EC type-examination certificate UK/0126/0065 Revision 1

Similar documents
United Kingdom of Great Britain and Northern Ireland

United Kingdom of Great Britain and Northern Ireland

Centrifugal Gas Separator ZGA. Operating Manual. Dimensions, weights and other technical data are subject to changes.

Certificate of Approval. No 5/6B/211

EC type-examination certificate UK/0126/0126

Compiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.

Vehicle- or rack-mounted liquefied gas meters, pump supplied

TRZ 03-K Volumeter. Proven Technology. Superior Performance. TRZ 03-K Volumeter is a Turbine Gas Flowmeter for Secondary Gas Metering.

Vehicle-mounted meters, pump supplied

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

pren CEN standard-draft pr EN 12261

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

EC type-examination certificate UK/0126/0014 Revision 6

INTERNATIONAL OIML R 32 RECOMMENDATION. Rotary piston gas meters and turbine gas meters ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

Flow divider designs MTL

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

M-06 Nitrogen Generator (Nitrogen Making Machine)

TF- & DM-Series. Turbineflowmeter

P U B L I C N O T I C E

MECHANICAL BULKMETERS BM Series

New! ProFlow. Sliding Vane Meters DN (½ - 2 ) _ 142. Product Bulletin

VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES 10

Air Eliminators and Combination Air Eliminators Strainers

Model DE-1, VDE-1 and DE-2 Air Release Heads

Technical Datasheet ZHA Series Gear Flow Meters Aluminum Version with ball bearing for lubricating media

Metering Code Gas TSO, measurement by connected party Effective from to the present

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Inflatable Packer Single & Double. Single & Double Packer Dimension. Wireline Packer. Water Testing Packer (WTP) Packer

ZHM ST Series. Technical Datasheet. Gear Flow Meters for lubricating, non lubricating, abrasive and corrosive fluids

Product Information. Three in One: Gas Meter Tariff Device Volume Corrector. Ultrasonic Gas Meter ECOSONIC X12

RMG Meßtechnik GmbH. Publication No E

CAST IRON SAFETY VALVE TYPE 6301

Size 6 up to 31.5MPa 1) up to 25 L/min

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

Radar, Ultrasonic and RF Level Transmitters

Displacement 12, , Maximum flow rate (at 1450 rpm) bar.

DMX 3 - DMX 3 MF INSTALLATION OPERATION MAINTENANCE. Your distributor : TECHNICAL INSTRUCTIONS (e) Revision

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

DK46 - DK800 Supplementary instructions

WaterSense Specification for Spray Sprinkler Bodies. Version 1.0

Circulating Lubrication Systems (Oil)

Summary of the MRA LPG Codes of Practice

Cover Page for Lab Report Group Portion. Pump Performance

Compressors. Basic Classification and design overview

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Electronic Turbine Meter TERZ 94

KRONES filling systems for beer Filling of glass containers and cans

Introduction to Pumps

Key Features & Advantages of JEHA MK IV (5,000 PSI Hydraulic Test Stands)

Variable Displacement Double Pump A20VO. Series 1, for open circuits Axial piston - swashplate design, Back to back - design

Coriolis Mass Flow Meter

Restriction Orifice. Single or Multi Stage Orifice to. Reduce Pressure or. Limit the Flow Rate

SINGLE VALVE WITH LOW-FLOW BYPASS

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

Si C132. Safety valves for pressure relief in accordance to PED, DIN/EN and ASME. Engineering GREAT Solutions

TYPE ECS SEAL METAL BELLOWS DRY-RUNNING SECONDARY CONTAINMENT Technical Specification

Circulating Lubrication Systems (Oil)

Instruction Manual Dräger MSI P7 and MSI P7 plus

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

Additive Injectors. AccuPlus. Installation and Operations. The Most Trusted Name In Measurement

SIKA Ba_ODWT15_en 05/2018. Operating manual for oil deadweight tester 0.015% accuracy ODWT15

Supplementary Operator s Manual 42/24-14 EN Rev. 3

Smart Water Application Technologies (SWAT)

PRODUCTS CATALOGUE 2017 / Torino - Strada Settimo 388/15 Tel (+39) /43 Fax (+39)

SIHI LPH-X - Liquid Ring Compressors

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

BACK PRESSURE / SUSTAINING

ARCHIVED. Compliance Document for New Zealand Building Code Clause G11 Gas as an Energy Source. Prepared by the Department of Building and Housing

Instructions for Use

PRESSURE TRANSDUCERS WITH UNIFIED (4-20) ma OR (10-50) ma OUTPUT SIGNAL

Air Eliminator Series

Pressure Equipment Directive (PED) 97/23/EC Page 033 of 124

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

G REQUIREMENTS FOR THE INSTALLATION OF GAS BOOSTERS, MICROTURBINES AND ASSOCIATED SYSTEM PROTECTIVE DEVICES

Guideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society

BACK PRESSURE / SUSTAINING

Fixed Displacement Pump KFA for commercial vehicles in open circuits

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

IMPLEMENTATION OF EIGA CARBON DIOXIDE STANDARDS

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

ECS Protector Nitrogen Inerting Vent (PAV-WN)

Axial piston pumps type PVC

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group "Pressure"

Axial piston pumps type PVC

É DANAK PROD Feg.No.7025

What is LPG? Released Energy in the narrowest area. Clean and sure in the practise

Displacement. from 2 up to 6 sections balanced, unbalanced from 0.8 to 31 ccm FLOW DIVIDERS

MANUAL. Additive Injector AccuPlus. Installation / Operation Manual. MN05002E Issue/Rev. 0.2 (9/17)

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

PREVENTION OF EXCESSIVE PRESSURE DURING FILLING OF CRYOGENIC VESSELS

DEUTSCH. Flüssigkeits- Mengenmesser FMO. Seite Flow Meter FMO. Page Compteur volumétrique. Page 43-63

LPG DRIVER ATTENDED TRANSPORT LOADING

"BS An overview of updates to the previous ( 2009 ) edition. Andrew Wrath & BS7965 Working Group

Another convenient term is gauge pressure, which is a pressure measured above barometric pressure.

Rotor Gas Meter. Creators in flow

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Design. Pompetravaini-NSB API SB Liquid Ring Compressor for Gas Processing. Working Principle

(Refer Slide Time: 2:16)

TEST SPECIFICATION NYT-909-C

DIVERLESS SUBSEA HOT TAPPING OF PRODUCTION PIPELINES

Transcription:

UK/0126/0065 MI-005 EC type-examination certificate UK/0126/0065 Revision 1 issued by: The National Measurement Office Notified Body Number 0126 In accordance with the requirements of the Measuring Instruments (Liquid Fuel delivered from Road Tankers) Regulations 2006 (SI 2006/1259) and the Measuring Instruments (Non- Prescribed Instruments) Regulations 2006 which implement, in the United Kingdom, Council Directive 2004/22/EC, this EC type-examination certificate has been issued to: Toptech Systems NV Nateus Business Park Nieuwe weg 1 - Haven 1053 2070 Zwijndrecht (Antwerp) Belgium in respect of an interruptible measuring system for liquids other than water and having the characteristics described below. Designation : MultiLoad II/(measurement transducer installed) Qmin-Qmax : see paragraph 3.1 Minimum measured quantity : see paragraph 3.1 Accuracy class : 0.5 Mechanical environment : M2 Electromagnetic environment : E2 Climatic environment : -25 C to +55 C open, condensing Temperature range of liquid : -10 C to +50 C Intended for measurement of : liquid petroleum products, bio-fuels and ethanol The necessary data (principal characteristics, alterations, securing, functioning etc) for identification purposes and conditions (when applicable) are set out in the descriptive annex to this certificate. This Revision replaces previous versions of this certificate. Issue Date: Valid Until: Reference No: 03 May 2011 22 February 2020 T1154/0001 Signatory: for P R Dixon Chief Executive National Measurement Office Stanton Avenue Teddington TW11 0JZ United Kingdom Tel +44 (0)20 8943 7272 Fax +44 (0)20 8943 7270 Web www.bis.gov.uk/nmo 0135

Descriptive Annex 1 INTRODUCTION The instrument is an interruptible meter measuring system for loading or unloading road tankers and comprises the MultiLoad II electronic calculator/indicator (flow computer) and a choice of measurement transducers (meter sensor & transducer) and gas elimination devices as specified below. 2 CONFIGURATION OF THE MEASURING SYSTEM 2.1 Essential parts 2.1.1 Measurement device The measurement device comprises the meter sensor and a transducer as listed in section 4.1. 2.1.2 Electronic calculating/indicating device (flowcomputer) The flow computer is the MultiLoad II, manufactured by Toptech Systems. See Evaluation Certificate TC7311 for details. 2.1.3 Gas elimination device The gas separators/gas elimination devices are listed in section 4.3. 2.2 Conditional parts 2.2.1 Temperature sensor If a temperature sensor is used, it must be a class A or B PT100 sensor to measure the liquid temperature. The temperature sensor, if fitted, must be installed within 1 metre upstream or downstream of the measuring transducer. The measured liquid temperature can be used by the flow computer to calculate the delivered volume at standard temperature (15 C). 2.3 Non-essential parts - Pump(s), pipe work and connection - Isolating valves - Vent-off valves 2

3 CHARACTERISTICS OF THE MEASURING SYSTEM 3.1 Essential characteristics The essential characteristics of the system are stated on page 1 of this certificate. Q min - Q max See table in section 4.1.3 (1) Maximum working pressure: 10 bar (P max ) Minimum delivery (MMQ): 200 L or, 500 L (2) Type of liquid Liquids other than water of low viscosity, except liquefied gases, including biofuels and ethanol. The specific liquid viscosities are dependent on the measurement transducer being used, see table 4.1.3. (1) any measurement transducer listed in section 4.1.3 may be used in conjunction with a gas separator device listed section 4.3.1 providing the maximum rate of flow is not greater than the maximum rate of flow of any component of the system. (2) when using the Stokota BR-150, the MMQ is 500L. 3.2 Conditional characteristics 3.2.1 Hydraulic circuit An example of a possible basic outline of the hydraulic circuit and the essential components are shown in figure 1, before a delivery is started the system shall be free of air. 3.3 Non-essential characteristics 3.3.1 The measuring instrument is utilised as top loading or bottom loading. 3.3.2 The shape of the name plate. 3.3.3 Optional (additive) injection points may be present. If present they are located upstream of the measurement sensor. 3.3.4 Some parts of the system may be used as a common part for multiple measuring instruments. For example the pump can be used to feed multiple instruments. 3

4 MAIN COMPONENTS/PARTS OF THE MEASURING INSTRUMENT 4.1 Measurement device The measurement transducers have the following essential parts: 4.1.1 FMC Model: Prime4 (including encoder) Measuring chamber: This is a rotary positive displacement type. The measuring chamber consists of a cylindrical housing with an inner rotor having two evenly spaced blades which rotate as liquid flows through the meter (the Rotor revolves on Tungsten carbide bearings); the motion of the blades is controlled with a special cam. Measuring chambers of volume are formed between the two blades, the rotor, the housing and the top cover. Electronic pulser/encoder: The exciter gear, integral part of the rotor, converts rotation of the rotor into electrical pulses together with a pulse pickup located in a well on the side of the meter cover. 4.1.2 FMC(Smith) models L(H)S-42 or SE42 or E3, (L)SF60 or F4 or VF60 & S35 & S45 & (L)ST160 or T40 Measuring chamber: This is a rotary positive displacement type. The measuring chamber consists of a cylindrical housing with an inner rotor having two evenly spaced blades which rotate as liquid flows through the meter (the Rotor revolves on ball bearings); the motion of the blades is controlled with a special cam. Measuring chambers of volume are formed between the two blades, the rotor, the housing and the top cover. 90 drive gear: On the output shaft of the rotor a drive gear can be mounted. An adjustment device is not present in this drive gear. The FMC(Smith) measurement transducers may be used with any of the electronic pulsers/encoders approved within this certificate or any other approved pulser, including: Internal pulser of Prime 4 Eltomatic type 01/09 Eltomatic type 01/08 4

4.1.3 The essential characteristics of the measurement transducers are: Model designation Flow rate range Viscosity Q min - Q max (L/min) mpa.s L(H)S-42 /SE42 / (E3) 150-1900 0.3-17 8-350 25-1000 500-10000 Prime 4 190-3400 0.3-17 3.5-120 8-350 100-1000 500-10000 (L)ST 160/(T40) 50-1600 0.3-17 25 1000 500-10000 S35 150-1900 0.3-17 8-350 25-1000 500-10000 S45 200-3000 0.3-17 8-350 25 1000 500-10000 (L)SF60 / F4 / VF60 200-3000 0.3-17 8-350 25 1000 500-10000 Non essential parts of the measurement transducer: - An optional filter can be mounted at the inlet. 4.2 Gas Separator device These can be of following makes and have following essential parts. NOTE : If one or more degasser(s) is/are shared across multiple measurement instruments, one needs to verify that either the pump(s) to feed the installation cannot exceed the max flow of the degasser(s) used, or that the total maximum flow the measuring systems are capable of flowing does not exceed the maximum flow of the degasser(s) used. 4.2.1 FMC, type VDR The inlet and outlet of the body (cylinder) are tangentially constructed. This forces the 5

liquid into a rotational movement. This centrifugal movement in conjunction with a decrease in flow velocity and pressure causes air and gas to be segregated from the liquid and released subsequently through the automatic operated float valve(s). This valve(s) is placed on top of the air separator body. 4.2.2 Stokota, type BR150 The inlet and the outlet of the body (cylinder) are tangentially constructed. This forces the liquid into a rotational movement. This centrifugal movement in conjunction with a decrease in flow velocity and pressure causes air and gas to be segregated from the liquid and released subsequently through the automatic operated float valve(s). This valve(s) is placed on top of the air separator body. 4.2.3 S.A.M.P.I. Spa, EGS_1 & EGS_2. As described in Evaluation Certificate TC 7329. 4.2.4 Bopp & Reuther Messtechnik GmbH, type ZGA The gas separator is made of a welded pressure vessel with an integrated automatic float-deaeration device. The liquid enters tangentially at the upper port, resulting in a swirling flow inside the gas separator. This swirling motion is sustained by the tangential outgoing liquid at the outlet port. The distribution of pressure in the swirling flow causes any air or gas to escape via the ventilating valve. The direction of flow is indicated by an arrow on the inlet port. The sight glass is used to monitor the float and the liquid. 4.2.5 The devices have following essential characteristics: Model Designation Q Max (L/min) Bore size Inlet/Outlet Flange (Std. Available) VDR 10 1000 2", 2½", 3" VDR 20 2000 2", 3", 4" VDR 25 2500 3", 4", 6" VDR 30 3000 4", 6" VDR 40 4000 4", 6" VDR 60 6000 6", 8" VDR 70 7000 6", 8" VDR 100 10000 8", 10" VDR 130 13000 8",10" VDR 180 18000 10",12" VDR 240 24000 10",12",16" VDR 350 35000 12", 16" BR 150 2200 3", 4" EGS_1 3300 2", 3", 4" EGS_2 1700 2", 3", 4" 6

Model Designation Q Max (L/min) Container capacity (L) Effective volume (L) ZGA 25 100 29 10 ZGA 25 100 29 10 ZGA 50 300 45 25 ZGA 65 700 120 60 ZGA 80 1200 180 95 ZGA 100 1200 180 95 ZGA 100 2000 300 180 ZGA 100 3000 470 295 ZGA 150 3000 470 295 ZGA 150 5000 1000 675 ZGA 200 5000 1000 675 ZGA 250 5000 1000 675 ZGA 200 10000 2200 1500 ZGA 250 10000 2200 1500 ZGA 300 10000 2200 1500 ZGA 300 12000 2700 1900 ZGA 300 20000 1) 5000 2800 ZGA 400 20000 1) 5000 2800 ZGA 300 25000 1) 7000 5000 ZGA 400 25000 1) 7000 5000 1) with 2 deaeration devices 4.2.6 Optional and non essential parts of air separators: - Strainer before the inlet of the air separator - The separated air/gas is released into the air or into a vapour recovery line 5 APPROVAL CONDITIONS 5.1 The certificate is issued subject to the following conditions on inscriptions - Manufacturers mark or name - Accuracy class - Maximum operating pressure - Liquid type(s) - Operating temperature range - Minimum Measured Quantity (1) - Flow rate range - Serial number - Certificate number 7

- CE marking - Supplementary metrology marking - Notified body identification number (1) MMQ stands for Minimum Measured Quantity. The inscription MMQ L in the neighbourhood of the display of the flow computer and/or on the nameplate. 5.2 Location of seals and verification marks Components that may not be dismantled or adjusted by the user will be secured by either a wire and seal or tamper evident label and securing mark. The securing mark may be either: a mark of the manufacturer and/or manufacturer s representative, or an official mark of a verification officer or Notified body 5.3 The following items shall be secured: - nameplate to the measuring instrument (incl. CE marking). Removal shall be impossible without damaging it or without breaking a seal. - the measurement sensor against removal : - electronic pulser against removal - measurement chambers against opening - the gas extractor against removal - the mechanical connections between the meter sensor and the pulser (if applicable) - the flow computer as described in Evaluation Certificate TC7311. - the temperature sensor used as part of the volume conversion functionality against removal 6 RECOMMENDED TESTS The meter measuring system should be tested at a minimum of two substantially different rates of flow between the maximum and minimum rates of flow. Due regard should be paid to the viscosity of the liquid used for the verification tests to ensure that the permitted limits of error are not likely to be exceeded when other liquids which the system is intended to measure are metered. 7 ILLUSTRATIONS/DOCUMENTATION Figure 1 Figure 2 Figure 3 Figure 4 Hydraulic diagram MultiLoad II Example of Hydraulics Installation Example of the name plate 8

8 CERTIFICATE HISTORY ISSUE NO. DATE DESCRIPTION UK/0126/0065 23 February 2010 Type examination certificate first issued. UK/0126/0065 Revision 1 3 May 2011 Revision 1 Issued: Front Page Update of company Name Section 4.2 Note added Sections 4.2.4 & 4.2.5 - Bopp & Reuther Messtechnik GmbH, type ZGA gas seprator added Figure 4 Name plate updated. Figure 1 Hydraulic diagram 9

Figure 2 MultiLoad II 10

Figure 3 Example of Hydraulics Installation Figure 4 Example of the name plate Crown copyright 2011 National Measurement Office This material may be freely reproduced except for sale. 11