SIMULATION OF CONTAINMENT HYDROGEN CONTROL SYSTEM AT IGNALINA NPP

Similar documents
Nuclear safety Lecture 4. The accident of the TMI-2 (1979)

HYDROGEN RISK ANALYSIS FOR A GENERIC NUCLEAR CONTAINMENT VENTILATION SYSTEM

SENSITIVITY ANALYSIS OF THE FIRST CIRCUIT OF COLD CHANNEL PIPELINE RUPTURE SIZE FOR WWER 440/270 REACTOR

APPLICATION OF COCOSYS CODE FOR INVESTIGATION OF GAS MIXING IN MISTRA TEST FACILITY

Digester Processes. 1. Raw Sludge Pumping System

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS. A high-capacity EBA system [CSVS] [main purge]

Transient Analyses In Relief Systems

EMERGENCY CORE COOLING SYSTEM SIMPLIFICATION

ASVAD THE SIMPLE ANSWER TO A SERIOUS PROBLEM. Automatic Safety Valve for Accumulator Depressurization. (p.p.)

Simulation of Experiment on Aerosol Behaviour at Severe Accident Conditions in the LACE Experimental Facility with the ASTEC CPA Code

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

EXPERIMENTAL SUPPORT OF THE BLEED AND FEED ACCIDENT MANAGEMENT MEASURES FOR VVER-440/213 TYPE REACTORS

Evaluation of the fraction of Unit-3 vent gas that flowed into Unit-4 reactor building

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER P: REFERENCE OPERATING CONDITION STUDIES (PCC)

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER F: CONTAINMENT AND SAFEGUARD SYSTEMS 7. CONTAINMENT HEAT REMOVAL SYSTEM (EVU [CHRS])

Verification and validation of computer codes Exercise

Research Article Experimental Studies for the VVER-440/213 Bubble Condenser System for Kola NPP at the Integral Test Facility BC V-213

SAFETY DEMONSTRATION TESTS ON HTR-10

HTR Systems and Components

Loss of Normal Feedwater Analysis by RELAP5/MOD3.3 in Support to Human Reliability Analysis

Pressure Systems Safety Regulation

The Common Project for Completion of Bubbler Condenser Qualification (Bohunice, Mochovce, Dukovany and Paks NPPs)

ASSIGNMENT 2 CHE 3473

ASSIGNMENT 2 CHE 3473

IAEA SAFETY STANDARDS for protecting people and the environment

Effects of Delayed RCP Trip during SBLOCA in PWR

IAEA SAFETY STANDARDS for protecting people and the environment

10. SYSTEM ANALYSIS. The assessment consist of two elements: Safety Analysis Report and an independent Review of Safety Report.

SHUTDOWN SYSTEMS: SDS1 AND SDS2

Preliminary Failure Mode and Effect Analysis for CH HCSB TBM

1 SE/P-02. Experimental and Analytical Studies on Thermal-Hydraulic Performance of a Vacuum Vessel Pressure Suppression System in ITER

The Nitrogen Threat. The simple answer to a serious problem. 1. Why nitrogen is a risky threat to our reactors? 2. Current strategies to deal with it.

The «practical elimination» approach for pressurized water reactors

XA TEPSS RELATED PANDA TESTS (ESBWR)

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Considerations for the Practical Application of the Safety Requirements for Nuclear Power Plant Design

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage

Steam generator tube rupture analysis using dynamic simulation

V.H. Sanchez Espinoza and I. Gómez-García-Toraño

Helium Loop Karlsruhe (HELOKA) large experimental facility for the in-vessel ITER and DEMO components

The API states the following about tube rupture for a shell-and-tube heat exchangers:

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

Absorption - The process of contacting a vapor and gas stream with an absorbing liquid to remove specific materials from the gas stream.

ON TRANSIENTS IN PUMA

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS 2. VOLUME AND CHEMICAL CONTROL (RCV [CVCS])

Fig. 2. M.I. Yaroslavtsev, 2002

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

DAV - P. Product Catalogue DAV - P. Air release & Vacuum Break Valves. (Plastic Air Valves) DAV - P. Edition 2012

Heat Pump Connections and Interior Piping

ICONE ASSESSMENT OF THE TRACE REACTOR ANALYSIS CODE AGAINST SELECTED PANDA TRANSIENT DATA

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

HEALTH AND SAFETY EXECUTIVE HM NUCLEAR INSTALLATIONS INSPECTORATE

Leaks from Unit-3 PCV and steam release in a large amount

SIMULATION OF ENVIRONMENTAL FLIGHT CONDITIONS

DESIGN OF REACTOR CONTAINMENT STRUCTURE AND SYSTEMS FOR NUCLEAR POWER PLANTS

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand

Assessment of Internal Hazards

Hazard Operability Analysis

Applied Fluid Mechanics

Steam penetration in steam sterilization processes

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Inerting System Design for Medium Speed Vertical Spindle Coal Pulverizers TABLE OF CONTENTS

IEM on Severe Accident Management in the light of the accident at the Fukushima Daïchi NPP

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment

Cable in Conduit Conductor (CICC) quench modelling

Portable Oil Lube Air Compressors

SPIROVENT VACUUM DEGASSERS

Classical Event Tree Analysis and Dynamic Event Tree Analysis for High Pressure Core Melt Accidents in a German PWR

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

Körting Liquid Jet Vacuum Ejectors

NORMAL OPERATING PROCEDURES Operating Parameter Information

Unit 24: Applications of Pneumatics and Hydraulics

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

Technical Data Sheet MF010-O-LC

Level 2 PSA for the VVER 440/213 Dukovany Nuclear Power Plant

Installation Operation Maintenance

REGULATORY OBSERVATION

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels

Large Scale BWR Containment LOCA Response Test at the INKA Test Facility

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Tirpur Area Water Supply Project A Report on Transient Modeling Study

SAFETY APPROACHES. The practical elimination approach of accident situations for water-cooled nuclear power reactors

NUBIKI Nuclear Safety Research Institute, Budapest, Hungary

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels

DESIGN OF REACTOR CONTAINMENT STRUCTURE AND SYSTEMS FOR NUCLEAR POWER PLANTS

NE 405/505 Exam 2 Spring 2015

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

1.2 Example 1: A simple hydraulic system

Profile LFR-43 HELENA ITALY. Italian National Agency for New Technologies, Energy and Sustainable Economic Development, C.R. ENEA Brasimone, Italy

The Compact, Portable, Efficient and Economical Solution to boost Shop Compressed Air Pressure by 2 or 3 times

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

Periodical surveys of cargo installations on ships carrying liquefied gases in bulk

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

Passive BWR Integral LOCA Testing at the Karlstein Test Facility INKA

EXPERIMENTAL STUDY ON HYDROGEN EXPLOSIONS IN A FULL-SCALE HYDROGEN FILLING STATION MODEL

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

Transcription:

SIMULATION OF CONTAINMENT HYDROGEN CONTROL SYSTEM AT IGNALINA NPP Egidijus Babilas, Egidijus Urbonavicius, Sigitas Rimkevicius Laboratory of Nuclear Installation Safety, Lithuanian Energy Institute 1. INTRODUCTION Various risk studies have shown that the containment failure due to H 2 combustion without using a sufficient H 2 mitigation system could be a major cause for large offsite release in case of an accident [1]. Even through Ignalina NPP with RBMK-1500 reactor formally does not have full-scope containment, the ALS performs a function of containment. ALS is a pressure suppression type confinement, which protects the population, employees and environment from the radiation hazards. Therefore it is necessary to investigate H 2 distribution and capability of hydrogen control system to maintain the acceptable H 2 concentration in the ALS compartments during the transient processes. In the NPP hydrogen appears due to: 1) the water radiolysis during normal NPP operation and 2) steam reaction with zirconium (this mechanism is related to severe accidents). A detailed nodalisation is required in order to consider a formation of the convection loops and other local effects. To prevent the possible hydrogen accumulation in the ALS during an accident the H 2 control system, which includes H 2 concentration monitoring, H 2 dilution by the compressed air injection and H 2 exhaust by the ventilation system, is installed. Operation of the ventilation system and compressed air supply system are foreseen in the symptom based Emergency Operating Procedures (EOP) [2]. The present paper presents the analysis of H 2 distribution and H 2 control system operation in the INPP ALS compartments in case of the maximum design basis accident (MDBA). The design data on H 2 release was taken from the safety justification of the Ignalina NPP design [3] and considered for the presented analysis. The nodalisation of Ignalina NPP ALS considering the operation of the H 2 control system was developed for COCOSYS code [4]. The current nodalisation allows simulating the local H 2 distribution and assessing the efficiency of the H 2 control system. The operation of the related safety systems is considered as well. 2. NOMENCLATURE ALS Accident Localisation System ALTs ALS towers

AVC Air venting channel BSRC Bottom steam reception chamber CTCS Condenser Tray Cooling System ECCS Emergency Core Cooling System EOP Emergency Operating Procedure GDC Gas Delay Chamber HCC Hot Condensate Chamber INPP Ignalina nuclear power plant LOCA Loss of Coolant Accident LWR Light water reactor MCC Main Coolant Circuit MCP Main Circulation Pump MDBA Maximum design basis accident MER Mass and Energy Release Rate NPP Nuclear Power Plant PH Pressure Header RBMK Russian acronym for Large Power Channel Reactor SDD Steam discharge device 3. CONTAINMENT OF IGNALINA NPP A characteristic feature of the major light water reactors is the containment, which protects the workers, public and environment from radiation hazard. This is a large, strong, steel and reinforced concrete building, which encloses the reactor and its cooling circuits. Formally, Ignalina NPP does not have containment but the major part of the Main Circulation Circuit (MCC) is enclosed by the ALS, which performs a function of containment. The ALS of Ignalina NPP (Fig. 1) consists of a number of interconnected compartments with 10 condensing pools to condense the accident-generated steam and to reduce the peak pressures that can be reached during any loss of coolant accident (LOCA). In this respect, the ALS of Ignalina NPP is a pressure suppression type containment. The condensing pools are located at five elevations in two ALS towers. In the case of MCP pressure header rupture the accident-generated steam is directed to four bottom condensing pools in both ALS towers. The other pools are designed for the condensation of steam released through the MCC overpressure protection system and do not participate in the MDBA sequence. To maintain the water level of 1.05 m, there are two holes of 50 mm diameter in each overflow barrier of condensing pools. Two rectangular holes, distributed at an elevation of 1.1 m in each overflow barrier, allow the condensate overflow to the hot condensate chamber (HCC) in the case of water level increase in the condensing pool. In each

pool of 2, 3 and 4 level, there are 10 steam distribution devices, each about 20 m long. The bottom pool has 7 devices 20 m long and 3 devices 10 m long. The steam distribution devices are 800 mm diameter pipes connected to rectangular, steel metal downcomers (vent pipes) that under normal operation conditions are submerged to a depth of 0.85 1 m in the water of condensing pools. At the exit end the vent pipes are provided with a saw-tooth edge in order of better steam distribution and reduction of condensation type oscillations. To avoid boiling of the water in the condensing pools the Condensing tray Cooling System (CTCS) provides water to these pools. Heat exchangers of CTCS are cooled with service water. The characteristic feature of ALS is that in the initial phase of the accident a clean air from the wet-well is pushed away to the environment by the air from the drywell. This helps to reduce the peak pressure in compartments. The isolation of ALS from the environment is achieved by the floating ball-type valves. A detailed description of Ignalina NPP can be found in [5]. The volume of compartments in front of condensing pools (drywell) is 20600 m 3, behind the condensing pools 28330 m 3 [5]. The water volume in the condensing pools 2800 m 3 [5]. During normal operation several ventilation systems provide cooling of the ALS atmosphere to maintain a temperature of 50 C in the compartments before the condensing pools and 35 C in the compartments behind the condensing pools. The exhaust ventilation systems maintain a slight under pressure in the compartments to avoid any release of radioactive fission products to the environment. These ventilation systems are equipped with iodine and aerosol filters. In case of a LOCA inside the ALS compartments all the ventilation fans are stopped and the double hermetic valves on the ventilation lines are closed automatically. 4. HYDROGEN CONCENTRATION CONTROL IN ALS The operation of the ventilation and compressed air supply systems is an accident management measure for controlling the hydrogen concentration and preventing hydrogen accumulation as well as the formation of combustible mixtures. As foreseen in the EOP [2] the hydrogen concentration control is performed manually and consists of the following subsystems: hydrogen monitoring system, exhaust ventilation system to remove hydrogen, compressed air supply system for hydrogen dilution and the branch of the condenser tray cooling system (CTCS) spraying into BSRC. Hydrogen concentration monitoring in the ALS compartments of Ignalina NPP is performed in the following compartments:

bottom steam reception chambers, gas space of each condensing pool, air venting channels and gas delay chambers. If the hydrogen concentration in BSRC reaches a defined set-point, then the operator turns on the fan of the exhaust ventilation system to discharge the steam/gas mixture through the filters to the ventilation stack. At the same time the sprays that are installed in BSRC are activated to condense the steam. When the hydrogen concentration decreases to 0.4 % the ventilation and BSRC sprays are stopped manually. If the hydrogen concentration increases in the compartments behind the condensing pools, then the operator 17 25 26 19 9 10 28 11 27 20 18 24 30 4 3 2 12 13 5 29 6 1 22 7 15 21 11 23 14 16 8 Fig. 1 Principal scheme of the Ignalina NPP Accident Localisation System 1. fuel channel 2. main circulation pumps 3. MCP suction header 4. MCP pressure header 5. group distribution header 6. ECCS headers 7. hot condensate chamber (HCC) 8. CTCS pumps and heat exchangers 9. discharge pipes section 10. pipe from the steam relief valves 11. steam gas mixture from the reactor cavity 12. condensing pools 13. steam distribution headers 14. bottom steam reception chamber (BSRC) sprays. 15. water seals/s traps between HCC and 16. BSRC vacuum breakers BSRC 17. air removal corridor sprays 18. air venting channel 19. gas delay chamber tank 20. gas delay chamber 21. reinforced, leak tight compartments 22. Lower Water Piping compartments

23. steam relief valves from Lower Water 24. top steam reception chamber Piping to reinforced leak tight compartments 25. tip up hatches 26. knock down hatches 27. main safety valve and fast acting steam 28. drum separators discharge valve 29. BSRC steam distribution corridors 30. core starts to supply compressed air to the location with the increased hydrogen concentration and turns on the ventilation to discharge the steam/gas mixture from the gas delay chamber. The capacity of the exhaust ventilation system 2WZ56 is from: reinforced leak tight compartments 19000 m3/h, BSRC of each ALS tower 400 m3/h, group distribution header compartments 4500 m3/h, each ALS tower 7500 m3/h. The compressed air to the ALS compartments is supplied with a temperature of 15 C and without prior purification. The air is supplied to the spaces above the water of the condensing pools. To dilute the gas there, the air can be supplied to each condensing pool separately, e.g. if an increased hydrogen concentration is detected in the 1 st condensing pool, then the air is supplied only to the space above the water of this pool. The supply rate to each condensing pool is 500 m 3 /h, i.e. the maximal possible supply of compressed air to both ALTs is 4000 m 3 /h to the pools 1 to 4. The branch of the CTCS spraying into BSRC is operated manually too. The total flow rate to BSRC sprays is 250 m 3 /h. The spray nozzles are installed close to the 1 st condensing pool at the elevation of 9.5 m. The operation of these systems is considered in the model. 5. ACCIDENT SCENARIO AND INJECTION RATES Until the current analysis any quantitative information was available concerning a severe accident scenario in RBMK type reactors. The reason is the special assembly of the graphite moderated channel type boiling water reactor. Thus, the phenomena identified for LWR core melt accidents are not simply transferable to RBMK and also the developed analysis tools are not appropriate without some modifications. Therefore, at the moment for the analysis of the hydrogen distribution in the Ignalina NPP ALS the maximum design basis accident - rupture of a MCP pressure header - was selected. The analysis of MCC behaviour in case of a PH rupture was performed employing the code RELAP5 [3]. The boundary conditions of this analysis were defined as ALS conservative (all safety systems operate as designed) resulting in the largest coolant release to the ALS and, thus, leading to higher loads. This mass and energy release (MER) was already applied for the analysis of the ALS thermal

hydraulic behaviour with RALOC and COCOSYS [6]. Taking the same scenario it will be possible to evaluate the influence of H 2 on the thermal hydraulic results. A H 2 release rate is available from the report for the justification of the Symptom Based Emergency Operating Procedures [2]. In the report it is given that in case of a PH rupture (with different boundary conditions compared to [3] - i.e. with an additional failure of one check valve in the reactor cooling circuit) the hydrogen release rate can be described by the G= 0.29 t where t is the time from the beginning of the accident. Further on is stated that due to the steam-zirconium reaction the hydrogen production is relatively high for 10 hours and later the H 2 release is terminated. During this period ~110 m 3 of hydrogen is released to the ALS. The report [2] provides also a rough conservative estimate on possible hydrogen concentrations in the ALS compartments and possible loadings if a combustible mixture appears. The break of the MCP pressure header, i.e. the release of the coolant together with hydrogen was assumed to occur in the left loop of the reactor cooling circuit. The MER is given in Fig. 2 and the considered H 2 release rate is shown in Fig. 3. Mass flow, kg/s 30000 25000 20000 15000 10000 5000 mass flow enthalpy 1800 1500 1200 900 600 300 Enthalpy, kj/kg 0 0 0,1 1 10 100 1000 10000 100000 Time, s Fig. 2 Coolant mass flow rate and specific enthalpy calculated with RELAP5 6. INPP ALS MODEL FOR THE CODE COCOSYS COCOSYS is a lumped-parameter code for the comprehensive simulation of all relevant phenomena, processes and plant states during severe accidents in the containment of light water reactors, also covering the design basis accidents [4]. Considering that the most probable hydrogen accumulation places are the top compartments of the ALS towers, i. e. before and behind of steam condensing pools [2], these compartments were modelled in more detail. The refined ALS model allows possible convection loops, which can have a significant influence for the H 2 distribution in long term. This refined ALS nodalisation was based on previously developed ALS model for calculation of the thermalhydraulic parameters in ALS during MDBA. Detailed

description of the ALS model, which was used as a basis for the current simulation, can be found in [7]. The model of Ignalina NPP ALS for the code COCOSYS used in the analysis consists of 109 nodes, 291 junctions of different type, including pumps and 341 structures to consider the heat transfer to building structures. The model includes all the accident-affected ALS compartments, condenser tray cooling system, drainage and other related systems. The model includes the Emergency Core Cooling System (ECCS), which uses ALS as a water reservoir. 0,3 0,25 H2 flow rate, m3/s 0,2 0,15 0,1 0,05 0 0,1 1 10 100 1000 10000 100000 Time, s Fig. 3 Hydrogen release rate to the ALS The refined model of the bottom steam reception chamber and condensing pools of ALS towers are presented in the Fig. 4. In the previous model the current compartments were modelled as two equivalent compartments. To estimate the probable convection in these compartments, the condensing pools were modelled according to their real location. The BSRC was subdivided according to location of condensing pools as well (Fig. 4). BSRC_L10 COLL_L4 PSS_L4 BSRC_L9 from PBB5 BSRC_L8 COLL_L3 PSS_L3 BSRC_L7 BSRC_L2 BSRC_L1 BSRC_L6 PSS_L2 COLL_L2 BSRC_L5 HCC_L BSRC_L4 PSS_L1 COLL_L1 BSRC_L3 BSRC_L2 BSRC_L1 Fig. 4 Nodalisation of the BSRC and condensing pools in the left tower of ALS

As described in Section 2, there are 5 condensing pools in each tower of ALS and in case of a pressure header (PH) rupture only the four lower pools are steam loaded in the accident sequence. Therefore, the pressure suppression pool zone model DRASYS of the COCOSYS code [4] was applied to simulate the four lower condensing pools (nodes PSSL1 - PSSL4 and PSSR1 - PSSR4 for left and right ALS towers respectively). The 5 th condensing pool was simulated as a NONEQUILIB zone model of COCOSYS code [4] node (PSSL5 and PSSR5 for left and right ALS towers (ALT) respectively) considering the water mass and the volume of atmosphere above the water surface. The headers of the steam distribution devices (SDD) were simulated as a separate node for each condensing pool (COLL_L1 to COLL_L4 and COLL_R1 to COLL_R4 for left and right ALS towers, respectively). The BSRCs were split in 10 nodes each, i.e. according to the height and into two sides located left and right of the condensing pools (nodes BSRC_L1 to BSRC_L10 and BSRC_R1 to BSRC_R10 for left and right ALTs, respectively). In the previous analyses the hot condensate chamber (HCC) and the air venting channel (AVC) in each ALS tower were combined to one node including also the volume and structures of the 5 th condensing pool. For the intended hydrogen distribution analysis these compartments were simulated by several nodes. AVC is split in upward direction according to the location of the condensing pools. Additionally the AVC was split into two parts one is close to the condensing pool and the other is close to the outer "cold" wall of the ALS tower. Such subdivision allows the formation of possible convection loops. The lowest nodes (HCC_L and HCC_R) represent the HCC including water pools and are simulated applying the NONEQUILIB [4] zone model. Junctions are subdivided into three groups: atmospheric junctions, drain junctions (including junctions simulating water overflow from condensing pools) and pump systems. Ventilation was not considered because it turns off automatically closing the fast-acting isolation valves. These valves closes, when the overpressure in the compartments rises to 0.02 bar, what happens in case of PH break immediately at the begin of the accident. The sprays are a part of the CTCS, i.e. in each ALT there is one special branch of the CTCS piping system supplied by the same pumps and coolers. In the input deck CTCS sprays are simulated as separate systems, consisting of a cooler, a pump and a valve each. Energy and mass transfer between sprays droplets and nodes atmosphere is simulated applying the IVO [4] model of COCOSYS. The initial diameter of the spray droplet was defined as 1 mm. Spray paths were given representing the droplet falling through the different nodes of the AVC compartment. Walls, ceilings and floors of the ALS are represented in the input deck by structures. Heat transfer to structures, energy conduction in solid materials and wall temperature profiles are calculated in the COCOSYS code for energy sink/source evaluation. The large number of different compartments with complex geometry of the Ignalina NPP ALS causes considerable surface areas and mass of structures. The massive concrete walls may not have the large influence on the short-term accident analysis, but they

play an important role representing significant energy sink in the long-term. A linear initial temperature profile across the walls between two nodes is assumed, whereas a constant initial temperature is defined for inner walls. The free convection, forced convection and condensation heat transfer models were applied for all simulated walls. The simulation of water drainage from the condensing pools to HCC appears along the side walls of the pools. Therefore, a specific CDW heat transfer model of COCOSYS code [4] was applied for the walls, which separate condensing pools from AVC. 7. SIMULATION OF THE HYDROGEN CONTROL SYSTEM The operation of the hydrogen control system is controlled by the operator depending on the local concentration measured. This is realized in the COCOSYS input deck by EXTERNAL EVENTS [4]. At the NPP the hydrogen concentration is monitored in compartments corresponding to nodes BSRC-L9 and BSRC-L10 in the left ALS tower, to BSRC-R9 and BSRC-R10 in the right ALS tower and in the gas space above each condensing pool simulated by PSS* nodes. In the input deck it was assumed that the hydrogen concentration in the BSRC of both ALTs is monitored only in nodes BSRC-L9 and BSRC-R9. Such assumption allows decreasing the number of external events in the input deck and does not have a large impact on the results because the conditions of the neighboured nodes BSRC-L10 and BSRC-R10 are similar. Usually, the operation of ventilation systems is not considered in LOCA analyses, because they are turned off automatically (confinement isolation). For the current analysis the operation of the exhaust ventilation system is considered in the ALS model to an extent related with hydrogen concentration control. The intakes of the ventilation system are located in BSRC on both sides of the condensing pools, i.e. in the nodes BSRC-L9 and BSRC-L10 in the left ALS tower, and BSRC-R9 and BSRC-R10 in the right ALS tower. The ventilation of the BSRC is simulated by the outlet fan systems F-BSRC-L and F-BSRC-R for the left and right ALS tower respectively. According to EOP-5 [2] the ventilation system should be activated when the volume concentration of hydrogen in the corresponding tower reaches 0.5 % and turned off when it decreases below 0.4 %. The venting of the ALS tower behind the condensing pools is simulated by the outlet fan systems F-GDC-L and F-GDC-R for the left and right tower respectively. These ventilation systems are activated if the volume concentration of hydrogen above any of the condensing pools reaches 1 % and turned off when the concentration above all the pools is less than 0.4 %. The intakes of this ventilation system in the gas delay chambers (GDC) are assumed to be located in the nodes GDC1 and GDC2 in the left and right ALTs respectively. Compressed air supply outlets are located above each condensing pool. The inlet fan systems F-PSS* simulate the compressed air injection above the water of the

condensing pools. The air supply is assumed from the node ENVIRON, which simulates a second environment independent from the node ENVIR. There are no junctions modelled between ALS compartments and ENVIRON. This way, no gas exchange with ENVIRON, which would influence the calculated gas concentrations, will take place. Activation of each system is controlled individually by the local volume concentration of hydrogen. If the concentration in the gas space above any condensing pool exceeds 0.4 %, then the respective fan system is activated to inject air. It should be noted that the switch-off of the compressed air system is not explicitly stated in EOP-5 [2]. Therefore, in order to avoid a numerous switching on and off at 0.4 %, it was assumed in the data deck, that the system is switched off when the hydrogen concentration decreases below 0.2 %. The CTCS branch connected to BSRC sprays is simulated by the pump systems SP_BSRC-L and SP_BSRC-R for the left and right ALTs respectively. The CTCS branch related to BSRC sprays is activated and turned off at the same set points as the exhaust ventilation system taking steam/gas mixture from BSRC, i.e. activated when the volume concentration of hydrogen reaches 0.5 % and turned off when it decreases below 0.4 %. RESULTS A detailed thermal hydraulic analysis of an anticipated MCP pressure header break in the Ignalina NPP ALS was already performed and presented in [6]. The main results of the analysis are presented in Fig. 5 Fig. 8. Some results are compared whit the results received from the calculation of the MDBA without operation of the hydrogen control system (base case). Due to the hydrogen concentration increase in the left ALT exceeding 0.4 % already after 305 s the corresponding supply of compressed air and after 770 s (when exceeding 1 %) the exhaust ventilation system should be operated. Fig. 5 represents the mass flow histories of the hydrogen control system (except the CTCS spray branches) and so, gives an outline on operator actions to be done in accordance to the emergency operating procedures [2]. As it can be seen from the figure, already 5 minutes after start of the accident the operator has to switch on different systems for controlling the hydrogen. The calculation results with regard to the volume concentration of hydrogen in PSS nodes are shown in Fig. 6. As it can be seen from figure, thanks to the operation of the hydrogen control system the maximum concentration in the node PSSL4 was reduced from 6.2 % in the base case [8] to 1.2 % in the current analysis. The very short lasting maximum in the highest BSRC nodes of the left ALT, i.e. BSRC-L9 and BSRC-L10, was reduced from 5.2 % in the base case to 4.6 % in the current calculations. It is impossible to judge about the flammability knowing only the hydrogen concentration, because gas mixtures with high hydrogen concentration might be inerted by steam.

COCOSYS, NPP Ignalina-2, Break of PH with H2, case 2 10000 5000 1000 500 exhaust ventilation compressed air supply F-BSRC-L F-BSRC-R F-GDC-L F-GDC-R F-PSS1L F-PSS4L Volume flow, m3/h 100 50 10 5 1 0 5000 10000 15000 20000 25000 30000 Time, s Fig. 5 Operation of the exhaust ventilation and compressed air systems COCOSYS, NPP Ignalina-2, Break of PH with H2, case 2 10 5 1 0.5 Volume concentration, % 0.1 0.05 0.01 0.005 0.001 0.00050 H2_GASROOM_PSSL1 H2_GASROOM_PSSL2 H2_GASROOM_PSSL3 H2_GASROOM_PSSL4 H2_GAS_PSSL5 H2_GASROOM_PSSR1 H2_GASROOM_PSSR2 H2_GASROOM_PSSR3 H2_GASROOM_PSSR4 H2_GAS_PSSR5 0.00010 0 10000 20000 30000 40000 50000 60000 70000 80000 Time, s Fig. 6 Volume concentration of hydrogen in PSS nodes Corresponding information on the explosion is included in the ternary diagrams, given in Fig. 7. In the base case [8] the atmosphere above the 4 th condensing pool of the left ALT reaches flammability conditions after about 10000 s. In the same case the uppermost BSRC compartments approach to flammability conditions for a very short period during the reverse flow of water [8]. As shown in the Fig. 7, in the analysed case flammability conditions are suppressed thanks to the operation of the hydrogen control system.

detonation limit flammabil ity limits Fig. 7 Hydrogen concentration in case of PH break with hydrogen discharge Beside the hydrogen concentration the operation of the hydrogen control system strongly influences thermal hydraulic parameters. At the water supply by operation of the sprays in the BSRC increase the steam condensation rate. Due to increased steam condensation in the BSRC reached the underpressure conditions. Such pressure behaviour in BSRC leads to the reverse water flow from the condensing pools into BSRC. In Fig. 8 pressure histories of current case (case 2) are compared with results of the base case [8]. Due to the operation of the hydrogen control system, the pressure in the compartment system changes significantly. So, a (partial) reverse flow from the condensation pools occurs earlier and more often than in the base case [8] - after 7 000, 11 000, 21 000, 23 000 and 25 000 s instead of only after 26 400 s [8]. During and/or after reverse flow processes, vacuum breakers open a path from the compartments outside the confinement to the bottom steam reception chambers. Nevertheless, strong pressure drops cannot be avoided this way. After 40 000 s process time, in both cases the general pressure level approaches to normal pressure conditions, i.e. 100 kpa.

water reverse flow into the BSRC* nodes Fig. 8 Pressure in selected nodes before and behind the condensing pools compared with base case CONCLUSIONS For the current analysis a COCOSYS input deck with a detailed nodalisation, consisting of 109 nodes, 302 junctions including 25 pump systems, 12 fan systems and 341 structures, was set up. This input model allows the simulation of convective flows in special regions of the accident localisation system, the calculation of different steam loading of the single condensing pools and of the local accumulation of hydrogen in compartments. The effectiveness of the hydrogen control system was investigated in the present case, where the system was operated manually (i.e. by operator actions) according to the emergency operation procedures. Comparing the results with those of the base case [8], it appears that the operation of exhaust ventilation and compressed air supply systems leads to a more homogeneous distribution of the hydrogen in ALS and partly removal from the ALS. Thus, the highest hydrogen concentration in the gasroom of the 4 th condensing pool and in the highest BSRC nodes in the left accident localisation tower was reduced to 1.2 % and 4.6 % respectively. An assessment of the explosion of this atmosphere composition can be given with ternary diagrams. Different to the base case [8] the formation of flammable hydrogen mixtures can be suppressed by the hydrogen control system. Comparing base case [8] and present case results, it is visible, that the operation of the hydrogen control system significantly influences the atmosphere conditions and the ALS response at all. In the analysis hydrogen concentration threshold values were reached already 5 min after accident initiation. According to the emergency operation procedures several operator actions are required to activate/deactivate the exhaust ventilation, the compressed air supply and the CTCS spray systems and or to keep the HCC water level in designed limits in the long term. The realisation of the sequence of actions

supposed seams to be questionable taking into account the stress situation of the staff during an accident. This gives manifold possibilities for variant calculations to investigate the consequences of the corresponding operator actions (delayed action, actions not performed, wrong actions which caused strong sub-atmospheric pressure or a pressure difference between both ALT, ). REFERENCES 1. Veser A. at. al. Multidimensional simulation of hydrogen distribution and turbulent combustion in severe accidents, 1999 22 November- 1 December, FISA99- EU research in reactor safety, Luxembourg. 2. Safety justification of Symptom Based Emergency Operation Procedures, EOP5, 1997, RDIPE report, 1997 3. Safety Analysis Report for Ignalina NPP Unit 2, 2001,Lithuanian Energy Institute, Kaunas 4. Klein-Hessling W., 1998, COCOSYS 1.2 User manual. 5. Almenas K., Kaliatka A., Uspuras E., Ignalina RBMK-1500., 1998, A Source Book, extended and updated version, Lithuanian Energy Institute, Kaunas,. 6. Urbonavicius E., E. Babilas (LEI Kaunas), S. Arndt, H. Wolff (GRS Berlin), RALOC and COCOSYS Analyses for the Simulation of Processes in the Accident Localisation System of the Ignalina-2 NPP in Case of a Pressure Header Break, 2001 November, BMU/BfS Project SR 2333, Arbeitspunkte 3.3.8 und 3.3.9, Technical Note, Berlin. 7. Babilas E., Rimkevicius S., Urbonavicius E. Influence of building structures modelling to the results of thermo-hydraulic evaluation of Ignalina NPP ALS, 2002, Energetika, Vol. 4. pp 3-11 (in Russian). 8. Urbonavicius E., E. Babilas (LEI Kaunas), S. Arndt, H. Wolff (GRS Berlin), RALOC and COCOSYS Analyses for the Simulation of Processes in the Accident Localisation System of the Ignalina-2 NPP in Case of a Pressure Header Break, 2004 February, BMU/BfS Project SR 2443, Technical Note, Berlin.