Sizing safety vents for non-tempered systems (organic peroxides): a new tool at lab scale

Similar documents
Runaway reaction. Development of a new experimental vent sizing tool for non tempered systems at the laboratory scale

Relief System Sizing for Runaway Chemical Reactions: A Simple Comprehensive Approach

Road transportation of dangerous goods quantitative risk assessment and route comparison

LARGE-SCALE EVALUATION OF VENT-SIZING METHODOLOGY FOR VAPOUR-PRESSURE SYSTEMS

Considerations relevant to the process design of reactor relief systems are discussed, and appropriate sizing methods described.

Modelling Pressure: Leakage Response in Water Distribution Systems Considering Leak Area Variation

Modified Equation for Gassy Decomposition. Sima Chervin Eastman Kodak Company H. K. Fauske FAI LLC

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary

Implementation of Directive 1999/92/EC : some concerns for the definition of ATEX zones

Behaviour of a highly pressurised tank of GH2 submitted to a thermal or mechanical impact

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

Compliance for a cross four-bar knee joint

Changes rules and evolution of results in judo, an analysis: of the 2012 and 2016 Olympic Games and 2015 and 2017 World Championships.

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

Transient Analyses In Relief Systems

Chapter 13 Gases, Vapors, Liquids, and Solids

Fall 2004 Homework Problem Set 9 Due Wednesday, November 24, at start of class

SIMULATIONS OF HYDROGEN RELEASES FROM A STORAGE TANKS: DISPERSION AND CONSEQUENCES OF IGNITION

Analysis of reflected blast wave pressure profiles in a confined room

PRESSURE RELIEF VENTING SYSTEMS EXAMPLES OF GOOD AND BAD PRACTICE

Accelerating Rate Calorimeter

Generating Calibration Gas Standards

Tutorial. BOSfluids. Relief valve

Ch. 11 Mass transfer principles

Steam generator tube rupture analysis using dynamic simulation

Increasing the Understanding of the BP Texas City Refinery Accident

Study of potential leakage on several stressed fittings for hydrogen pressures up to 700 bar

Chem 110 General Principles of Chemistry

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

Comparing Mirrored Mutations and Active Covariance Matrix Adaptation in the IPOP-CMA-ES on the Noiseless BBOB Testbed

Simulations of hydrogen releases from high pressure storage systems

Chapter 10 Gases. Characteristics of Gases. Pressure. The Gas Laws. The Ideal-Gas Equation. Applications of the Ideal-Gas Equation

Relief Systems. 11/6/ Fall

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

I.CHEM.E.SYMPOSIUM SERIES NO. 110 EMERGENCY RELIEF REQUIREMENTS FOR REACTIVE CHEMICAL STORAGE TANKS

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Figure Vapor-liquid equilibrium for a binary mixture. The dashed lines show the equilibrium compositions.

You should be able to: Describe Equipment Barometer Manometer. 5.1 Pressure Read and outline 5.1 Define Barometer

States of Matter. Q 7. Calculate the average of kinetic energy, in joules of the molecules in 8.0 g of methane at 27 o C. (IIT JEE Marks)

Test Report # Rev 0. Adiabatic Compression With Constant Bleed Valve

Part 6: Critical flow orifices

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI

Classes at: - Topic: Gaseous State

EVALUATION OF TWO-PHASE FLOW MODELS FOR

Energy and mass transfer in gas-liquid reactors.

Numerical Simulations of a Train of Air Bubbles Rising Through Stagnant Water

The Discussion of this exercise covers the following points:

SELECTION CRITERIA FOR SAFETY VALVE

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

Hydrostatics Physics Lab XI

PREDICTION OF TOTAL PRESSURE CHARACTERISTICS IN THE SETTLING CHAMBER OF A SUPERSONIC BLOWDOWN WIND TUNNEL

European directive 2007/23/EC on the placing on the market of pyrotechnical articles : are you concerned?

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

Flow in a shock tube

Gas Laws. Introduction

THE WAY THE VENTURI AND ORIFICES WORK

Kinetic-Molecular Theory

An innovative technology for Coriolis metering under entrained gas conditions

Name Chemistry Pre-AP

Properly Size Vents for Nonreactive and Reactive Chemicals

APTAC Test Procedure for DIERS Round Robin Testing of Vinyl Acetate Polymerization

INFLUENCE OF INITIAL PRESSURE ON THE IGNITION AND COMBUSTION OF A PROPELLING CHARGE. Patrice Franco

CHAPTER 31 IDEAL GAS LAWS

Process Dynamics, Operations, and Control Lecture Notes - 20

Instruction Manual. Pipe Friction Training Panel

Chapter 5. Nov 6 1:02 PM

How to deal with the essential safety requirements of the EU directive in the placing on the market of pyrotechnic articles

Chapter 10: Gases. Characteristics of Gases

D R A F T. Operating Procedures for the NPDGamma Liquid Hydrogen Target at the BL 13. Version 1.00

Simulation of Experiment on Aerosol Behaviour at Severe Accident Conditions in the LACE Experimental Facility with the ASTEC CPA Code

Chapter 13 Fluids. Copyright 2009 Pearson Education, Inc.

Example: 25 C = ( ) K = 298 K. Pressure Symbol: p Units: force per area 1Pa (Pascal) = 1 N/m 2

I. CHEM. E. SYMPOSIUM SERIES NO. 85

A New Way to Handle Changing Fluid Viscosity and the Full-to-empty Effect

Adiabatic Calorimetry

The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine.

2. Determine how the mass transfer rate is affected by gas flow rate and liquid flow rate.

Gilbert Kirss Foster. Chapter 10. Properties of Gases The Air We Breathe

States of Matter Review

METHOD 2E - DETERMINATION OF LANDFILL GAS PRODUCTION FLOW RATE. NOTE: This method does not include all of the

Tube rupture in a natural gas heater

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Applied Fluid Mechanics

8. Now plot on the following grid the values of T (K) and V from the table above, and connect the points.

MODELING OF THERMAL BEHAVIOR INSIDE A BUBBLE

ON PASSIVE MOTION OF THE ARMS FOR A WALKING PLANAR BIPED

World of Chemistry Notes for Students [Chapter 13, page 1] Chapter 13 Gases

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

SIMULATION OF ENTRAPMENTS IN LCM PROCESSES

Pneumatic Conveying Principles BSH&E SEMINAR

Characterizing Flow Losses Occurring in Air Vents and Ejector Pins in High Pressure Die Castings

A. What are the three states of matter chemists work with?

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Chapter 9 Gases: Their Properties and Behavior

EXPERIMENTAL STUDY OF HOT INERT GAS JET IGNITION OF HYDROGEN-OXYGEN MIXTURE

Chapter 10 Fluids. Which has a greater density? Ch 10: Problem 5. Ch 10: Problem Phases of Matter Density and Specific Gravity

POGIL EXERCISE 18 All You Need to Know About Gas Laws

Liquefied gas over water : an experimental approach at medium scale to assess gas/water interactions and vapor dispersion

Transcription:

Sizing safety vents for non-tempered systems (organic peroxides): a new tool at lab scale Luc Véchot, Jean-Pierre Bigot, Marc Kazmierczak, Patricia Vicot To cite this version: Luc Véchot, Jean-Pierre Bigot, Marc Kazmierczak, Patricia Vicot. Sizing safety vents for nontempered systems (organic peroxides): a new tool at lab scale. Michel Cournil. XI Congrès de la Société Française de Génie des Procédés. Des réponses industrielles pour une société en mutation., Oct 27, Saint Etienne, France. Société Française de Génie des Procédés, pp.isbn=2-91239-7-5, 27. <hal-451759> HAL Id: hal-451759 https://hal.archives-ouvertes.fr/hal-451759 Submitted on 3 Jan 21 HAL is a multi-disciplinary open access archive for the deposit and dissemination of scientific research documents, whether they are published or not. The documents may come from teaching and research institutions in France or abroad, or from public or private research centers. L archive ouverte pluridisciplinaire HAL, est destinée au dépôt et à la diffusion de documents scientifiques de niveau recherche, publiés ou non, émanant des établissements d enseignement et de recherche français ou étrangers, des laboratoires publics ou privés.

Sizing safety vents for non-tempered systems (organic peroxides): a new tool at lab scale VECHOT Luc a, BIGOT Jean-Pierre a*, KAZMIERCZAK Marc b, VICOT Patricia b a ENSM-SE, Centre SPIN, Département GENERIC, 158, Cours Fauriel 4223 Saint-Etienne Cedex 2 b Direction Certification, INERIS BP2, 655 Verneuil en Halatte Abstract This paper deals with the development of a new experimental similarity vent sizing tool for non tempered chemical system combining the advantages of both DIERS method (laboratory scale) and UN similarity method (less overconservative). This tool is an extension of the VSP2 (Vent Sizing Package II) adiabatic calorimeter. The objective of this new vent sizing tool is twofold. The first is to provide the required A/V ratio necessary to assure a safe relief. The second is to provide measurement of mass vented during blow-down. This paper gives a description of this tool and exposes the first promising results obtained. Its main limits are also given. Keywords: non tempered reaction ; runaway reaction ; similarity ; cumene hydroperoxide (CHP) ; adiabatic calorimeter 1. Introduction In order to protect chemical reactors from runaway reactions, vent sizing methods, based on data obtained from adiabatic calorimetry and two-phase flow models, were designed by the DIERS (Design Institute for Emergency Relief System). Nevertheless, these methods can lead to unrealistically large vent areas, specially for untempered systems (gas-generating and hybrid systems, peroxide decomposition for example). In the case of peroxide decomposition runaway reaction, DIERS vent area can be overestimated by one order of magnitude (Fauske, 2). More realistic vent areas are obtained with similarity methods such as the one proposed by the United Nation Manual of Tests and Criteria (UN) for the transportation of peroxide. This latter method has the disadvantage of being time consuming, laborious and requires heavy safety precautions. This paper proposes a new similarity vent sizing tool combining the advantages of both DIERS method (laboratory scale) and UN method (less overconservative). This tool allows blowdown experiments to be carried out at laboratory scale. The objectives are both direct determination of the required vent area and measurement of the mass vented during blow-down. First of all, a diagnostic of vent sizing methods for gassy system is done. Reasons which led us to build this new tool are underlined. A description of the new tool is then given. Finally validation tests and limits of the new tool are presented. 2. Context of this work Our initial objective was to understand the reason why DIERS vent sizing method for untempered system was often overconservative. 2.1 DIERS classical method for gassy systems DIERS classical vent sizing method for pure gassy systems (Le). * Corresponding author: bigot@emse.fr 1

dm dt dm dt = W = GA (1) g = mmg Wxi (2) Safe vent size is obtained if the pressure rise can be stopped when gas generation rate is maximum. This leads to consider a pressure rise rate equal to zero at turn-around: dp dt = (3) By assuming ideal gas and constant liquid specific volume, recombining Equations 1 to 3 leads to the following expression for the vent area, A: Vg dt Gc A vi = vgmmg+ (4) T dt ( ) Where v = xv + 1 x v i i g i l is the inlet specific volume. This equation means that at turn-around the volumetric discharge rate is equal to the sum of: Volumetric gas generation rate by reaction Volumetric expansion rate due to thermal dilatation. We will neglect this term as is generally done. All of the terms in Equation 4 (G c, v i, m and m g ) have to be evaluated at turn-around in order to calculate the vent area. They are unfortunately not known. So, DIERS method makes the following safe assumptions at turn-around: all the initial mass is still present in the vessel: m = m (Leung and Fauske, 1987) flow through the vent is homogeneous (Leung, 1995): G c = (G c ) HEM reactor contents are homogeneous (Leung, 1995): α = α hom g m reaction rate is maximum: m = ; this latter is obtained from measurements in an g max adiabatic calorimeter. DIERS vent sizing formula resulting from the above assumptions is then: 2 m Tmax V2 1 dp2 1 A = m T V P dt G ( ) t 2max R max max c HEM hom 2.2 Similarity method: UN 1 litre vessel test The United Nation Manual of Test and Criteria (UN) proposes a similarity method using a 1 dm 3 vessel test. The similarity method reproduces experimentally at small scale the phenomena which occurs at large scale during the runaway and the blow-down. The aim of this method is to obtain similarity concerning: runaway reaction kinetics (as DIERS method does) hydrodynamic behaviour: two phase vent flow and vessel hydrodynamics at small scale representative of the ones occurring at large scale. If these two similarity conditions are obtained then vent area which provides safe protection of the small scale reactor is scaled up using: A/V=constant. Area to volume scale up is conservative in the case of non tempered systems because relative mass loss is larger at larger scale (Leung and Fauske, 1987). The UN 1 litre vessel test leads to a more realistic vent area compared to DIERS method, because prior mass loss and two phase flow are experimentally taken into account. (5) 2

2.3 A laboratory similarity vent sizing tool DIERS vent sizing method has the advantage to be carried out at laboratory scale but it is often overconservative. Even if a more realistic vent size can be obtained with the UN 1 litre vessel test, this latter method has the disadvantage to be time consuming, laborious and requires heavy safety precautions due to the fact that the sample size is large. Our objective is to design a similarity vent sizing tool at laboratory scale. This similarity laboratory tool has to simulate blowdown experiments by the mean of a relief system. We also decided to measure vented mass (Δm) during relief. This can give an estimate of the contribution of this factor in DIERS oversizing. 3. New similarity vent sizing tool features This tool is an extension of the adiabatic calorimeter VSP2. The reactor in which chemical runaway reaction occurs is the VSP2 blowdown test cell. The extension of the VSP2 consists in: the addition of a relief system the addition of a vented mass measurement device the adaptation of VSP2 to blowdown experiments 3.1 Addition of relief system Two venting systems generally exist on chemical reactors or storage vessels: a feed bleed system which is designed to avoid pressure changes when filling or emptying the capacity. This feed bleed system is supposed to vent only gas. a rupture disc (or a safety valve), which is designed to open when the pressure in the reactor reaches the vent set pressure (P s ) Small extra gas quantities are vented via the feed-bleed system. This maintains the pressure in the reactor close to the atmospheric pressure. Gas flow rate is a function of feed bleed size. In case of runaway reaction, pressure in the reactor starts to increase when gas volumetric gas generation rate is greater than the volumetric discharge rate via the feed-bleed system. The rupture disc opens when pressure in the reactor reaches P s. In the new vent sizing tool, the rupture disc is simulated by a relief vent line and the feed bleed system by a feed bleed line (Figure 1). Pressure regulator 2 barg 7 barg 5 L N2 cylinder 5 L N2 cylinder Actuated valve, 1/4 VSP2 Control Box P 2 Feed bleed line Ball valve, 1/8 Metering valve, 1/8 Vented mass ΔP Differential pressure transducer PC Vented mass measurement Secondary containment vessel emptying line, 1/4 Blowdown test cell P 1 T 1 VSP2 4 litre containment vessel Metering valve, 1/8 Actuated ball valve, 1/8 Relief vent line Glass column filled with water Figure 1. New similarity vent sizing tool 3

3.1.1 Relief vent line The relief vent line is connected to the outlet of the blowdown test cell outside of the VSP2 containment vessel (Figure 2). This line is made of 1/8 stainless steel tube (inner diameter = 1.76 mm). The line includes an actuated 1/8 ball valve (C V =.2) followed by a 1/8 metering valve (needle valve) (C V = -.3). When pressure in the test cell reaches set pressure, an opening signal is sent by the VSP2 software to the ball valve actuator. By this way, the test cell is opened to the atmosphere. Contents of the test cell are vented through the metering valve. Venting flow is a function of the metering valve opening. VSP2 4 liter containment vessel Ball valve Metering valve for feed-bleed line Pneumatic actuator Feed-bleed line Vent line Solenoid ball valve Metering valve for relief vent line Figure 2.Picture of relief system 3.1.2 Relief vent line The feed bleed line is installed in parallel to the relief vent line (Figure 2). It s also made of 1/8 stainless steel tube and includes a manual 1/8 ball valve followed by a 1/8 metering valve (needle valve). During a runaway experiment, this line is always open. 3.1.3 Determination of equivalent ideal nozzle diameter for the relief vent line The objective of the new vent sizing tool is to obtain directly the required A/V ratio for a rupture disc. Our relief system is composed of several complex elements and cannot be considered as an ideal nozzle. We determined an equivalent ideal nozzle area corresponding to the relief vent line. For each setting of the metering valve, a depressurization test of the VSP2 containment vessel (using nitrogen) through the relief vent line provides a curve: VM 2 wg dp2 mn 2 = = f( P 2) (6) RT dt The obtained curved has to be compared to a gas flow model for an ideal nozzle described with the following equations: γ + 1 2 γ 1 mcritical = A γ ρ2 P2 γ + 1 (7) 2/ 1 / 2γ P atm subcritical = ρ 2 2 γ 1 P2 P2 m A P where : γ = (C p /C v ) N2 γ ( γ+ ) γ Patm (8) 4

3 "Metering valve" of relief vent line adjusted at 2 turns N 2 mass flow (g/min) 25 2 15 1 5 Experiment Model : Ideal nozzle, diameter =.38 mm 2 4 6 8 1 12 14 16 Pressure (bar) Figure 3. Characterization of relief vent line Figure 3 presents data obtained for the depressurisation of the containment vessel with the metering valve of relief vent line adjusted to 5 turns open. The experimental data are fitted with the model for a.38 mm diameter ideal nozzle. This characterization work is done for different settings of the metering valve. Figure 4 shows that it is possible to simulate a range of equivalent ideal nozzle diameters between.35 mm and.75 mm..8 Equivalent ideal nozzle diameter (mm).75.7.65.6.55.5.45.4.35.3 1 2 3 4 5 6 7 8 9 1 11 Relief vent line metering valve adjustment (number of turn open) Figure 4.Equivalent ideal nozzle diameter for the relief vent line 3.2 Addition of a vented mass measurement system The vented mass measurement device is composed of a glass column (1 m high, 5 cm inner diameter) partially filled with water. The outlet of the relief vent line is immerged into the water column. A differential pressure transducer (-1 mbar) is connected to the bottom of the column. Feed-bleed line PTFE perforated tube Glass column Metering valve for relief vent line Relief vent line Differential pressure transducer (-1 mbar) Figure 5.Picture of vented mass measurement system During relief, chemical products are vented through the column (quench of the reaction is realized at the same time). Gas is ejected while liquid and condensable matters are collected at 5

the top of the water. This leads to an increase of the hydrostatic pressure at the bottom of the column. Flow from the relief vent line is transferred to the water column through a PTFE perforated tube in order to obtain small bubbles. It allows reducing perturbations on pressure measurement. Assuming that vented chemical mixture is not miscible with water, ΔP mesured is translated to vented mass measurement (Δm) through the following formula: m h A A ΔP ΔP g measured Δ = ρmixture Δ mixture column = column (9) ρ mixture : chemical mixing density Δh mixture: height of vented chemical mixing A column : glass column cross section ΔP : initial differential pressure (due to the water) The fraction of initial mass which is vented (Δm/m ) is given by: Δm A ΔP ΔP (1) m m g column measured = 3.3 Adaptation of VSP2 to blow-down experiments Standard DIERS tests with untempered systems are generally done with open cells. Blow-down tests can give higher pressure rise rates (we observed 15 bar/s for 3% cumene hydroperoxyde solution). To avoid test cell swelling, nitrogen pressure rise rate in the VSP2 containment vessel has to be improved. For the standard set up, nitrogen supply is done by the mean of a high pressure cylinder (2 bar, 5 litres) connected to a pressure regulator (outlet pressure set at 7 bar). Maximal pressure rise rate we obtained with this configuration is approximately 6 bar/s. In order to increase containment vessel pressure rise rate, we connected a second nitrogen cylinder (5 litres) to the outlet of the pressure regulator. The pressure of this latter cylinder is fixed by the pressure regulator (7 bar). This device provides quasi-constant pressure at the outlet of the pressure regulator and we could increase containment vessel pressure rise rate up to 15 bar/s. Test cell pressure decrease when vent opens can also be very rapid. The maximal pressure decrease rate obtained with the standard set-up was not always enough to avoid test cell crushing. We added a secondary containment vessel emptying line (1/4 stainless steel tube) to solve this problem. Pressure decrease rate was changed from.2 bar/s to 4.5 bar/s when P 2 = 1 bar. 4. Test of the similarity vent sizing tool : CHP runaway experiments The new vent sizing device was tested by running non tempered system runaway experiments. The decomposition of cumene hydroperoxide (CHP), which produces non condensable gases, was chosen. 4.1 Chemical system and runaway scenario 8% (w/w) CHP solution in cumene is diluted in a high boiling point solvent: 2,2,4-trimethyl- 1,3-pentanediol diisobutyrate. High boiling point of both peroxide and solvent is the criterion which allowed us to consider this system as untempered (CHP: T bp = 116 C at P =.2 bar, solvent: T bp = 28 C at P = 1 bar). The composition of the chemical system is (w/w): 3% CHP, 7.5% cumene, 62.5% 2,2,4-trimethyl-1,3-pentanediol diisobutyrate. A temperature increase rate of.5 C/min simulates a fire scenario. 4.2 Experiment running steps Blowdown experiments running step are the following: Assembly of the test cell according to VSP2 documentation. Vent line characterization (Figure 3) 6

Filling of reactant in test cell Feed-bleed line opening Guard heater activation (will always be activated to limit heat losses) Heating of the sample 2 C SADT + 5 C (= 85 C) by main heater Fire simulation : from 85 C heating of the sample at.5 C/min (constant heating power until the end of the runaway reaction) Relief vent line opening when test cell pressure reaches set pressure (P s = 4.5 bar). 4.3 Results Figure 6 presents a 3% CHP runaway experiment with similarity vent sizing tool. Test cell pressure (P1) and liquid temperature (T1) histories are plotted. The experimental conditions are: Initial reactant mass: 79 g Test cell volume = 125 cm 3 Initial fill level = 65% (v/v) Relief vent line : A/V = 1.36 x 1-3 m -1 (3 turns opened) Feed bleed line metering valve = 3/8 turn opened The whole experiment lasts approximately 3 hours. The runaway period is relatively short (a few minutes). Figure 7 shows a zoom for pressure, temperature and vented mass profiles during the relief period for the same runaway experiment. Time zero corresponds to relief vent line opening. We can observe two pressure peaks which is typical for untempered systems. The first one, corresponding to relief vent line opening, has no obvious influence on temperature profile. This behavior confirms that the chemical system is untempered. Dynamic vented mass measurement could be made. 2.4% of initial mass was vented at turn-around for that particular experiment. Initial fill level = 65% ; A/V =1.36 x 1-3 m -1 3 25 Temperature Pressure 12 1 Temperature ( C) 2 15 1 5 Fire Simulation.5 C/min Heating 2 C --> 85 C Runaway 2 nd pressure peak 1 st pressure peak ; Vent line opening 8 6 4 2 Pressure (bar) 2 4 6 8 1 12 14 16 Time (min) Figure 6.Whole 3% CHP runaway experiment with test cell blowdown 7

Temperature ( C) Pressure (bar) Δm/m (%) 32 3 28 26 24 22 2 2 15 1 5 6 5 4 3 2 1 Initial fill level = 65% A/V= 1.36 x 1-3 m -1 2 4 6 8 1 12 14 2 4 6 8 1 12 14 2 4 6 8 1 12 14 Time (s) Exp Mean Figure 7.3% CHP runaway experiment: relief period (time corresponds to relief vent line opening) 4.4 Limits of the new vent sizing tool The following technical limits have been observed: Working with concentrated peroxide (>3% CHP or example) can lead to test cell failure, volume swell (A/V uncertainty). Limited range of equivalent ideal nozzle diameter can be simulated (.35 mm -.75 mm). Using a metering valve is convenient (easy to change A/V) but not ideal: need to characterize vent line before each experiment because of aging. When initial fill level is higher than 8 %, liquid enters feed bleed line (which is supposed to vent only gas). Technical solutions will be introduced in the future to solve these problems. 5. Conclusions and perspectives A new similarity vent sizing tool combining the advantages of both DIERS method (laboratory scale) and UN method (less overconservative) has been built by extending VSP2 adiabatic calorimeter. This tool allows blow-down experiments to be carried out at laboratory scale. It was tested with CHP in 2,2,4-trimethyl-1,3-pentanediol diiso-butyrate. Dynamic mass vented measurement have been obtained. That is the second main point of the new tool. Taking this vented mass into account can sometimes account for DIERS oversizing by a factor of two. However the following work has to be done to improve the capacity of the new tool: Improvement of vented mass measurement resolution Extension of equivalent diameter range by increasing the relief line size Use of calibrated orifices to have a better assessment of relief vent line and feed bleed line equivalent diameter Reduction of heat losses in order to allow for adiabatic tests. An upcoming paper will deal with discussion of vented mass measurements and specific behaviour of CHP system. It will allow for a discussion of possible causes for DIERS method being so much oversizing. 8

Nomenclature: A : Ideal nozzle equivalent area (m²) G Critical vent mass flux (kgm - ².s -1 ) m: Reactant mass in the vessel (kg) m g : Gas mass (kg) m : Mass flow (kg/s) m g : Specific gas generation rate (kg gas.kg -1.s -1 ) M wg : Molecular weight of the gas (kg/mole) P: Pressure (Pa) P 1 : Pressure in the test cell (Pa) P 2 : Pressure in the containment vessel (Pa) P atm : Atmospheric pressure (bar) P max : Pressure at turnaround (bar) P s : Vent opening pressure (bar) T : Temperature (K) v g : Gas specific volume inside vessel (m 3.kg -1 ). v i : Specific volume at vent inlet (m 3.kg -1 ) v l : Liquid specific volume (m 3.kg -1 ). V c : Containment vessel volume (m 3 ) V g : Volume of gas in the reactor (m 3 ) W : Vented mass flow (kg.s -1 ) x i : Vent inlet flow gas mass fraction Δm: vented chemical mixture mass Δh: height of vented chemical mixture ρ: density (kg.m -3 ) φ : adiabaticity factor Subscripts : Initial conditions 1: Test cell 2: Containment vessel c: Critical (sonic) column: Glass column g: Gas HEM: Homogeneous equilibrium model hom: Homogeneous vessel contents i: inlet mixture: vented chemical mixture R: reactor References Fauske, H.K., 2. Properly size vents for non reactive and reactive chemicals. Chemical Engineering Progress, 17-29 Leung, J.C.; Fauske H.K., 1987. Runaway system characterization and vent sizing based on DIERS methodology. Plant/Operation Progress 6(2), 77-83 Leung, J.C., 1995. Simplified Vent Sizing Methods Incorporating Two-Phase Flow. International symposium on runaway reactions and pressure relief design, AIChE 2-236 UN, Appendix 5 of Recommendations on the Transport of Dangerous Goods, Manual of Tests and Criteria http://www.unece.org/trans/danger/publi/manual/manual_e.html 9

1