DIFFERENTIAL PRESSURE ADJUSTMENT Partner valve

Similar documents
FLOW RATE DYNAMIC BALANCING

Pressure independent control valve (PICV) FLOWMATIC

ACCREDITED. Technical specifications series

CALEFFI. Pre-adjustable pressure reducing valves with self-contained cartridge series 01085/17 GB. replaces 01085/14 GB

CALEFFI. Motorised temperature regulating unit for heating systems. 167 series 01239/15 GB. replaces dp 01239/13 GB. Function

Installation, commissioning and servicing instructions

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions

Pre-adjustable pressure reducing valves with self-contained cartridge

CALEFFI. Ball zone valves. series /03 GB

CALEFFI. Flow rate metering device. 683 series 01040/10 GB. Function

Heat Pump Connections and Interior Piping

differential pressure regulating valve - threaded

Some system examples

STAP. Differential pressure controller DN

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Installation, commissioning and servicing instructions

Automatic balancing valves ASV

STAP. Differential pressure controllers DN , ANSI flanges

Chapter 10: Bidirectional Flow Controls

Function. brass EN CW617N brass EN CW617N brass EN CW614N. brass EN CW614N brass EN CW617N EPDM

Lesson 6: Flow Control Valves

STAP. Differential pressure controller DN 15-50

Overview of types. T5-R B2/R B2 en v Subject to changes 1 / 4. k vs (Sequence 2)

ACCREDITED. Function. series 5360/

Technote. Frese PVS - Dynamic Pressure and Flow Regulation Valve. Application. Features. Benefits.

Installation, commissioning and servicing instructions

Lecture 19 PRESSURE-CONTROL VALVES [CONTINUED]

Differential pressure controller (PN 25) AVP - return and flow mounting, adjustable setting

STAD Series. Balancing and control valves. Technical Data Sheet. WattsIndustries.com

Dimensioning open-close, control and pressure-independent valves. Table of contents. General notes for project planning

STAP. Differential pressure controllers DN , ANSI fl anges

Cim 787 Variable orifice balancing valve

ACCREDITED H series Inclined pressure reducing valve sizes DN 15 (1/2 ) and DN 20 (3/4 )

VFPIP/VFPIM/VFPI 15-25

Technote. Frese ALPHA cartridges. Application. Features. Benefits.

Description. Measuring Device 3760XBI USP. Balancing

130400A 1/2 NPT Female A 3/4 NPT Female A 1 NPT Female A 1 1/4 NPT Female A 1 1/2 NPT Female A 2 NPT Female

Differential pressure controller (PN 16) AHP - return mounting, adjustable setting

Automatic balancing valves ASV

PCTV/PCMTV/PCTVS15-25

2-port and 3-port valves PN 16

AVP-F. p setting range (bar) Code No. 003H6200

Time-Delay Electropneumatic Applications

PVM 15-50, differential pressure valves

Application Notes for Valve Sizing Sizing valves for steam service with the aid of sizing charts

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

CALEFFI. Inclined pressure reducing valves series 01024/17 GB. replaces 01024/14 GB

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

PCMTV Pressure independent control valves, DN20-DN32 with integrated flow limiter for thermal emitters and differential pressure regulator

Experiment Instructions. Circulating Pumps Training Panel

Function. Code Automatic filling units with pressure gauge connection Size 1/2 Code Automatic filling units with pressure gauge Size 1/2

Introduction. Part one: Identify the Hydraulic Trainer Components

Products no longer available

553 Series.

Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN

VARIABLE ORIFICE BALANCING VALVE PN 25 TECHNICAL DATA SHEET. Approved by*: Main features:

Technote. Frese PV-SIGMA Compact Dynamic Pressure and Flow Regulation. Description. Application. Operation. Features. Benefits.

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V

Radiator valves VDN2.. VEN2.. VUN2..

Automatic balancing valves ASV

Upgradable balancing valves USV

Differential pressure and flow controller (PN 16) AVPQ - return mounting, adjustable setting

CALEFFI. Reduced pressure zone backflow preventer. 574 series 01022/18 NA D E C F B D E. Function

Pressure reduction controller (PN 16, 25, 40)

Pettinaroli Pressure Independent Control Valves. EvoPICV

Pressure Independent Control Series

Differential pressure control and flow limiter AVPB/AVPB-F, PN 16

Differential pressure controller (PN 16) AVPL - return mounting, adjustable setting

CALEFFI. DISCAL deaerator. 551 series 01060/17 GB. replaces dp 01060/14 GB

Type OSE. Type OSE Slam-Shut Valve. Features and Benefits. Introduction. Bulletin 71.6 D102356X012. April 2018

Automatic balancing valves

Differential pressure controller (PN 16) AVPL return mounting, adjustable setting

Seated valve for steam (PN 25) VFS 2 2-way valve, flange

By-pass valves Series 466 Thermatic - Series USVR

Differential Pressure Control Valve. Passim

MRO Oil-Air Ratio Regulator

6-way characterised control valves DN15 / DN 20 / DN 25

Technical data sheet. Type overview. Technical data. Safety notes. T5-R2.. Open-close en v Subject to changes 1 / 3

safety shut-off Valve HON 703 / HON 704

AVPQ/AVPQ-F, PN 16. Application

Reset Volume Controller 2 Reversing Relay 3 Air Valve Actuator 4 Lower-of-Two-Pressures Relay 4 Diverting Relay 5 Higher-of-Two-Pressures Relay 5

Technical Manual. Liquid Level Transmitter CT801-LB/S

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

V311. Venta. Three-way Plug Valve, Flanged PN 16

Series MX pressure regulators 3/

The Discussion of this exercise covers the following points:

Radiator valves VDN1.. VEN1..

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

2-port seat valves PN25 with externally threaded connections

Description Pressure range Connection thread Device Page

Leak free Pipe Rupture Valve for Excavators

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

971 Series Pressure Reducing Regulators

DIFFERENTIAL PRESSURE REGULATING VALVE zcon

V5001P. Kombi-Auto Differential Pressure Control Valve. Product specification sheet

Cover Page for Lab Report Group Portion. Head Losses in Pipes

BALANCING OF CONTROL LOOPS

PILOT OPERATED PRESSURE REDUCER VALVE - Series VR4R

High Performance BSP Dial Up Pattern Pressure Reducing Valve

VZL valve - 2/3/4-way

Transcription:

alancing part 7 TENIL FOUS DIFFERENTIL PRESSURE DJUSTMENT Partner valve The use of the ΔP regulators to keep the differential constant at the ends of a secondary circuit is usually accompanied by the installation of a manual balancing valve, this partner valve installed on the delivery line at the compensation valve installation on the return line. The partner valve is essentially a manual balancing valve fitted with an adjustable obturator through an external knob and two pressure test ports located at the obturator ends, which can be used for the connection capillary with the ΔP regulator valve. 3,,, 0, 3 0 The partner valve can be used with two different modes depending on how the capillary is connected before or after the obturator.

ONNETION WIT PILLRY DOWNSTREM TE OTURTOR With the capillary connected after the obturator, the partner valve is external to the circuit to which the ΔP is kept constant. y schematizing the secondary circuit as shown in the figure below, the partner valve does not have any influence within the controlled circuit. t the aforementioned circuit, the ΔP valve maintains a constant differential of ΔP OST and, as previously seen, the flow rate depends only on the Kv of the adjustment valve. The partner valve therefore contributes to reduce the differential given by the head of the primary circuit. ΔP VP ΔP cost ΔP OST ΔP ΔP In this configuration its application is a support to the ΔP regulator in order to keep the differential to be reduced at an acceptable value. The diagram below shows a circuit of a certain length where the head provided by the pump increases getting closer to the pump itself and at the same time there is an increase of the differential that the ΔP regulator valve has to reduce. s can be seen, switching from circuit to, the head that the valve ΔP has to compensate increases considerably: ΔP ΔP = = - 0 = kpa ΔP ΔP = = 0-0 = 30 kpa ΔP ΔP = = 80-0 = 70 kpa aving a fairly high differential already in the design conditions means letting the differential compensating valve work with the obturator very close to the seat; in this situation, in partial load conditions, the already very stressed valve may be forced to further reduce the bore cross section, thus failing to work in the best conditions. 0 0 0 70 30 80 0 On the circuit in consideration, a partner valve will be installed for each branch with the capillary connected downstream of the obturator. For a secondary circuit balanced by a ΔP valve, the minimum upstream head to operate the valve properly can approximate at one and a half the head value required for the circuit. =, ΔP =, 0 = kpa OST

Therefore under these conditions the ΔP =, MIN to be ΔP =, 0 = kpa OST "used" by the compensating valve is: = = 0 = kpa The partner valve setting is: ΔP S = - = - 0 - = 0 kpa ΔP VP = - = 0-0 - = kpa ΔP VP = - = 80-0 - = kpa p (mm w.g.) 0,000 0,,, 3 3, 0 p (kpa) 00 0 0,000 0 0,000 0,000 80 0 0 00 PRTNER VLVE DJUSTMENT p (mm w.g.) 0,000 0,,, 3 3, p (kpa) 00 The 00valve must be adjusted using the Kv diagrams. In the case of circuit, for a design flow rate of 300 00 l/h, the partner valve must introduce a 0 kpa load loss. 0 s indicated by the diagram, the partner valve 0, 0,0 0, must be set to the 0,3 0,, 0 "," position, with a Kv value of 0,9 m 3 G (m /h. 3 /h),000,000,000 0 0 0 00 setting position Kv (m 3 /h) 0,,, 3 3, (Kvs) 0,3 0, 0,9,38,7,,8,9 00 circuit circuit circuit Within the individual secondary circuits, the pressures distribution will be:, 0 00 0 0,0 0, 0,3 0, 0,, 0 setting position 0,,, 3 3, (Kvs) Kv (m 3 /h) 0,3 0, 0,9,38,7,,8,9 0, G (m 3 /h) 0 80 0 0 kpa 0 kpa s can be seen, the ΔP regulators are configured to work all under the same design conditions.

ONNETION WIT PILLRY UPSTREM OF TE OTURTOR. Unlike the previous case, when the capillary is connected before the obturator, the partner valve is an integral part of the circuit whose ΔP is kept constant by the differential regulator. If the secondary circuit is schematized as in the following figure, the partner valve has a direct influence within the controlled circuit, whose ΔP valve ends maintains a constant differential ofδp OST. To exemplify the situation it is hypothesized that the secondary circuit to be controlled with the ΔP valve is composed of three identical circuits connected by a vertical distribution. ΔP cost SEONDRY IRUIT The nominal flow rate of nominal load loss of 0 kpa is the design data of the individual circuit. The vertical distribution causes a kpa load loss for each connection section. Therefore the secondary circuits and are subjected to a head of = kpa and = kpa. head other than the nominal head causes a greater flow rate in the individual circuits than the design flow rate, which can be calculated with the balancing factor F. IRUIT WIT ΔP REGULTOR To make the secondary circuit independent of the head variations of the primary circuit, the circuit is balanced with a differential compensating valve. The reference positions for setting the ΔP regulator could be kpa (not recommended because below the nominal value) or at 0 kpa. In the case of a differential compensating valve set at 0 kpa, the overall flow rate for the secondary circuit is as follows: F = 0, 0, = =, 0 0, 0 0, G = G = 990 = 0 l/h G = F G =, 300 = 0 0, 0, F = = =, 0 G = F G =, 300 = 30 l/h, 30 l/h 0, 37 l/h 30 l/h 30 l/h 7, 0 l/h 37 l/h 0 l/h 30 l/h 7, 0 0 l/h 0 kpa

IRUIT WIT ΔP REGULTOR ND LNING VLVE ON SINGLE IRUIT In these conditions, an appropriate solution would be to insert a manual balancing valve on each individual circuit, set so as to return the design flow rate to the nominal value. IRUIT WIT ΔP REGULTOR ND PRTNER VLVE If the insertion of balancing valves is not possible, the partner valve connected to the upstream capillary can be used. In this case, the setting must be equal to the difference between the setting value of the differential compensating valve (0 kpa) and the nominal load loss of the circuit ( kpa). of partner valve = 0 - = kpa 0 8 900 l/h 8 30 l/h 0 0 kpa The head unbalancing caused by the internal distribution of the secondary circuit are not balanced in this configuration. 0 0 kpa ONLUSION Depending on how it is connected to the differential compensating valve, the partner valve has two completely different functions: With the capillary connected downstream of the obturator the load loss that the partner valve introduces is not part of the secondary circuit controlled by the ΔP valve but of the primary circuit. Its function, in this case, is to prevent the ΔP regulator from working with the obturator too close to the closing position With the capillary connected upstream of the obturator the partner valve is an integral part of the circuit controlled by the differential compensating valve and has the function of "refining" the differential compensating valve setting as much as possible to the nominal value, adjusting the flow rate accordingly. REFERENE DOUMENT: TE. ROURE 00 Visit aleffi on YouTube youtube/aleffivideoprojects 087G WE RESERVE TE RIGT TO MKE NGES ND IMPROVEMENTS TO TE PRODUTS ND RELTED DT IN TIS PULITION, T NY TIME ND WITOUT PRIOR NOTIE. aleffi S.p.. S.R. 9 n. 800 Fontaneto d gogna (NO) Italy Tel. +39 03 89 Fax +39 03 8373 info@caleffi.com www.caleffi.com opyright 07 aleffi