MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Similar documents
TSS21 Sealed Thermostatic Steam Tracer Trap

DF1 and DF2 Diffusers

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

AVC32 Carbon Steel Air Vent for Steam Systems

AVM7 Stainless Steel Thermostatic Air Vent

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

BPT13 Balanced Pressure Thermostatic Steam Traps

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Dri-Line Mk3 Monnier Compressed Air Drain Trap

PV4 and PV6 Piston Valves

TP1 and TP2 Temporary Cone Shaped Strainers

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

CVS10 Sanitary Check Valves

CP10 Sensor Installation and Maintenance Instructions

DCV6 Disc Check Valve

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

CA44, CA44S, CA46 and CA46S Air and Gas Traps

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

FV Flash Vessel Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

CS10-1 Stainless Steel Clean Steam Separator

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

CA10S, CA14 and CA14S Air and Gas Traps

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

MF2M Monnier Miniature Compressed Air Filter

Thermocirc Installation and Maintenance Instructions

APT14, APT14HC and APT14SHC Spares 2

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

PC10HP Pipeline Connector (ASME 600)

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

SRV66 Sanitary Pressure Reducing Valve

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

MFP14-PPU (Vented) Automatic Packaged Pump Units

ML3M Monnier Miniature Compressed Air Lubricator

SRV2S Pressure Reducing Valve

Manual Actuated Boiler Blowdown Valves

BDV1 and BDV2 Blowdown / Depressurisation Valves

TW Temperature Control Valve

BCV31 DN40 - Blowdown Control Valve

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

Spirax Compact FREME Flash Recovery Energy Management Equipment

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

BCV31 DN20 - Blowdown Control Valve

BRV71 and BRV73 Pressure Reducing Valves

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

Vane Flow Switches Colima FLU Series

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

QuickHeat TM Packaged Heat Exchanger Solutions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

M111 Spiraflo Transducer

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

BDV60 Blowdown Vessel Installation and Maintenance Instructions

BCVi43 Blowdown Control Valve

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

Colima TOR Magnetic Level Switches

Transcription:

1250650/6 IM-P125-07 ST Issue 6 MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance 7. Spare parts IM-P125-07 Printed in the ST UK Issue 6 Copyright 2007 1

1. Safety information Safe operation of this product can only be guaranteed if it is properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. This product complies with the requirements of the European Pressure Equipment Directive 97/23/EC and falls within category SEP and therefore does not carry the mark. Group 2 Group 2 Product Gases Liquids MST21 SEP SEP i) The product has been specifically designed for use on steam, air or water / condensate which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections before installation. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 2 IM-P125-07 ST Issue 6

1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and / or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal permit to work system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post warning notices if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. IM-P125-07 ST Issue 6 3

1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures in excess of 270 C (518 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to Maintenance instructions ). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Safety information - Product specific The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. 1.16 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.17 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 IM-P125-07 ST Issue 6

2. General product information 2.1 Description The MST21 is a maintainable balanced pressure thermostatic steam trap designed for relatively small condensate loads usually associated with instrument tracing applications. It is manufactured in stainless steel and is corrosion resistant and easily maintainable. Available types MST21 Standard capacity for tracing loads (standard unit) MST21H High capacity for special applications Capsule fill and operation Standard capsules are marked with the letters 'STD' for operation at approximately 10 C (18 F) below steam saturation temperature. Optionally the capsule can be supplied for sub-cooled 'SUB' operation at approximately 22 C (39.6 F) below steam saturation temperature or a 'NTS' fill capsule for operation at approximately 4 C (7.2 F) below steam saturation temperature. Standards This product fully complies with the requirements of the European Pressure Equipment Directive 97 / 23 / EC. Certification This product is available with a manufacturers' Typical Test Report. Note: All certification / inspection requirements must be stated at the time of order placement. Note: For additional information see the following Technical information Sheet: TI-P125-08. Fig. 1 MST21 2.2 Sizes and pipe connections MST21 ¼" " and ½" screwed BSP, EN ISO 228-1, or NPT. MST21H ½", ¾" and 1" screwed BSP, EN ISO 228-1, or NPT. IM-P125-07 ST Issue 6 5

2.3 Pressure/temperature limits (ISO 6552) Temperature C Pressure psi g Steam saturation curve Pressure bar g Temperature F The product must not be used in this region. The product should not be used in this region as damage to internals may occur. Body design conditions PN25 PMA Maximum allowable pressure 25 bar g @ 300 C (363 psi g @ 572 F) TMA Maximum allowable temperature 400 C @ 23 bar g (752 F @ 333 psi g) Minimum allowable temperature 0 C (32 F) PMO Maximum operating pressure 21 bar g @ 270 C (305 psi g @ 518 F) TMO Maximum operating temperature 270 C @ 21 bar g (518 F @ 305 psi g) Minimum operating temperature 0 C (32 F) Designed for a maximum cold hydraulic test pressure of: 38 bar g (551 psi g) 6 IM-P125-07 ST Issue 6

3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation: 3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2 Determine the correct installation situation and the direction of fluid flow. 3.3 Remove protective covers from all connections and the protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 3.4 The trap is designed for installation with the capsule in a vertical line with the inlet at the top and the outlet at the bottom. This will ensure that it is self-draining. If fitted in a horizontal line, the trap should be preceded by a short drop leg. 3.5 When the trap is discharging to atmopshere, it is strongly recommended to install a diffuser on the outlet side of the trap. This reduces any problem of noise and erosion by cushioning high velocity discharge. See TI-P155-02 for further information. 3.6 Suitable isolation valves must be installed to allow for safe maintenance and trap replacement. 3.7 Open isolation valves slowly until normal operating conditions are achieved. 3.8 Check for leaks and correct operation. Note: If the trap is to discharge to atmosphere ensure it is to a safe place, the discharging fluid may be at a temperature of 100 C (212 F). 4. Commissioning After installation or maintenance ensure that the system is fully functioning. Carry out tests on any alarms or protective devices. 5. Operation The operating element is a capsule containing a small quantity of a special liquid with a boiling point below that of water. In the cold conditions that exist at start-up, the capsule is relaxed. The valve is off its seat and is wide open, allowing unrestricted removal of air. This is a feature of all balanced pressure traps and explains why they are well suited to air venting. As condensate passes through the balanced pressure steam trap, heat is transferred to the liquid in the capsule. The fill liquid boils before steam reaches the trap. The vapour pressure within the capsule causes it to expand and the trap shuts. Heat loss from the trap then cools the water surrounding the capsule, the fill condenses and the capsule contracts, opening the valve and releasing condensate until steam temperature approaches again at which the cycle is repeated. IM-P125-07 ST Issue 6 7

6. Maintenance Note: Before actioning any maintenance programme observe the 'Safety information' in Section 1. 6.1 General information Before undertaking any maintenance on the trap it must be isolated from both the supply line and return line and any pressure allowed to safely normalise to atmosphere. The trap should then be allowed to cool. When reassembling, ensure that all joint faces are clean. Maintenance can be undertaken, once the safety procedures have been observed. It is recommended that new gaskets and spares are used whenever maintenance is undertaken. Ensure that the correct tools and necessary protective equipment are used at all times. When maintenance is complete open isolation valves slowly and check for leaks. 6.2 How to replace the internals (reference Figure 2) - Remove the cap (2) using a spanner. - Lift out the screen (6), spring (4), capsule (3), and spacer plate (5). - Replace with new internals in the correct order. Make sure the conical spring (4) is positioned with the narrow end in contact with the capsule. - Fit a new gasket (7). - Refit the cap (2) using a little anti-seize compound on the threads and tighten to the recommended torque (see Table 1). 7. Spare parts The spare parts available are shown in solid outline. Parts drawn in broken lines are not supplied as spares. Available spares Internals set for MST21 3, 4, 5, 6, 7 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of trap. Note: When placing an order always state capsule fill (see Section 2.1). Example: 1 - Internals set for a ¼" Spirax Sarco MST21 balanced pressure thermostatic steam trap having an 'STD' fill capsule for operation at 10 C (18 F) below steam saturation temperature. Table 1 Recommended tightening torques Item or N m No. Size (lbf ft) mm ¼" 22 A/F ½" 32 A/F 1 and " 32 A/F 2 ¾" 36 A/F 1" 41 A/F Fig. 2 1 6 4 3 5 7 2 8 IM-P125-07 ST Issue 6