Accompanying decals should be prominently displayed at or near location of Bay-O-Net as a warning to service personnel. Failure to do so will constitute a waiver of all warranty and indemnity obligations which may be attributable to Eaton. If the fuse is installed, the plastic follower assembly supplied with the housing should be installed on the lower end of the fuse. Otherwise, the follower assembly should be attached to the Bay-O-Net operating handle so the user can assemble it to the fuse. Operation Inspection Torque Requirements To Seal Sealing requirements are obtained by first handtightening the locknut, and then continuing an additional 1/4 to 1/3 revolution. Clearances Mechanical External latch clear for shotgun stick operation. Table 2. Dialectric Clearances Clearance to Ground or Between Dielectric (kv BIL) Phases (in oil) 96 1.1 125 1.5 150 2.5 Mechanical Strength Strip Point of Threads (housing) in excess of 400 in-lbs. Lead Training Connect voltage source through bottom leads of housing and transformer coil leads to upper contacts of housing. All leads should remain below the oil level. Use mounting studs fastened to housing tabs to make terminal connections. 2

EL Bay-O-Net Current-Limiting Fuse T his page is intentionally left blank. 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN132023EN Rev. 0 November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.