Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869

Similar documents
Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

Chlorine Supply Containers And Piping

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

CAPITAL CONTROLS SERIES NXT3000

Installation Instructions For Flat Seated Bolted Type RAH Series Disk Holders

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

Instruction Manual ADVANCE Series 480 Vacuum Regulator

Installation, Operation, and Maintenance Manual

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

TITAN FLOW CONTROL, INC.

1200B2 Series Service Regulators. Instruction Manual

Instruction Manual Series 200 ADVANCE Cylinder or Ton Container Mounted Vacuum Regulators

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER RELIEF VALVE

Installation, Operation, and Maintenance Manual

64 Series Pressure Reducing Regulators

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

WHEATLEY Series 500 Swing Check Valve

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

MEGR-1912 Instruction Manual

Flange Bolt Torquing. for Resistoflex Plastic-Lined Piping Products. Torquing. Retorquing. Hydrotesting. Annual retorquing

Preparation and Installation of the Composite Type Rupture Disc (Light Lip and Heavy Lip) in 30 Seat 7I Insert, Full Bolted, and Union Type Holders

Preparation and Installation of the Standard Type Flat Seat Rupture Disc / UNISERT Insert Holder Assembly (Sizes 10 and Larger)

Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

Chemical Injection Technologies Installation/Service Bulletin

MEGR-1627 Instruction Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

DuraSite 3000 Sample Vessel User's Guide. Version Rev-1

1800C and 1800C-HC Series Service Regulators

Constant Pressure Crude Oil Container Model CPCCP

AWWA C504 COMPLIANT VALVES FROM 3 THRU 108

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

Vaporizer Piping Liquid Chlorine Manifolds

1301 Series High-Pressure Regulators

Types 749B and R130 Changeover Manifolds

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

Operation Manual Piston Sensed Gas Pressure Regulators

Installation, Operation and Maintenance Manual for Back Pressure Regulator

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Atmospheric relief valve type 1100 Installation and maintenance instructions

627 Series Pressure Reducing Regulators

Instruction Manual MicroChem 2 Chlorine Probes Series CL4000

INSTALLATION, OPERATION and MAINTENANCE MANUAL

WHEATLEY Series 822/820 Swing Check Valve

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

1805 Series Relief Valves

INSTRUCTION MANUAL. CVS P37 LP Gas Reducing Regulator

PILOT OPERATED RELIEF VALVE SAFETY PRODUCTS THAT PROTECT EQUIPMENT, LIVES & THE ENVIRONMENT

Anti-flood device Model B-1

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

OPERATING AND MAINTENANCE MANUAL

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

SAPAG. Safety valves, type 5700 Storage, Use, Operation and Maintenance Instructions. IMPORTANT NOTICE

TECHNICAL DATA. Page 1 of 12

Float Operated Level Controllers

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

D05 Pressure Regulating Valves

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

Installation Troubleshooting Maintenance Instructions Installation / Start-up

Temperature Controllers

VALVES & MEASUREMENT

HYDROSTATIC LEAK TEST PROCEDURE

KFI Approved. High Pressure CO2 System Technical Datasheets

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

DuraSite 500(1) Portable Sample Vessel User's Guide. Version (1) = 90 Duro Wetted O-Rings

INSTRUCTION MANUAL. Anchor Darling 800 Globe Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

Installation, Operation, and Maintenance Manual

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Pressure Regulators. Operating Instructions. Instrumentation

DS05C,D,G Dial Set Pressure Regulating Valves

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Model Series 62 Constant Differential Relay

V43 Pressure Actuated Water Regulating Valve

TECHNICAL DATA CAUTION

Cash Valve TYPE G-4 PILOT OPERATED PRESSURE REDUCING REGULATOR FOR STEAM, AIR AND GASES. ISSUED - MARCH 2001 CAVMC-0512-US-0208 ISO 9001 Certified

Pressure Dump Valve Service Kit for Series 2300 Units

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

R600 and HSRL Series Instruction Manual

Transcription:

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869-1 - 115.6020.15

These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause significant property damage, severe personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies for clarification before commencing any work at 215-997-4000 and ask for a Field Service Manager. De Nora Water Technologies reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact De Nora Water Technologies for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies equipment is conditioned on the customer absolving De Nora Water Technologiesfrom any consequences of such a decision. De Nora Water Technologies has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. De Nora Water Technologies cannot be responsible deviations from the recommended instructions that may result in a hazardous or unsafe condition. De Nora Water Technologies cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that De Nora Water Technologies. De Nora Water Technologies takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to De Nora Water Technologies for equipment shipped F.O.B Jobsite. Do not install damaged equipment. De Nora Water Technologies, Colmar Operations Colmar, Pennsylvania, USA is ISO 9001: 2008 Certified 115.6020.15-2 -

Table of Contents 1 INTRODUCTION...4 1.1 Reference Literature...4 2 INSTALLATION...5 2.1 Pressure Relief Valve and Rupture Disc...5 2.2 Location...5 2.3 Piping Materials...5 2.4 Vent Piping...5 2.5 Relief Valve Calibration...5 3 OPERATION...8 4 SERVICE...9 4.1 Inspection and Cleaning of Pressure Relief Valve...9 4.2 Rupture Disc Replacement...9 FIGURES 1 Chlorine/Sulfur Dioxide Pressure Relief Valve Dimensions...4 2 Rupture Disc Replacement...6 3 Pressure Relief Valve Assembly With Pressure Gauge...6 4 Pressure Relief Valve With Switch...7-3 - 115.6020.15

1 INTRODUCTION 1.1 Reference Literature The following literature is referenced throughout this instruction manual: 115.6030 - Vaporizer instruction manual 115.3002 - Vaporizer piping connections The pressure relief valve is designed to prevent excessive gas pressure within the liquid vaporizer (or other protected equipment) by venting pressures in excess of 300 psig (2068 kpa) to a location where emergency discharge of gas can be safely tolerated. It is mounted downstream of a rupture disc assembly which is designed to rupture at 300 psig (2068 kpa). An optional pressure switch or gauge may be installed between the relief valve and rupture disc to indicate a ruptured disc condition. The pressure relief valve is designed to be utilized on systems, with capacities for chlorine up to 10,000 PPD (200 kg/h), and for sulfur dioxide up to 8,000 PPD (150 kg/h) See Figure 1. Figure 1 - Chlorine/Sulfur Dioxide Pressure Relief Valve Dimensions 115.6020.15-4 -

2 INSTALLATION Refer to the liquid vaporizer instruction manual 115.6030 for details on installation of the pressure relief valve when used with the vaporizer. When used to protect other equipment, the following guidelines apply: 2.1 Pressure Relief Valve and Rupture Disc Install the pressure relief valve as shown in bulletin 115.3002, and Figures 3 and 4. 2.1.1 The relief valve must be installed without a shutoff valve between it and the vaporizer s gas outlet. Install a manual valve in parallel with the pressure relief valve. This valve will normally be in the closed position. It may be opened as a manual vent valve only. Route a 1" vent pipe (schedule 80 seamless steel pipe [ASTM A-106, Grade B]) from the pressure relief valve to a point outdoors where gas discharge can be tolerated. Position the end of the pipe downward so it will not collect foreign matter or water. 2.1.2 Always install rupture disc between pressure relief valve and the protected equipment. Install as indicated in Figure 3. The rupture disc burst pressure rating must not be great than the pressure relief valve setting. 2.1.3 An optional pressure switch set to actuate at 200 psig (1380 kpa/13.8 bar) may be installed in the gas line between the vaporizer discharge and the pressure relief assembly. This will act as an early warning of an over-pressure condition. 2.2 Location 2.2.1 The pressure relief valve must be installed with no shutoff valves between it and the protected equipment. 2.2.2 The relief valve is designed to relieve at 300 psig (2068 kpa). It is mounted downstream of a rupture disc assembly which is designed to rupture at 300 psig (2068 kpa). An optional pressure switch or gauge may be installed between the relief valve and rupture disc to indicate a ruptured disc condition. See Figures 3 and 4. 2.3 Piping Materials All piping to and from the pressure relief valve should be schedule 80 seamless steel pipe (ASTM A-106, Grade B) with 3000 lb. CWP forged steel fittings (A-105, Grade I or Grade II). Joints should be coated with a white lead paste, PTFE tape or other methods recommended by the Chlorine Institute. Teflon pastes certified for gaseous and liquefied gas service for the chosen gas may also be used. 2.4 Vent Piping Install the pressure relief valve with the side connection pointing towards the vent. Route an unrestricted one inch (1") vent pipe (schedule 80 seamless steel pipe [ASTM A-106, Grade B]) from the valve to a location where emergency discharge of chlorine gas can be safely tolerated. The end of the pipe must be positioned or protected to prevent rainwater or foreign materials from entering the pipe. 2.5 Relief Valve Calibration The relief valve is calibrated at the factory to open at 300 psig (2068 kpa). No additional adjustment is required. - 5-115.6020.15

OUTLET FLANGE FLOW DIRECTION RUPTURE DISC INLET FLANGE Figure 2 - Rupture Disc Replacement 1 INCH NPT VENT CONNECTION PRESSURE RELIEF VALVE SET AT 300 PSIG (2100 KPA) (REPLACEMENT PART NO. BM-4060) 600 PSIG (42 kg/cm2) PRESSURE GAUGE WITH DIAPHRAGM PROTECTOR (REPLACEMENT PART NO. A-356) 12 [305] RUPTURE DISC ASSEMBLY. NON-FRAGMENTING TYPE, RATED AT 250 PSIG (1700 KPA) FOR THE VAX4690 AT 300 PSIG (2100 KPA) FOR THE 71V3000 (REPLACEMENT PARTS: R-1827 FOR THE VAX4690, 18704-1 FOR 71V3000) 1 INCH NPT CONNECTION Figure 3 - Pressure Relief Valve Assembly With Pressure Gauge 115.6020.15-6 -

Figure 4- Pressure Relief Valve With Switch - 7-115.6020.15

3 OPERATION Be sure the manual bypass valve is closed before introducing chemical. The relief valve will require re-calibration upon disassembly for cleaning following an over-pressure condition. 115.6020.15-8 -

4 SERVICE Routine inspection and testing of the pressure relief valve when the protected equipment is shut down for maintenance, will ensure safe operation. 4.1 Inspection and Cleaning of Pressure Relief Valve Routine maintenance procedure for use when valve has not vented since last inspection. 4.1.1 Shut down the system. If used with the liquid vaporizer, refer to the shut-down section of the Vaporizer Instruction Manual 115.6030. Be certain that there is no gas under pressure in the system before proceeding. 4.1.2 Remove the spring bolt by turning counterclockwise until it is free to pull out of the body. Count and note the number of turns when removing the spring bolt. This number should be used in 4.1.5. 4.1.3 Inspect the valve plug assembly for scratches and nicks. If they are present, replace the assembly. If a good seating surface is indicated, clean plug with soap and hot water or a mild solvent. Dry thoroughly. 4.1.4 Inspect the valve seat area of the body, clean and dry. If the seat is not smooth, replace. 4.1.5 Install the valve plug assembly and screw into body to previous depth using the same number of turns noted from 4.1.2. 4.1.6 A check of the pressure relief valve may be made by removing the entire valve from the system and testing on a hydrostatic pressure pump. Adjusting pressure higher or lower may be accomplished by turning spring bolt in or out. 4.1.7 The pressure relief valve may also be checked in the piping system by filling the system with nitrogen or dry air to the desired blow off pressure, adjusting valve as previously described. To prevent premature rupture of the rupture discs, when performing this test, be sure to remove any that may be exposed to the test pressure. Reinstall the rupture discs after the test is completed. 4.2 Rupture Disc Replacement If one of the rupture discs are ruptured, as indicated by the pressure switch or the pressure gauge actuation, refer to Figures 2, 3, or 4, and proceed as follows: 4.2.1 Refer to the Vaporizer instruction manual, and shut down the vaporizer. 4.2.2 When the vaporizer is shut down completely and pressure is removed from the system, loosen and remove the four studs securing the inlet and outlet flanges. 4.2.3 Remove the ruptured disc. 4.2.4 Install a new rupture disc with the dome facing upward. System pressure must be against the concave side of the disc. 4.2.5 Install lightly oiled, free running studs and nuts to finger tightness. Using a cross torquing pattern, torque each nut with a calibrated torque wrench at 20% increments of the torque value recommended by the manufacturer. Repeat 20% increments and cross torquing pattern until final torque value is achieved. 4.2.6 Ensure the flanges are parallel. 4.2.7 Re-start the vaporizer according to the procedure in the vaporizer instruction manual 115.6030. - 9-115.6020.15

Design improvements may be made without notice. Represented by: De Nora Water Technologies 3000 Advance Lane Colmar, PA 18915 ph +1 215 997 4000 fax +1 215 997 4062 web: www.denora.com mail: info.dnwt@denora.com OCT 2015 115.6020.15-10 - Registered Trademark. 2015. All Rights Reserved.