ME 4710 Motion and Control: Integrator Wind-up Reference: Franklin, Powell, Emami-Naeini, Feedback Control of Dynamic Systems, Prentice-Hall, 2002.

Similar documents
Lab 4: Root Locus Based Control Design

Fail Operational Controls for an Independent Metering Valve

Fail operational controls for an independent metering valve

Characterizers for control loops

CHAPTER 7: THE FEEDBACK LOOP

Digital Level Control One and Two Loops Proportional and Integral Control Single-Loop and Cascade Control

Gerald D. Anderson. Education Technical Specialist

TR Electronic Pressure Regulator. User s Manual

OIL & GAS. 20th APPLICATION REPORT. SOLUTIONS for FLUID MOVEMENT, MEASUREMENT & CONTAINMENT. Q&A: OPEC Responds to SHALE BOOM

ZIPWAKE DYNAMIC TRIM CONTROL SYSTEM OUTLINE OF OPERATING PRINCIPLES BEHIND THE AUTOMATIC MOTION CONTROL FEATURES

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

Control Valves, Actuators, & Pressure Safety Valves

LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

(12) United States Patent (10) Patent No.: US 6,598,456 B2

Equation 1: F spring = kx. Where F is the force of the spring, k is the spring constant and x is the displacement of the spring. Equation 2: F = mg

living with the lab control of salinity 2012 David Hall

Application Worksheet

NATIONAL UNIVERSITY OF SINGAPORE. EE3302/EE3302E Industrial Control Systems E1: ADVANCED CONTROL SYSTEMS

Unit 55: Instrumentation and Control Principles

Recovery from a Process Saturation Condition. Benefits of Using DeltaV PIDPlus

PI control for regulating pressure inside a hypersonic wind tunnel

Moyno ERT Power Sections. Operational Guidelines

MANUAL KPS Pressure Control Valve

Control Valve : The Final Control Element. Nimish Shah

SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION

Compensator Design for Speed Control of DC Motor by Root Locus Approach using MATLAB

living with the lab control of salinity 2012 David Hall

How to Combat Process Disturbances and Interactions

CONTROL AND IMPLEMENTATION OF AN AUTONOMOUS SAILBOAT

AN AUTOMATIC DEPTH CONTROL SYSTEM FOR ON-LINE MEASUREMENT OF SPATIAL VARIATION IN SOIL COMPACTION

Introduction to Scientific Notation & Significant Figures. Packet #6

One of the most important gauges on the panel is

Testing of hull drag for a sailboat

Flight Dynamics II (Stability) Prof. Nandan Kumar Sinha Department of Aerospace Engineering Indian Institute of Technology, Madras

Applying Hooke s Law to Multiple Bungee Cords. Introduction

1. A tendency to roll or heel when turning (a known and typically constant disturbance) 2. Motion induced by surface waves of certain frequencies.

intended velocity ( u k arm movements

ISO 29990:2010 Standards

New Methods in Modeling and Control of Modern Electrohydraulic Systems

RC 195 Receiver-Controller

STICTION: THE HIDDEN MENACE

Instrumentation (and

Interception of a Projectile Using a Human Vision-Based Strategy

Workshop 302-compressor-anti-surge

( ) ( ) *( A ) APPLICATION DATA. Procidia Control Solutions Coarse/Fine Control. Split-Range Control. AD Rev 2 April 2012

LQG Based Robust Tracking Control of Blood Gases during Extracorporeal Membrane Oxygenation

29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies

Wind Tunnel Instrumentation System

Experimental Investigation on Transient Response of Two Stage Pressure Relief Valve

Internet Technology Fundamentals. To use a passing score at the percentiles listed below:

Author s Name Name of the Paper Session. Positioning Committee. Marine Technology Society. DYNAMIC POSITIONING CONFERENCE September 18-19, 2001

PRESSURE CONTROL TRAINER

At each type of conflict location, the risk is affected by certain parameters:

Calculation of Trail Usage from Counter Data

The Discussion of this exercise covers the following points:

Implementing Mid Ranging in a DCS Environment

Bouncing Ball A C T I V I T Y 8. Objectives. You ll Need. Name Date

control of salinity Thanks to David Hall, from LWTL

Level Process Control. Penn State Chemical Engineering

Preparation for Salinity Control ME 121

DP Ice Model Test of Arctic Drillship

Lab 3: Pumps in Series & Pumps in Parallel

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Gas Laws. Introduction

Evaluation of control methods for floating offshore wind turbines

2.6 Control Systems Cascade Loops

Autopilot setup. VRF (Virtual Rudder Feedback) calibration. Software setup NSS evo2 Installation Manual

Hydraulics. Hydraulic Pressure Control

Line Following with RobotC Page 1

IE098: Advanced Process Control for Engineers and Technicians

Mitos Fluika Pressure and Vacuum Pumps Datasheet

Operational Behaviour of Safety Valves with Constant Superimposed Backpressure

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters

Guida parametri EVD 200. Manuale d'uso User manual

Using Markov Chains to Analyze a Volleyball Rally

MODULE 5 ADVANCED MECHANICS EXPERIMENT 533 PROJECTILE MOTION VISUAL PHYSICS ONLINE

Naval Postgraduate School, Operational Oceanography and Meteorology. Since inputs from UDAS are continuously used in projects at the Naval

Application Block Library Fan Control Optimization

The Physics of Water Ballast

REACTOR 40 MECHANICAL Configuration Guide

Constructing the Bell Curve

- creating the pong bat animation with various options

CONTROL VALVE FROM CONTROL LOOP THEORY PERSPECTIVE: An overview

Report for Experiment #11 Testing Newton s Second Law On the Moon

CHAPTER 1 ORGANIZATION OF DATA SETS

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

Overview. 2 Module 13: Advanced Data Processing

Injection Controller Program User Manual (for FloBoss 107 and ROC800-Series)

Heat Pump Connections and Interior Piping

DYNAMIC POSITIONING CONFERENCE October 7-8, New Applications. Dynamic Positioning for Heavy Lift Applications

Constant pressure air charging cascade control system based on fuzzy PID controller. Jun Zhao & Zheng Zhang

Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST)

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI

BERNOULLI EFFECTS ON PRESSURE.ACTIVATED W ATER LEVEL GAUGES

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

STT 315 Section /19/2014

DYNAMIC POSITIONING CONFERENCE. October 13-14, Arctic. DP In Ice Conditions

VI. Static Stability. Consider a parcel of unsaturated air. Assume the actual lapse rate is less than the dry adiabatic lapse rate: Γ < Γ d

Transactions on Ecology and the Environment vol 12, 1996 WIT Press, ISSN

Transcription:

ME 4710 Motion and Control: Integrator Wind-up Reference: Franklin, Powell, Emami-Naeini, Feedback Control of Dynamic Systems, Prentice-Hall, 2002. The system shown below is a model of a closed-loop hydraulic actuator with a proportionalintegral-derivative (PID) controller. As the system responds to a step position command, the integral term of a PID compensator will continue to increase until the actuator reaches its final position. If the integral term becomes too large during this response, it can create large overshoot. As shown in the model, one way to correct this problem is to simply limit the magnitude of the integral term. The results shown below are for the system responding to a step position command of magnitude 10. The PID command saturation level has been set so that no saturation of the combined PID command signal occurs. The model was then executed for two different limits on the integral command. The limit of 100 has no effect on the limit of the integral command, so those results show how the system responds with no saturation limits. Conversely, the integral saturation level of 10 clearly lowers the integral part of the PID command and changes the system s response. The two plots in the top row show the individual PID command signals at the two integral saturation limits. The plot on the upper left clearly shows that the integral command signal is not limited when the integral limit is 100, and the plot on the upper right shows a limited integral command and the corresponding proportional and derivative commands. Kamman Motion and Control page: 1/5

The plots in the bottom row show the saturated PID command signal and the actuator position response at the two integral saturation limits. The plot on the lower left shows the total PID command signal is not limited. The plot on the lower right shows the improvement to the step response achieved by limiting the magnitude of the integral command. The system has less overshoot and a lower settling time. The locations of the approximate two-percent settling times are indicated on the plot. If left unchecked, the integral command builds until the actuator reaches its final position, and then its takes time for the PID command level to decrease. This effect is known as integrator wind-up. Kamman Motion and Control page: 2/5

The effects of integrator wind-up can be worsened when the actuator itself experiences saturation. A second set of results is shown below for integrator saturation levels of 100 and 10 and a PID compensator signal saturation limit of 50. As shown in the figure on the top left, the integrator signal now experiences saturation when the limit is set at 100. So, the integrator command has increased due to the actuator saturation. The saturated compensator command is shown in the figure on the bottom left. The step response of the system is shown on the bottom right. Note that actuator saturation has increased the settling times of the system at both integrator saturation levels. It also significantly increased the overshoot at the higher integral saturation level. Kamman Motion and Control page: 3/5

A second solution to integrator wind-up is to add a feedback loop to the compensator that is activated when saturation occurs. In the model shown below, the amount of PID command signal saturation is calculated by taking the difference between the compensator command and the saturated compensator command. That difference is multiplied by the anti-wind-up gain and then subtracted from the actuator position error to lower the input to the integrator, and hence, lower the integral command. For good performance, the anti-windup gain should be large enough to limit the size of the integral command signal and can be found by trial-and-error. Model results are shown below for two anti-wind-up gains and a PID command signal saturation level of 20. The top two plots show the PID command signals for anti-wind-up gains of 0.025 and 0.075. The bottom two plots show the saturated command signals and the actuator position response associated with the two anti-wind-up gains. The lower anti-wind-up gain is not large enough to stop integrator wind-up. At this gain, the actuator position significantly overshoots the position command of 10 and takes over 2 seconds to settle within two-percent of the command. The higher anti-wind-up gain reduces the integral command significantly, reduces the overshoot to almost zero, and reduces the two-percent settling time to just over 1 second. Kamman Motion and Control page: 4/5

Kamman Motion and Control page: 5/5