OBSOLETE DESIGN DATA FOAM MAKER APPLICATION

Similar documents
OBSOLETE DESIGN DATA. CONCENTRATE CONTROLLERS 2, 3", 4", 6" and 8" (50, 80, 100, 150, and 200 mm)

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

OBSOLETE. Wet pipe low flow manifold system

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

Wet pipe low flow foam/water system

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

FOAM TANK (1/2) DATA SHEET

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. Table 1 - Specifications

TECHNICAL DATA NOTICE

How To Troubleshoot Low Pressure On Well Systems Page 1

TECHNICAL DATA OBSOLETE

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Des Plaines Fire Dept. Engineer Program

TECHNICAL DATA CAUTION

1 Exam Prep. Tabs and Highlights

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

April 17, ,666, Sheets-Sheet. B. N. WALIS AIRSHIP Filed May 29, 1925

TECHNICAL DATA. Dry 132a. October 1, 2008

TECHNICAL DATA. Page 1 of 12

Air Eliminators and Combination Air Eliminators Strainers

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

SEMI FIXED/PORTABLE LINE PROPORTIONERS SLP NPR270

BERMAD Fire Protection Hydraulic Control Valves

Tanker Fill Tests. Evaluating Direct Fill Lines DeKalb County, Alabama. November 16, Tests DeKalb County, AL

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

Bladder Tank Installation & System Design Information

SECTION 2 APPLICATION OF FUNDAMENTALS

DESIGN DATA. Dry 105a. September 5, 2008

Foam Mixers & Proportioning Systems

Storage and Pre-planning Considerations

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2009 Edition)

TotalPac X Single interlock Preaction system Electric release

Pipe Thread Connection 1/2 inch NPT. Friction Loss Refer to Figure 3

Flow Material Length. Weight GPM LPM. Style 3095

United States Patent (19) Widecrantz et al.

Calculations of hydraulic resistance of simple pipelines for liquid viscous and non-newtonian products.

appendix a recommended rules For sizing the water supply system PRE-PRINT Chart a 1.2 FriCtion losses For Disk-type water Meters

Apparatus Operator/Pumper

Bermad Pressure Reducing. Model: 42T

Foam Systems. Fire Protection Solutions

AIR FOAM CHAMBER DATA SHEET

TECHNICAL DATA Q= C. Table 1 - Specifications

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Basic layout 2016 IRRIGATION-MART. Check (Non- Leak) Valve. Friction Fit. Sprinkler. Figure 1 - Hanging Sprinkler & Check Valve Assembly

E 094 E 103 E 143 Tank top mounting Connection up to G1 / -16 SAE Nominal flow rate up to 135 l/min / 35.7 gpm

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

Model 420-HY Pressure Regulating Hydrant Valve

OPERATION AND MAINTENANCE MANUAL

III. Identify the initial installation requirements for standpipe systems

Pipe-Away Pressure Vacuum Vent /Conservation Vent

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

CRYOGENICS & LNG Application Guide

Contents. Catalog HY /US Load and Motor Control Valves SERIES CAVITY DESCRIPTION FLOW PRESSURE PAGE NO. LPM/GPM BAR/PSI

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

Chapter 16 Test. Directions: Write the correct letter on the blank before each question.

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

Operating Instructions

SINGLE VALVE WITH LOW-FLOW BYPASS

VERTICAL BLADDER TANK

then the work done is, if the force and the displacement are in opposite directions, then the work done is.

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM CHART A 1.2 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2"

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEMS CHART A-1 FRICTION LOSSES FOR DISK-TYPE WATER METERS 1-1/2"

Mass Split of Two-Phase-Flow

Gauge Adapters. Senior 2 1 2" [63,5] Bolt Circle Adapt ers. 22 Series ISO 9001:2008 CERTIFIED. Low pressure applications. The Measure of Excellence

HORIZONTAL BLADDER TANK

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

BEFORE SALES AFTER SALES

FIREGROUND HYDRAULICS

Pump Stages. By Tom Murray

Apparatus Operator Refresher Training Program

Foam Chamber Model-FC

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

Air Amplifiers & SYSTEMS

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

s 7 United States Patent (19) is is 11, 3,719,278 (45) March 6, 1973 supplied to an inlet chamber from which it flows

Model: 43T. Bermad Pressure Relief Valve

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

FIRE FIGHTER II SKILL PERFORMANCE CHECK SHEETS NFPA FIRE FIGHTER II SKILL STATION MENU

im,?har. In 4. Inventor: Wesley D. Burgess, His Attorney. years, is a Re fig. 4. o-6 o title?: 15! / 3.

United States Patent (19)

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Eliminating Medical Gas Shutdowns for 10 years

MS.RAJA ELGADY/PRESSURE PAPER 3

VIKING OBSOLETE CONCENTRATE CONTROL SYSTEM OPERATING, MAINTENANCE, AND FILLING MANUAL. Vertical And Horizontal Bladder Tanks

The Discussion of this exercise covers the following points:

Flygt Mix-Flush System

Periodical surveys of cargo installations on ships carrying liquefied gases in bulk

EDUCTOR. principle of operation

FE Petro vs. New Red Jacket Competitive Comparison

TECHNICAL DATA. Q = C v P S

PHILADELPHIA FIRE DEPARTMENT HIGH PRESSURE FIRE HYDRANT SYSTEM PFD TRAINING MANUAL SUPPLEMENT ENGINE PRACTICES SUPPLEMENT 101 PAGE 1

Gas-Detection Instruments

Application Worksheet

MEDICAL EQUIPMENT CATALOG

Transcription:

Foam 410 a 1. DESCRIPTION Foam makers are in-line foam dis - charge devices. Foam makers are utilized in hazards where enhanced foam qualities are needed to protect a hazard. Foam makers are gen er - ally installed in hazards that are sumped or diked. 2. RULES OF INSTALLATION NFPA 11 directs the designer to lo - cate or space the foam makers around a dike or sump based on the discharge rate of the foam maker. The design requirements are as fol - lows: A. Foam makers with flow rates less that 60 gpms (15,82 lpms ) shall be located so that the outlet is not farther than 30 ft (9 m) from any point in the dike. Ex - planation: Due to the low flow rate, foam makers that dis - charge less than 60 gpms (15,82 lpms ) should only be used on small dikes or should be used on narrow dike areas. Refer to Figures #1 and #2. B. Foam makers with flow rates greater than 60 gpms (15,82 lpms ) shall be located that the outlets are equally spaced around the dike area but in no case spaced farther than 60 ft (18,2 m) apart. Explanation: The larger flow rate allows for the fact that foam solution will flow faster and cover more uniformly than water alone. Foam maker dis - charge outlets are always to be located that uniform cov er - age of the dike floor is achieved. Foam solution dis - charge rates larger than 60 gpms (15,82 l/min) are to be equally space over the linear dimension of the dike. Refer to Figure #3. Installation Note When applying foam solution on any hazard, plunging of the foam so lu tion should be avoided. This is especially true of foam makers. Foam makers are inline foam discharge devices and do not have an end that applies directly to the fuel surface. Foam makers are referred to as low level foam discharge devices because the discharge end of the foam maker is piped on the hazard side of the dike, and then drop the supply down the side of the dike wall, then the piping is directed towards the dike wall. The dike wall acts as a splash board where the foam solution drops down the wall to the surface of the fuel. The foam solution spreads at a fast rate across the fuel surface. Synthetic foam solution is oleo-phobic which means it resists fuel pick-up. Al - though it will resist mixing with the liq - uid fuel, the foam blanket will trap some of the flammable vapors in the bubble structure that is the foam blanket, due to this, plunging of the foam blanket in the liquid fuel should be avoided. 3. INSTALLING THE FOAM MAKER Normal methods of piping the dis - charge outlet from the foam maker is to install the foam maker horizontal and rise up from the end of the foam maker with a 90 degree elbow, cross over the dike wall, drop down the dike wall and terminate in a 45 degree el - bow directed back towards the wall. Refer to fig ure #4. 4. SUPPLYING THE FOAM MAKER There are many meth ods that are available in NFPA 11 to supply foam makers protecting a dike or sump area. A. Semi-fixed: Semi-fixed supplies are supplies that have all the near supply pip - ing and discharge piping in - stalled around the dike area. The proportioning device may or may not be in place. Semi-fixed pip ing installations will have sup ply out - let(s) located in the piping around the dike. The end of the supply outlet may have a pro por - tioning device such as an educ - tor sized for the discharge rate of the foam maker(s). A bulk sup ply of foam concentrate is per ma - nently located and piped to the eductor. A water supply can be fed from a fire hose that is con - nected from a yard hydrant to the eductor. Many petro-chemical and petro facilities have a private fire bri - gade equipped with large por ta - ble foam concentrate and water supplies. Another way of pro vid - ing semi-fixed supplies would be to have a foam solution supply that terminates in a Storz or hose connection. The end connection is then fed foam solution by a fire truck or foam tender at a flow rate and pressure of the design of the piping. Refer to Figure #5 for ex - amples of Semi-fixed in stal la - tions. B. Fixed Supplies Fixed foam solution supplies are sometimes known as automatic supplies. The sup ply of foam so - lution is supplied from a central location. At the central location there will be a riser normally equipped with a deluge valve and a proportioning device. The proportioning device is normally a concentrate controller when a foam blad der tank is used or an ILBP where pressure injection proportioning is utilized through a foam bladder tank or a foam pump. The discharge piping is supplied from a fixed riser and is installed between the riser and the piping used to pro tect the dike or sump area. This installation is what would be considered nor mal for most sprinkler designers and in - stallers. Refer to Figure #6 for examples of Fixed Supplies. 5. SIZING THE (S) Viking offers (4) different sizes in foam makers. Refer to Foam Data Page 930a-d for specific design in - for ma tion. Sizing the foam maker requires that the discharge density is known for the fuel and the are that is to be pro - tected is known. Once the total de - mand discharge is known, the dis - charge locations of the foam makers Form No. F_102099 New page issued

Foam 410 b must be determined. After the num - ber of discharge locations is de ter - mined, that amount can be divided into the demand dis charge. An example of this would be as fol - lows: (Refer to Figure #6) A dike is 120 (36,5 m) x 120 (36,5 m). The tanks located within the dike contain die sel fuel (a hydrocarbon). The density for protecting a hy dro - carbon is.10 gpms/sq. ft. ( 4 l/min m squared). Multiply 120 (36,5 m) by 120 (36,5 m) to determine the area of the dike. The area of the dike is 14,400 sq. ft. (1322.24 sq. m). Mul ti - ply the are by the density to de ter - mine the minimum flow rate. 14,400 sq. ft. x.10 gpms /sq. ft. = 1440 gpms Note ; (This is the minimum flow rate. For estimating purposes, an ad di - tional 15% should be added to the water demand. Always hydraulically calculate the system to determine the area flow rate.) 1440 gpms x 1.15% = 1656 gpms The minimum number of outlets re - quired for the dike is (8). Divide the demand flow rate required for the dike by the number of discharge out - lets to be used. Once the flow rate per discharge device is determined, a foam maker can be se lected. 1656 divided by (8) = 207 gpms per discharge outlet A flow rate per foam maker is es ti - mated to be 207 gpms. From Viking Foam Data Page 930d, two dis - charge devices could be selected. The VFM-25 has a flow range of 63 gpms through 232 gpms, the VFM-30 has a flow range of 117 gpms through 486 gpms. If the VFM-25 foam maker is selected, a required pressure at the foam maker would be 100 psi to provide the 207 gpms. If a VFM-30 is selected, the required pressure at the foam maker would be 30 psi to provide 207 gpms. De - pending on the available water sup - ply either device could be utilized. If you do not have the foam cham - ber/maker sizing calculation pro - gram from Viking, please contact The Viking Literature Department or visit our web site at www.vikingcorp.com. Note: Generally the area of the dike floor that is not occupied by a tank bottom is the determined area. In the example above if (5) tanks with bot - toms covering 200 sq. ft. (18,58 sq. m) each were located in the dike, 1000 sq. ft. (92,9 sq. m) could be de - ducted from the area of 14,400 sq. ft. (1339,5 sq. m).

Foam 410 c Figure1 Figure2

Foam 410 d Figure3 Figure4

Foam 410 e Figure5 Figure6

Foam 410 f Figure7 Form No. F_102099 New page issued