ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

Similar documents
Bio-Effluents Tracing in Ventilated Aircraft Cabins

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM

AN IMPROVED CROSS VENTILATION MODEL IN WINDY REGIONS

Effect of airflow direction on human perception of draught

CFD Analysis ofwind Turbine Airfoil at Various Angles of Attack

COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B. By Kimbal A. Hall, PE

OPTIMIZATION OF SINGLE STAGE AXIAL FLOW COMPRESSOR FOR DIFFERENT ROTATIONAL SPEED USING CFD

Surrounding buildings and wind pressure distribution on a high rise building

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES

Free Surface Flow Simulation with ACUSIM in the Water Industry

Determination of the wind pressure distribution on the facade of the triangularly shaped high-rise building structure

Cross Infection in Hospital Wards with Downward Ventilation - Different Locations of Return Openings without and with Partitions between Beds

Wind Effect on Smoke Exhaust by Natural Vent

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

CFD Analysis of Giromill Type Vertical Axis Wind Turbine

OPTIMIZATION OF RECUPERATER FIN GEOMETRY FOR MICRO GAS TURBINE

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN

Astudy of the air quality in the breathing zone in a room with displacement ventilation

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

CFD and Physical Modeling of DSI/ACI Distribution

CFD BENCHMARKING: HAMER HALL AUDITORIUM CASE STUDY

WIND AFFECTED ISOTHERMAL AIRFLOW PATTERNS IN A SCALE MODEL OF A SWINE BARN MEASURED WITH PIV SYSTEM

Statesville, NC. Results of AM ASHRAE 110 Laboratory Fume Hood Performance Evaluations Venturi Hood

Development of virtual 3D human manikin with integrated breathing functionality

COMPARISONS OF COMPUTATIONAL FLUID DYNAMICS AND

An Impeller Blade Analysis of Centrifugal Gas Compressor Using CFD

CFD Simulation and Experimental Validation of a Diaphragm Pressure Wave Generator

AERODYNAMIC CHARACTERISTICS OF NACA 0012 AIRFOIL SECTION AT DIFFERENT ANGLES OF ATTACK

A FIELD STUDY OF THE AIR CHANGE EFFECTIVENESS OF OVERHEAD AIR DISTRIBUTION AND DISPLACEMENT VENTILATION IN HEALTHCARE

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS

This is an author produced version of Determining the optimum spacing and arrangement for commercial wind towers for ventilation performance.

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test

ZIN Technologies PHi Engineering Support. PHi-RPT CFD Analysis of Large Bubble Mixing. June 26, 2006

A CFD ANALYSIS OF VENTILATION SYSTEM OF LAVATORY IN OFFICE BUILDING , Higashi-mita, Tama-ku, Kawasaki, Japan

Influence of rounding corners on unsteady flow and heat transfer around a square cylinder

CFD Study of Solid Wind Tunnel Wall Effects on Wing Characteristics

Two-way Fluid Structure Interaction (FSI) Analysis on the Suction Valve Dynamics of a Hermetic Reciprocating Compressor

NUMERICAL SIMULATION OF STATIC INTERFERENCE EFFECTS FOR SINGLE BUILDINGS GROUP

CFD analysis & Experimental Investigation of Shell & Tube Type Heat Exchanger with modified Slotted Baffles

Proceedings of the ASME th Biennial Conference on Engineering Systems Design and Analysis ESDA2014 June 25-27, 2014, Copenhagen, Denmark

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

MODELING THE PERFORMANCE OF PERSONALIZED VENTILATION UNDER DIFFERENT ROOM AIRFLOWS

Centre for Offshore Renewable Energy Engineering, School of Energy, Environment and Agrifood, Cranfield University, Cranfield, MK43 0AL, UK 2

OPTIMIZING THE LENGTH OF AIR SUPPLY DUCT IN CROSS CONNECTIONS OF GOTTHARD BASE TUNNEL. Rehan Yousaf 1, Oliver Scherer 1

Measurement and simulation of the flow field around a triangular lattice meteorological mast

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

Optimization of Ejector's Performance With a CFD Analysis. Amanda Mattos Karolline Ropelato Ricardo Medronho

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

STAR European Conference 2011

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM

Air Craft Winglet Design and Performance: Cant Angle Effect

Wind tunnel effects on wingtip vortices

VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

Investigation on Divergent Exit Curvature Effect on Nozzle Pressure Ratio of Supersonic Convergent Divergent Nozzle

How to Test Air Change Effectiveness

NUMERICAL AND EXPERIMENTAL INVESTIGATION OF THE FLOWFIELD IN A BLOWDOWN WIND TUNNEL

A Study on the Effects of Wind on the Drift Loss of a Cooling Tower

Workshop 1: Bubbly Flow in a Rectangular Bubble Column. Multiphase Flow Modeling In ANSYS CFX Release ANSYS, Inc. WS1-1 Release 14.

Inlet Swirl on Turbocharger Compressor Performance

Development of Biomimicry Wind Louver Surface Design

The Effect of Impeller Width on the Location of BEP in a Centrifugal Pump

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

Effect of Inlet Clearance Gap on the Performance of an Industrial Centrifugal Blower with Parallel Wall Volute

Numerical Simulations of a Train of Air Bubbles Rising Through Stagnant Water

Wind pressure coefficient determination for greenhouses built in a reclaimed land using CFD technique

Full scale measurements and simulations of the wind speed in the close proximity of the building skin

Numerical Simulation And Aerodynamic Performance Comparison Between Seagull Aerofoil and NACA 4412 Aerofoil under Low-Reynolds 1

Results of Field Measurements and CONTAM Simulation. Building Science

Australian Journal of Basic and Applied Sciences. Pressure Distribution of Fluid Flow through Triangular and Square Cylinders

Aerodynamics of a wind turbine

SIMULATION OF THE CROSSWIND AND THE STEAM ADDITION EFFECT ON THE FLARE FLAME

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

Numerical and Experimental Investigation of the Possibility of Forming the Wake Flow of Large Ships by Using the Vortex Generators

The Usage of Propeller Tunnels For Higher Efficiency and Lower Vibration. M. Burak Şamşul

SIMULATIONS OF HYDROGEN RELEASES FROM A STORAGE TANKS: DISPERSION AND CONSEQUENCES OF IGNITION

THEORETICAL EVALUATION OF FLOW THROUGH CENTRIFUGAL COMPRESSOR STAGE

Numerical Simulation for the Internal Flow Analysis of the Linear Compressor with Improved Muffler

Volume 2, Issue 5, May- 2015, Impact Factor: Structural Analysis of Formula One Racing Car

Investigation on 3-D Wing of commercial Aeroplane with Aerofoil NACA 2415 Using CFD Fluent

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it

MODELING AND SIMULATION OF VALVE COEFFICIENTS AND CAVITATION CHARACTERISTICS IN A BALL VALVE

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

Two phase discharge flow prediction in safety valves

CYCLE ANALYSIS OF LINEAR COMPRESSORS USING THREE- DIMENSIONAL CFD

Numerical and Experimental Investigations of Lift and Drag Performances of NACA 0015 Wind Turbine Airfoil

Effect of Diameter on the Aerodynamics of Sepaktakraw Balls, A Computational Study

Numerical Investigation of Multi Airfoil Effect on Performance Increase of Wind Turbine

Computational Analysis of the S Airfoil Aerodynamic Performance

Performance Analysis of Centrifugal Compressor under Multiple Working Conditions Based on Time-weighted Average

The Effect of Icing on the Performance of NACA Wind Turbine Blade

Analysis of pressure losses in the diffuser of a control valve

Increase in Evaporation Caused by Running Spa Jets swhim.com

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

AN EVALUATION OF ENCAPSULATED OIL FLOODED SCREW COMPRESSOR SYSTEMS. Nikola Stosic, Ahmed Kovacevic, ian K Smith and Elvedin Mujic

Performance of GOE-387 Airfoil Using CFD

The effect of wind speed on the performance of a split chimney

Transcription:

3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS Ahmed F. Elharoun, Ahmed A. Fahim, Esmail M. Bialy, and Essam E. Khalil Cairo University, Cairo, Egypt The well-designed ventilation system ensures thermal comfort, indoor air quality and yield energy saving by avoiding excessive high values of Air Changes per Hour (ACH). Stratum ventilation has been a recently proposed air distribution system. The current CFD research investigates the performance of stratum ventilation in an office by using two values of the air change per hour, changing the exhaust location, and changing the supply location. In addition, the numerical model studied the displacement ventilation and mixing ventilation and their results were compared with that of stratum ventilation. The temperature, velocity distribution, CO 2 concentration, ventilation effectiveness, effective draft temperature, and air diffusion performance index (ADPI) are discussed for all cases.the model was built and the mesh was generated using gambit 2.3.16 yielding 1.4 million cells. In addition, the model was simulated using Fluent 14. Model validation was done against experimental data using standard k-ε model turbulence model with acceptable agreement to ensure the reliability of the Computational Fluid Dynamic (CFD).From the research, the air change per hour (ACH) has a large effect on the stratum ventilation performance, and it was found that using 5 ACH gives better conditions in terms of thermal comfort and indoor air quality. The supply location is recommended to be above the occupant height to ensure that, the air reaches the breathing zone well. From investigating the stratum, displacement and mixing ventilations, the stratum ventilation provides better velocity, temperature, CO 2 concentration, ventilation effectiveness, and air diffusion performance index and ensures thermal comfort and indoor air quality. Keywords: Stratum ventilation, CFD, IAQ, ADPI and Ventilation effectiveness 1. INTRODUCTION The present research concerns with indoor air quality and thermal comfort under stratum, displacement and mixing ventilation. The air diffusion performance index (ADPI) and ventilation effectiveness are studied in all cases to evaluate the performance of the air distribution system and to check thermal comfort.stratum ventilation is a recently air distribution system. The air supply is located at the sidewall of the room.the air enters the room with high velocity to ensure that the air -237-

delivered enough to the occupant breathing zone, which improves the inhaled air quality. 1.1 Indoor Air Quality People spend more times indoors, which they exposed to air pollutants in their offices, schools and other indoor environments that will effect on their health. Exposure to these pollutants can lead to headaches, irritation in eye, nose and throat, difficulty breathing and Confusion. So the IAQ is closely related to occupant work efficiency and health. The most effective way to reduce indoor air pollution is to reduce or eliminate the sources. Occupants are considered as a source of contamination due to their activities.carbon dioxide is an indoor pollutant emitted in occupant exhalation process and correlates with its metabolic activity. 1.2 Thermal Comfort Thermal comfort is a condition of mind which expresses satisfaction with the surrounding environment, the main factors that affect on the human thermal comfortare air temperature, air velocity and movement, relative humidity and metabolic rate. 1.3 Air Diffusion Performance Index (ADPI) Air diffusion performance index is calculated to evaluate the performance of the air distribution system and it is statically related to the local air temperature and velocity. Air diffusion performance index is also the percentage of the points where the effective draft temperature is between -1.5 K and +1 K, when the air velocity less than 0.36 m/s. The ADPI equal or greater 80% is acceptable. The effective draft temperature for mixing ventilation and displacement ventilation is θ edt = (t x - t c )-8(v x - 0.15) and for stratum ventilation is θ edt = (t x - t c )- (v x 1.1), where θ edt = effective draft temperature (K), t x = local airstream temperature ( ), t c = average room temperature( ), v x = local airstream speed (m/s). In the present research 34 points chosen in the comfort zone and using its temperature, and velocity to calculate the effective draft temperature, then the percentage of these points that in the range of [-1.5 K] and [+1 K] will calculated and this percentage will represent the ADPI. Figure 1. Location of the points for calculating ADPI at z= 1.1 m -238-

1.4 Ventilation Effectiveness Ventilation effectiveness defined by the fraction of the outdoor air delivered to the space that reaches the occupied zone. It is calculated to evaluate the performance of the ventilation system when it s higher than unity it means that the ventilation is efficient, and it has the following formula: VE= (t out t in ) / (t bz t in ), where VE= Ventilation effectiveness, t in = supply air temperature, t bz = breathing zone air temperature, t out = exhausted air temperature. 2. CFD Model Validation In the current research, model validation was done against experimental data done by [1] using standard k-ε model turbulence model toensure the reliability of the Computational Fluid Dynamic (CFD). The published model (Fig. 2) was re-built and the mesh was generated using gambit 2.3.16 yielding 1400000 cells. The air enters the room with (0.2 m 0.17 m) supply grill and has a temperature of 21 and a velocity of 1.19 m/s. Heat loads of human, computer and lamps are 75 W, 180 W and 2 72 W, respectively. For more details on geometry and boundary conditions, please refer to the original published paper [1].The model was simulated using Fluent 14. Model validation was done against experimental data using standard k-ε model turbulence model. The simulation results are in acceptable agreement with experimental data as shown in Fig. 3a and Fig. 3. Figure 2. Configuration of the office [1] -239-

Figure 3a. Comparison between measured and present velocity profiles at line x= 2.95 m, y= 1.45 m. Figure 3b. Comparison between measured and present velocity profiles at line x= 1.65 m, y= 1.45 m. 3. CASE STUDY DESCRIPTION The office room under investigation as shown in Fig. 4 is 3.9m*2.9m*2.6m, with a 0.60 m*0.60 m perforated exhaust with 15.3% as the effective area ratio. The office wall is a constant temperature 25 C. The seated occupant heightis 1.2 m and is treated as a wall at a constant temperature according to Guyton [2] and its mean skin temperature is equivalent to 34 C. One point source of CO 2 was introduced at the height of 1.1 m of the occupant to simulate exhalation, the volume of the gases in dry expired air under standard conditions are 74.5% N 2, 15.7% O 2, 3.6% CO 2 and 6.2% H 2 O[2]. The volume of 0.5 liters is considered as the volume of an average breath per occupant, the mass flow or expired air from the occupants is calculated as 2*10-4 kg/s per occupant based on 20 times per minute during normal activity, [3]. The outdoor concentration of CO 2 was found to be 510 ppm as measured by Cairo oil refining company (cited by [4]). The computer is 0.4m*0.4m*0.4m, the two lamps are 0.17m*1.24m*0.07m, and the bookshelf is 0.4m*0.8m*1.85m. Heat loads of the occupant, lamps and computer are 75 W, 2*72 W and 180 W, respectively [1]. For all the stratum ventilation (SV) system cases and the mixing ventilation system the supply grill is 0.2m*0.17m.Cases 1and 2 (Fig. 4) have fixed parameters except for the ACH, which has the values of 5 and 10respectively. In case 3 the supply is at a height z=0.9m (Fig. 4). For the displacement ventilationsystem (DV) (case 4) the supply diffuser is 0.3m*1m (Fig. 4). In the mixing ventilation (MV) (case 5) the supply is at the center of the ceiling (Fig. 4).Inlet air velocity and temperature for all cases are summarized in Table 1. -240-

Office configuration for case 1and case 2 Office configuration for case 4 Office configuration for case 3 Office configuration for case 5 Figure 4. All cases configurations Table 1. Inlet air conditions Case ACH Inlet air temperature ( C) Inlet velocity (m/s) Case 1 5 19 1.2 Case 2 10 19 2.4 Case 3 5 19 1.2 Case 4 (DV) 5 19 0.136 Case 5 (MV) 5 19 1.2 The converged residual for continuity equation is less than 10-5. The converged residual for energy equation is less than 10-6. The converged residuals for species are less than 10-6.The converged residuals for momentum and k-ε turbulence equations are less than 10-3. 4. RESULTS AND DISCUSSIONS The current CFD research investigates the performance of stratum ventilation in an office by using two values of the air change per hour, changing the exhaust location, and changing the supply location. In addition, the numerical model studied the displacement ventilation and mixing ventilation and their results were compared with that of stratum ventilation. The -241-

temperature, velocity distribution, CO 2 concentration, ventilation effectiveness, effective draft temperature, and air diffusion performance index (ADPI) are discussed for all cases. For the stratum ventilation (case 1), the air velocity in the breathing zone is depicted in Fig. 5 in a horizontal plane at 1.1 m above the floor. The air stream velocities in front of and around the occupant are shown to have higher magnitudes than those in the other zones. The air velocity at the head level in front of the occupant is 0.18 m/s, which is less than the recommended maximum of 0.25 m/s to reduce drafts as mandated by ASHRAE [5]. The air temperature in the breathing zone is depicted in Fig. 6 in a horizontal plane at 1.1 m above the floor. The air stream temperature in front of and around the occupant is lower than that in the other zones. The air temperature is 24 C at the head level in front of the occupant and is high around the computer (heat source). The CO 2 concentration in the breathing zone is depicted in Fig. 7 in a horizontal plane at 1.1 m above the floor. The average concentration of CO 2 is 638 ppm the concentration at the head level in front of the occupant is 647 ppm. The air diffusion performance index is 94.11% as in Table 2 and the ventilation effectiveness is 1.3. In case 2, as shown in Fig.8, the air stream velocities in front of and around the occupant have higher magnitudes than those in the other zones. In addition, the maximum air velocity is at the spot near the supply. The air velocity at the head level in front of the occupant is 0.68 m/s, which is higher than the recommended maximum of 0.25 m/s to reduce drafts as mandated by ASHRAE [5], which make the occupant uncomfortable.the air temperature in the breathing zone is also depicted in Fig. 9 in a horizontal plane at 1.1 m above the floor. The air stream temperature in front of and around the occupant is lower than that in the other zones.the air temperature is 22.5 C at the head level in front of the occupant and is high around the computer (heat source). The CO 2 concentration in the breathing zone is depicted in Fig. 10 in a horizontal plane at 1.1 m above the floor.the average concentration of CO 2 is 582 ppm and the concentration at the head level in front of the occupant is 555 ppm.the air diffusion performance index is 82.35%as in Table.3 and the ventilation effectiveness is 1.55. Increasing the ventilation rate (ACH) from 5ACH to 10ACH, the air velocity in the breathing zone exceeds the maximum that mandated by ASHRAE [5] in addition, the air diffusion performance index decreased. So the 5 ACH provides better conditions and saving energy. Figure 5. Velocity contours (m/s) at z= 1.1 m Figure 6. Temperature contours( C) at z= 1.1 m -242-

Figure 7. CO 2 concentration contours (ppm) Figure 9. Temperature contours ( C) Figure 8. Velocity contours (m/s) Figure 10. CO 2 concentration contours (ppm) Table 2. Effective Draft Temperature at different points in case 1 Table 3. Effective Draft Temperature at different points in case 2. -243-

For case 3 when the air supply is at a height z=0.9mfrom the floor, the inlet air dropped away from the occupant in the lower zone andlarge amount of the air was obstructed by the desk. Therefore, the air does not reach the breathing zone with enough.the air velocity in the breathing zone is depicted in Fig. 11 in a horizontal plane at 1.1 m above the floor. The air velocity at the head level in front of the occupant is 0.044 m/s, which is low too much and means that the air is quasi stagnant. The air temperature in the breathing zone is depicted in Fig. 12 in a horizontal plane at 1.1 m above the floor. The temperature is high in the breathing zone because the air does not reach the breathing zone well, and due to the presence of the computer (heat source) where the air velocity around it does not enough to cool it.the air temperature is 25.7 C at the head level in front of the occupant. The CO 2 concentration in the breathing zone is depicted in Fig. 13 in a horizontal plane at 1.1 m above the floor. The average concentration of CO 2 is 648 ppm and the maximum concentration is in the small area close to the nose due to breathing, and the concentration at the head level in front of the occupant is 801 ppm. The air diffusion performance index is 23.52%as in Table.4and the ventilation effectiveness is 1. The distance between the air terminal and the occupant in case 3 is longer than that in case 1, which the air dropped away from the occupant and large amount of air obstructed by the desk. Therefore, the air does not reach the breathing zone enough. The air velocity at the head-chest level decreased largely, also the temperature and CO 2 concentration increased largely. Therefore, the air supply location should be above the occupant height to ensure that the air reaches the breathing zone enough for achieving thermal comfort and indoor air quality. Figure 11. Velocity contours (m/s) Figure 12.Temperature contours ( C) -244-

Table 4. Effective Draft Temperature at different points in case 3 Figure 13. CO 2 concentration contours (ppm) For the displacement ventilation (case 4), the air enters the room from a supply near the floor at the room corner.the velocity is high near the supply and gradually decreased inside the room. The air velocity in the breathing zone is depicted in Fig. 14 in a horizontal plane at 1.1 m above the floor. The air velocity is relatively high in the region in front of the supply where the air stream passes. In addition, the air velocity is high on the desk. The air velocity in front of the occupant at the head level is 0.035 m/s, which is low too much and means that the air is quasi stagnant. The air temperature is low near the floor, and the supply in addition, the air gradually gains heat. The air temperature in the breathing zone is depicted in Fig. 15 in a horizontal plane at 1.1 m above the floor. The air temperature is low away from the computer and higher around the computer. In addition, the air temperature is high in the breathing zone due to the presence of the computer (heat source) where the air velocity around the computer does not enough to cool it. The air temperaturereaches 32.5 C at the head level in front of the occupant that is very high and makes the occupant uncomfortable. The CO 2 concentration in the breathing zone is depicted in Fig. 16 in a horizontal plane at 1.1 m above the floor. The average concentration of CO 2 is 688 ppm. The concentration is high in the breathing zoneexceeding 1000 ppm. The concentration is low near the supply where the inlet air has low concentration.the air diffusion performance index is 17.64% as in Table 5 and the ventilation effectiveness is 0.66. For the mixing ventilation (case 5), the air enters the room from the ceiling and flows downward.the air velocities in the air stream have higher magnitudes than those in the other zones. The air velocity in the breathing zone is depicted in Fig. 17 in a horizontal plane at 1.1 m above the floor. The maximum air velocity is at the spot below the supply. The air velocities around the occupant and the computer are low compared with stratum ventilation case 2. In addition, the air velocity at the head level in front of the occupant is 0.145 m/s, which is less than the recommended maximum of 0.25 m/s to reduce drafts as mandated by ASHRAE [5]. The temperature in the air stream is lower than that in the other zones. The air temperature in the breathing zone is depicted in Fig. 18 in a horizontal plane at 1.1 m above the floor. The minimum air temperature is at the spot below the supply, and the temperature -245-

is high around the computer as the air velocity around the computer is not enough to cool it. The air temperature is 25 C at the head level in front of the occupant. The CO 2 concentration in the breathing zone is depicted in Fig. 19 in a horizontal plane at 1.1 m above the floor. The average concentration of CO 2 is 645 ppm and the minimum concentration is at the spot below the supply while the maximum concentration is in the area close to the nose due to breathing, and the concentration in front of the occupant is 830 ppm. The air diffusion performance index is 61.76%as in Table.6 and the ventilation effectiveness is 1. Figure 14. Velocity contours (m/s) Figure 16. CO 2 concentration contours (ppm) Figure 15. Temperature contours ( C) Figure 17. Velocity contours (m/s) at y=1.45 m Figure 18. Temperature contours ( C) at y=1.45 m Figure 19. CO 2 Concentration contours (ppm) -246-

Table 5. Effective Draft Temperature at differentp oints in case 4. Table 6. Effective Draft Temperature at different points in case 5. In displacement ventilation (case 4) and mixing ventilation (case 5), the temperature and CO 2 concentration in the breathing zone are higher compared to the stratum ventilation (case 1). In addition, the air velocities around the occupant, ventilation effectiveness, and ADPI are less than that in the stratum ventilation (case 1). Therefore, the stratum ventilation (case 1) has the best conditions in terms of thermal comfort and indoor air quality. The main difference between stratum, displacement, and mixing ventilation systems is that in stratum ventilation the air flows directly to the breathing zone in front of and around the occupant unlike displacement ventilation and mixing ventilation, so the breathing zone temperature is the lowest in stratum ventilation also the air velocities in front of and around the occupant are the higher as noticed in the research. The stratum ventilation (case 1), displacement ventilation (case 4), and mixing ventilation (case 5) have the same airflow rate and supply air temperature (t in ) so the value of t bz for stratum ventilation would be the lowest because the air directly flows into the breathing zone at the head level. Therefore, the ventilation effectiveness of stratum ventilation system is the higher as shown in Fig. 20. As shown in Fig. 20 and Fig. 21, case 1 have the best ADPI and good ventilation effectiveness so it is preferred. Case 3, case 4 and case 5 have the lowest ADPI < 80% and the lowest ventilation effectiveness so the air distribution is bad and thermal comfort conditions does not achieved. Figure 20. Ventilation effectiveness in all cases. Figure 21. Air diffusion performance index (ADPI) in all cases. -247-

5. CONCLUSIONS CFD techniques allow visualization of airflow, velocity, temperature and CO 2 concentration distributions by computer and saving time. It allows improvements in ventilation systems and innovative solutions to be investigated inexpensively without the need to build and test prototypes. From investigating the effect of changing the air change per hour in the stratum ventilation, we found that the 5 ACH provides the better conditions in terms of thermal comfort and indoor air quality. The air supply location recommended being at a height above the occupant height to ensure that the air reaches the breathing zone as well to achieve thermal comfort and indoor air quality. In the displacement ventilation and mixing ventilation, the air temperature and CO 2 concentration in the breathing zone are higher compared to the stratum ventilation (case 1). In addition, the air velocities around the occupant, ventilation effectiveness and ADPI are less than that in stratum ventilation. In the stratum ventilation system the air flows directly to the breathing zone in front of and around the occupant so it needs low ACH for achieving thermal comfort and IAQ compared with the other ventilation systems. In terms of thermal comfort and indoor air quality, the stratum ventilation system provides the best conditions as the air flows directly to the breathing zone at the head level in front of the occupant which improves the inhaled air quality. A computational fluid dynamic (CFD) is a good for calculating the effective draft temperature and air diffusion performance index (ADPI) for checking the thermal comfort. 6. REFERENCES [1] Lin Z., Tian L., Yao T., Wang Q., and Chow T.T., 2011, "Experimental and numerical study of room airflow under stratum ventilation, Building Energy & Environmental Technology Research Unit, School of Energy and Environment, City University of Hong Kong, Hong Kong SAR, China, Lab of Multiphase Flow in Power Engineering, Xi an Jiao tong University, Xi an 710049, China. [2] Guyton, A.C., 1986, "Textbook of Medical Physiology", Seventh edition, Saunders. [3] Schottelius B.A., 1978, "Textbook of Physiology", Eighteenth Edition. [4] Halawa T., 2007, "CFD investigation of HVAC system design for office spaces", M.Sc. Thesis, Faculty of Engineering, Cairo University, Giza, Egypt. [5] ANSI/ASHRAE Standard 55-2010: thermal environmental conditions for human occupancy, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, USA, 2010. -248-