Accu-Tab Systems 1000 Series by Axiall Corporation

Similar documents
Accu-Tab Systems 2000 P Series by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation

Accu-Tab PowerBase 3070AT by Axiall Corporation

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

Accu-Tab PowerBase 3140AT by Axiall Corporation

ECONOMY POOL SUNSHINE IONIZER MODEL SPE INSTALLATION INSTRUCTIONS

PURITY INSTALLATION INSTRUCTIONS MODEL P40

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

J Air and Water Kit Instructions Part# 02584

FLANGED TWO-PIECE BALL VALVES

Vessel Installation and Operating Manual

Operator's Manual. Model #PS Arch Chemicals, Inc Lake Park Drive Smyrna, GA PULSAR

D Series Air and Water Kit Part# 02550

Installation Instructions JATCO Environmental Protection Tank Model J-7000

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

200 PSI COMPRESSORS - MODEL NUMBERS

PC1131 Electric Air Compressor

FLANGED TWO-PIECE BALL VALVES

Installation Instructions JATCO Environmental Protection Tank Model J-5000CX

Installation and Operating Manual

SSFU SUPER SPRAYFAST UNIVERSAL ADHESIVE APPLICATOR

444C DUAL PERFORMANCE VALUE PACK

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

100C Air Compressor Kit

PoolNaturally. Pure. Simple. Genius. Installation and Product Use Instructions In ground and above ground pools

480C DUAL PERFORMANCE VALUE PACK

IMPORTANT SAFETY INSTRUCTIONS

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

Arch Feeder: Operator s Manual

Installation and Operating Instructions

IMPORTANT SAFETY INSTRUCTIONS

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

4-in-1 Professional Inflator Kit

ULTRA QUIET & OIL FREE

Model Portable Eyewash

400C & 450C DUAL PERFORMANCE VALUE PACKS

FLANGED MULTI-PORT BALL VALVES

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

1 Pound Treats Between 10,000 to 15,000 Gallons. 24 x 1lb. pouches

Nitrogen Supply System

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

200 PSI FAST-FILL AIR SOURCE KIT

ACCU-MIX 1200 / / 26270

SPECIFICATIONS APCEPH1

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

200 PSI HIGH-FLOW AIR SOURCE KIT

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

92831 TEL: (714) FAX:

APCO ASU-SCAV & ASU-CAV SINGLE BODY COMBINATION AIR VALVES

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

Operating Manual. Model BAC-30RT30/BAC-30DC

Saline C 6.0 Junction Box

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

KJ1000 Operating Instructions & Parts Manual NSN

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

Operating Instruction Manual for Liquid Nitrogen Containers. CRY/CRYC Series. Hagavish st. Israel Tel: , Fax:

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

FlashGARD HP Reverse Osmosis Filtration System Model Number FSTMO75 Part Number

ULTRA-LIGHT DUTY ONBOARD AIR SYSTEM

HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation and Operating Instructions

Marschalk Model # 94000

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

INSTALLATION AND OPERATION INSTRUCTIONS

NGP-250/500 Nitrogen Generator Quick Start Guide

RAM 4021 Operation Manual

BS Series Basket Strainer

Model TWBS.SH Tempered Water Blending System

Contact Chamber and PoolMoss Packs

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

SERIES BB TRASH BASKETS

4 and 8 Station PDS Control Installation & Operators Manual

EQUIPMENT OPERATION MANUAL. Loctite Dispense Valve Manual

Pure Water Power Purification System 4-Stage RODI Operations Manual

Cocoa Patio Pond with Lit Spillway

Operating Manual. Models AQT-02 & AQT-COO2 Manual No. MON004 (Rev 2 April 2000)

User Instruction Manual

Effective March 2015 Supersedes S August 2002

Light Commercial Reverse Osmosis System. EE-1000 Manual

Calibration Gas Instrument INSTRUCTION MANUAL. Release I. Advanced Calibration Designs, Inc.

Interface Devices, Inc. Hydraulic Mini Mule

Universal Valve Company Inc

Installation, Operation and Maintenance Manual

Oxygen Concentrator. Installation and Operation Manual. ClearWater Tech, LLC. Integrated Ozone Systems

Model No Product Name Handpiece Only Complete System

OPERATING MANUAL LO-CROSS-FLOW CF M

General Safety. All electrical work

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

Commercial Well Tank Installation Instructions

3" Chlorinating Tablets Controls Bacteria and Algae Growth Does Not Contain Stabilizer One Tablet Treats 10,000 Gallons of Water for Up to Seven Days

Installation, Operation, and Maintenance Manual

Installation and Operation 370ESP (Electric Single-Point Purger) & 370ESPR (Retrofit Purger)

Transcription:

Accu-Tab Systems 1000 Series by Axiall Corporation Installation and Operating Instructions Model 1050 DANGER: DO NOT MIX CHEMICALS! The Accu-Tab chlorinator is designed for use with Axiall approved tablets only. Do not use Cal-Hypo tablets with stabilized chlorine or bromine products, or other sanitizing chemicals. Fire or explosion could result. Rev 02-10-16

System Description The Accu-Tab tablet chlorinator system incorporates an Axiall chlorinator, which is designed to utilize Axiall s Accu-Tab SI calcium hypochlorite tablets. The chlorinator is mounted on an aluminum frame. Included in the system is an integrated, level controlled solution tank and discharge pump. Using a manually adjusted valve and flow meter the amount of water through the chlorinator is controlled. This results in a constant and predictable rate of chlorine delivery. The feeder is designed for use ONLY with Axiall Accu-Tab SI tablets to utilize the Axiall erosion feeder technology that erodes only the bottom layer of tablets on the sieve plate, while keeping tablets above the sieve plate dry and ready for use. Tablets other than Axiall Accu-Tab SI tablets will have different delivery rates, resulting in improper chlorine delivery. The base system holds ~50 lbs. of tablets. The optional Extender will double the capacity. How to calculate chlorine delivery needed Information required: System flow rate in USgpm (gpm) Chlorine demand of water to be treated (Demand ppm) Chlorine residual desired (Residual ppm) Formula is: gpm x (Demand ppm + Residual ppm) x 0.0005 = lbs. Cl2/hr. From charts on page 5, determine initial flow setting for chlorinator. Take chlorine residual readings and adjust flow to chlorinator until desired residual is reached. Model 1050 Shown with Extender installed 2

Installation and Start-Up Instructions A. Uncrate, remove from pallet, and check for damage that may have occurred during shipping. If damage occurred during shipment, file a claim with the shipping company. B. Place the chlorination system in a location near the place of application. C. Level the system with the supplied leveling bolts. This is important for proper chlorine delivery. D. Install a pressure regulator on the inlet supply line IF inlet line pressure is greater than 35 psi. Tank flooding will result if pressure exceeds 35 psi. E. Float valve is rated to 35 psi. If supply exceeds 35 psi when water system is shut down, a solenoid valve is required to be installed on the inlet line to prevent chlorination system flooding. The solenoid valve must be interlocked with your water system pump. A Solenoid valve is not supplied with this system. F. Connect Run signal wires (either 110v or dry contact) and Power wires to the electrical box. Schematics are shown on pages 6 & 7. G. Connect the inlet flow meter assembly to the solution tank (the parts were shipped loose to prevent breakage in shipping). H. Connect the inlet water supply with 1-1/2 PVC pipe or hose. Include an isolation valve at the main header line. Install the filter in the inlet line. I. Connect the chlorine control and check valve assembly to the pump discharge. Close the chlorine control valve completely. (The parts were shipped loose to prevent breakage in shipment.) J. Connect the discharge piping from the chlorine control valve to the chlorine application point with 1 PVC pipe or hose. Include an isolation valve at the main header line. K. Once the water input and output connections are in place, open isolation valves and check for leaks. Water will begin to flow into the chlorinator and fill the solution tank. L. Wait until water stops flowing into the solution tank. Open the chlorine control valve about 2-3 full turns, and open the ¼ ball valve to prime the pump. When water flows out, pump should be primed. Start the discharge pump. There is a delay timer for the pump. This is to prevent chattering under low level situations. M. Slowly, and in small, ¼ turn increments, continue to open the chlorine control valve to achieve the desired inlet flow. N. The chlorine delivery is determined by the flow rate through the chlorinator (see graphs). NOTE: After adjusting the chlorine control valve, the flow meter will take a few moments to stabilize. O. Turn the main water system OFF and ON several times, allowing it to operate for several minutes each time. Check all connections for leaks. 3

P. To begin chlorinating, remove the chlorinator lid and fill the Chlorinator with Axiall Accu-Tab SI tablets. Q. NOTE: Add only the amount of tablets that will be consumed in 5-7 days. Tablets in the chlorinator longer than 5-7 days will pick up moisture and bridging may occur. Installation Typical 4

Chlorine Delivery, # Cl2/Hr. Model 1050 Schematic and Parts List 3 2.5 Model 1050 Using Accu -Tab SI Tablets For Industrial use only 2 1.5 1 0.5 0 0 2 4 6 8 10 12 14 16 18 20 Flow Rate, GPM 5

6

Operating and Maintenance Instructions A. Clean the Check Valve at least every 4-6 months, to remove debris or scale. B. Disassemble Float Valve and clean every 6 months C. Cleaning the chlorination system Over time, and depending on the water chemical characteristics, some calcium scale may build up in the system. Following procedure to clean: 1. Prepare 1 gallon of weak acid (~5%) solution. 2. Open doors and windows for ventilation. 3. Reduce the tablet volume in the chlorinator by operating the system to deplete the tablets. 4. Physically remove any remaining tablets or pieces of tablets. Store in a safe manner (empty, clean Accu-Tab SI tablet pail). 5. Operate the system for 30 minutes to flush out all remaining chlorine solution, and hose down inside of chlorinator walls. 6. Shut down the system, and close isolation valve on line feeding the system 7. Drain tank level down to about ¾ tank if necessary to prevent system from overflowing while adding cleaning acid 8. Close the discharge isolation valve. 9. Very slowly and carefully pour the weak acid solution into chlorinator. 7

CAUTION: AS ACID DISSOLVES SCALE, CARBON DIOXIDE WILL BE RELEASED, AND FOAMING WILL OCCUR. IF ANY CHLORINE WAS LEFT IN THE TANK OR CHLORINATOR, CHLORINE GAS MAY ALSO BE RELEASED. 10. Allow to stand for 10-15 minutes. 11. Open isolation valves on the inlet and discharge to the system. 12. Be prepared to handle some acid being discharged to your water system. 13. Operate the chlorination system for 30 minutes to flush acid, and thoroughly wash out chlorinator with a hose. 14. Shut system down. 15. Inspect for any debris in the chlorinator or tank, and remove if found. 16. Add tablets and restart system to resume chlorination. Operating Troubleshooting Guide A. Solution Tank level runs low This can lead to inconsistent chlorine residuals. And can allow air to be pulled into the discharge pump, causing pump to lose prime. Follow the procedure to adjust: 1. Make sure pump is primed. 2. Start pump. 3. Slowly, and using small increments, close the chlorine control valve until the solution tank level is stabilized, and no air is being drawn into the pump. B. Solution Tank overflows 1. Check valve has debris in it and is allowing water to back flow. 2. Float valve is not shutting off flow to the system. 3. Float valve has failed. 4. Inlet pressure is greater than 35 psi. Add pressure regulator and/or solenoid valve on inlet line. C. Pump will not run. 1. Check voltage at Disconnect switch. 2. Check circuit breakers. 3. Check voltage at pump contactor. 4. If H/O/A switch in AUTO, check run signal. 5. If H/O/A switch in HAND, check for voltage across Terminals A1 & A2 on pump contactor. If 110v across A1 & A2, manually push in contactor. If pump runs, contactor bad. If contactor pulled in, and voltage on output side of contactor, pump motor bad. 6. Check for low level in solution tank. D. Contact Axiall Technical Service (855-934-3570) for assistance. E. Float Valve was installed in a lower flow position. Float valve may be adjusted for higher flow. Call Axiall for instructions. 8

CAL-HYPO SYSTEM LIMITED WARRANTY Limited System Warranty Axiall Corporation ("Axiall ") warrants (subject to the below conditions) only its title to this water treatment system equipment (the "System") and that the System will be free of defects in materials and workmanship for a period of twelve (12) months from its original installation date. THIS IS THE ONLY REPRESENTATION OR EXPRESS WARRANTY THAT AXIALL MAKES AND ALL OTHER EXPRESS WARRANTIES UNDER STATUTE OR ARISING OTHERWISE IN LAW FROM A COURSE OF DEALING OR USAGE OF TRADE WITH RESPECT TO THE SYSTEM ARE DISCLAIMED. ANY IMPLIED WARRANTIES EXISTING AS A MATTER OF LAW SHALL NOT EXCEED THE DURATION OF THIS LIMITED WARRANTY. IN THE EVENT THE SYSTEM FAILS TO CONFORM TO THIS WARRANTY, AXIALL'S EXCLUSIVE OBLIGATION AND YOUR EXCLUSIVE REMEDY SHALL BE LIMITED TO, AT AXIALL'S OPTION, THE FURNISHING OF NEEDED REPLACEMENT PARTS OR THE FURNISHING OF A NEW SYSTEM (BUT THIS DOES NOT INCLUDE INSTALLATION OR THE COSTS FOR INSTALLATION). EXCEPT AS PROVIDED IN THE IMMEDIATELY PRECEDING SENTENCE, IN NO EVENT WILL AXIALL BE LIABLE UNDER ANY THEORY OF RECOVERY (WHETHER BASED ON NEGLIGENCE OF ANY KIND, STRICT LIABILITY OR TORT) FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, PUNITIVE, OR CONSEQUENTIAL DAMAGES IN ANY WAY RELATED TO ANY USE MADE OF THE SYSTEM. Warranty Conditions. This Limited Warranty shall apply and be effective only if: (i) The Axiall Chlorinator Warranty Registration information has been completed within thirty (30) days of the customers receipt of the chlorination system via the Internet at http://www.accu-tab.com/warrantyregistration.aspx (ii) the chlorination system is installed and operated and maintained in accordance with this manual and the instructions accompanying the chlorinator system; (iii) only Axiall's Accu-Tab calcium hypochlorite tablets are used in the chlorinator. If any of these conditions are not met, this Limited Warranty will not apply and you acknowledge and agree that your purchase of the System will be on an "AS-IS" basis without any warranty of any kind whatsoever having been provided by Axiall. You assume all responsibility and risk and liability arising from: (i) the unloading, installation, storage, handling and use of the System, including use thereof alone or in combination with other materials; (ii) the improper functioning or failure of unloading, installation, transportation or storage equipment you use, whether furnished or recommended by Axiall or not; and, (iii) the failure to comply with laws, rules and regulations governing storage, unloading, installation, handling, and use of the System. You will indemnify, hold harmless, and defend Axiall from and against any claim, suit, damage, cost, expense, fine, liability, or cause of action whatsoever, including reasonable attorney fees, on account of relating to, or arising out of the use, possession, installation or resale of the System. This Limited Warranty gives you specific rights, and you also may have other rights, which vary from jurisdiction to jurisdiction. Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. Some jurisdictions do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. 9