Investigation to Improve Efficiency of Transcritical R744 Two-Stage Vapor Compression Systems

Similar documents
Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

Modeling and Testing of an Automobile AC Scroll Compressor, Part II: Model Validation

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

PERFORMANCE AND CHARACTERISTICS OF COMPRESSOR/EXPANDER COMBINATION FOR CO 2 CYCLE ABSTRACT

CFD Analysis and Experiment Study of the Rotary Two-Stage Inverter Compressor with Vapor Injection

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

Operation of Compressors Through Use of Load Stands

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors

Characterization and Performance Testing of Two- Stage Reciprocating Compressors using a Hot-Gas Load Stand with Carbon Dioxide

Numerical Simulation for the Internal Flow Analysis of the Linear Compressor with Improved Muffler

EXAM # 2. First Name Last Name CIRCLE YOUR LECTURE BELOW: INSTRUCTIONS

Scroll Compressor Operating Envelope Considerations

A Numerical Study of the Performance of a Heat Exchanger for a Miniature Joule-Thomson Refrigerator

Evaluation of a Prototype Rotating Spool Compressor in Liquid Flooded Operation

A virtual EXV mass flow sensor for applications with two-phase flow inlet conditions

Research of Variable Volume and Gas Injection DC Inverter Air Conditioning Compressor

Application of Computational Fluid Dynamics to Compressor Efficiency Improvement

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Scroll Compressor Performance With Oil Injection/Separation

TESTING AND ANALYZING ON P-V DIAGRAM OF CO 2 ROLLING PISTON EXPANDER

Investigation of Suction Process of Scroll Compressors

Development of Large Capacity CO2 Scroll Compressor

A Twin Screw Combined Compressor And Expander For CO2 Refrigeration Systems

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

University of Cincinnati

Impact Fatigue on Suction Valve Reed: New Experimental Approach

Analytic and Experimental Techniques for Evaluating Compressor Performance Losses

Test on a Twin-Screw Compressor

CO 2 radial piston compressor (transcritical)

Linear Compressor Discharge Manifold Design For High Thermal Efficiency

Linear Compressor Suction Valve Optimization

University of Cincinnati

Effect of Coiled Capillary Tube Pitch on Vapour Compression Refrigeration System Performance

Improvement of the Volumetric and Isentropic Efficiency Due to Modifications of the Suction Chamber

AIR EJECTOR WITH A DIFFUSER THAT INCLUDES BOUNDARY LAYER SUCTION

Vibration-Free Joule-Thomson Cryocoolers for Distributed Microcooling

Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

Small Variable Speed Hermetic Reciprocating Compressors for Domestic Refrigerators

Capacity Modulation of Linear Compressor for Household Refrigerator

Comparative Analysis of Two Types of Positive Displacement Compressors for Air Conditioning Applications

Performance and Operating Characteristics of a Novel Rotating Spool Compressor

ENGINEERING FLUID MECHANICS

Efficiency Improvement of Rotary Compressor by Improving the Discharge path through Simulation

Hermetic Compressor With Improved Motor Cooling

Using PV Diagram Synchronized With the Valve Functioning to Increase the Efficiency on the Reciprocating Hermetic Compressors

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory

Predicting the Suction Gas Superheating in Reciprocating Compressors

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

Heat Transfer Research on a Special Cryogenic Heat Exchanger-a Neutron Moderator Cell (NMC)

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

ASSIGNMENT 2 CHE 3473

Chapter 2: Pure Substances a) Phase Change, Property Tables and Diagrams

An Investigation of Liquid Injection in Refrigeration Screw Compressors

ASSIGNMENT 2 CHE 3473

Tip Seal Behavior in Scroll Compressors

Axial and Radial Force Control for CO2 Scroll Expander

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI

Yujiro Kitaide 1, Naoki Maruyama 1, Masafumi Hirota 1, Yusuke Onishi 2, Toshiaki Tsuchiya 2

Schedule of Requirements THERMODYNAMICS LABORATORY- CHEMICAL ENGINEERING DEPARTMENT

CFD Simulation of the Flow Through Reciprocating Compressor Self-Acting Valves

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Development and Experiences with a Hermetic CO2 Compressor

Development of a New Mechanism Compressor Named "Helical

Pressure Indication of Twin Screw Compressor

Experimental Investigation on the Operating Characteristics of a Semi-hermetic Twin Screw Refrigeration Compressor by means of p-v Diagram

Performance Analysis of Centrifugal Compressor under Multiple Working Conditions Based on Time-weighted Average

CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube

GLOSSARY OF TERMS. Adiabatic Compression Compression process when all heat of compression is retained in the gas being compressed.

Development of Scroll Compressors for R410A

Correlation Between the Fluid Structure Interaction Method and Experimental Analysis of Bending Stress of a Variable Capacity Compressor Suction Valve

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

Hermetic Compressor Manifold Analysis With the Use of the Finite Element Method

S-CO 2 Brayton Recompression Loop Design and Control

Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler

Valve Losses in Reciprocating Compressors

Chapter 4, Problem 30.

Single- or Two-Stage Compression

Design Optimization for the Discharge System of the Rotary Compressor Using Alternative Refrigerant R410a

ENGG. THERMODYNAMICS

Removing nitrogen. Nitrogen rejection applications can be divided into two categories

Ball Beating Lubrication in Refrigetation Compressors

Centrifugal Compressor Performance Deviations with Various Refrigerants, Impeller Sizes and Shaft Speeds

Near-Critical CO 2 Flow for Carbon Capture and Storage

Real Gas Performance Analysis of a Scroll or Rotary Compressor Using Exergy Techniques

Cooling Characteristics of GM-type Pulse Tube Refrigerator with Neon as Working Gas

Mass Split of Two-Phase-Flow

How to Select High Pressure and Gas Bypass

COMMERCIAL REFRIGERATION SYSTEMS WITH CO 2 AS REFRIGERANT

Domain Decomposition Method for 3-Dimensional Simulation of the Piston Cylinder Section of a Hermetic Reciprocating Compressor

ALICE SPD cooling system

Supercritical CO 2 Power Cycles: Design Considerations for Concentrating Solar Power

Characterization and Performance Testing of Natural Gas Compressors for Residential and Commercial Applications

CORESTA RECOMMENDED METHOD N 6

Lab 1c Isentropic Blow-down Process and Discharge Coefficient

Vibration Related Testing for Hermetic Compressor Development

Comparison of single and parallel ejector operation in transcritical R744 cycle.

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Process Nature of Process

Simulator For Performance Prediction Of Reciprocating Compressor Considering Various Losses

Transcription:

Purdue University Purdue e-pubs International efrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Investigation to Improve Efficiency of Transcritical 744 Two-Stage Vapor Compression Systems Jeniffer Mott Peuker University of Illinois at Urbana-Champaign Predrag S. Hrnjak University of Illinois at Urbana-Champaign Follow this and additional works at: http://docs.lib.purdue.edu/iracc Peuker, Jeniffer Mott and Hrnjak, Predrag S., "Investigation to Improve Efficiency of Transcritical 744 Two-Stage Vapor Compression Systems" (2008). International efrigeration and Air Conditioning Conference. Paper 900. http://docs.lib.purdue.edu/iracc/900 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-OM directly from the ay W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

Investigation to Improve Efficiency of Transcritical 744 Two-Stage Vapor Compression Systems Jennifer Mott PEUKE, Predrag HNJAK* Department of Mechanical Science and Engineering University of Illinois at Urbana-Champaign Urbana, IL 61801 *(Phone: +1-217-244 6377, Fax: +1-217-333 1942, Email: pega@uiuc.edu) 2171, Page 1 ABSTACT The objective of this paper is to discuss an experimental investigation of a two-stage compression and expansion system with the intent of showing system performance improvement over a two-stage compression and single expansion system for an air-conditioning application. For the mechanical subcooling system, the low, moderate, and high air-temperature conditions showed a 6 to 8% increase in COP over the baseline system. Additionally, the optimization of the high-side pressure is more critical because variations from the optimum pressure have a larger effect on the COP than adjusting the bypass mass flow rate. Further analysis into the bypass valve operation for the mechanical subcooling system was done using a correlation for a short tube with a constant area. 1. INTODUCTION The interest in 744 as a refrigerant has increased as there has been a push toward environmentally friendly refrigerants. Since 744 has an ozone depleting potential of zero and its global warming potential is negligible if it is recovered from industrial processes, it is seen as one possible replacement for traditional refrigerants such as 134a.(Baek et al., 2005; Cecchinota, et al., 2005) Because of its critical pressure, 7.38MPa, and relatively low critical temperature, 31.06 C, the cycle operation is different from traditional vapor compression cycles, which can cause the refrigerant at the high-side pressure to be supercritical.(cecchinota, et al., 2005) For supercritical operating conditions, the heat transfer in the gas cooler does not involve a phase change but only gas cooling, thus the condenser is replaced by a gas cooler. (Cecchinota, et al., 2005) Additionally, because of the supercritical nature of the cycle, the throttling process behaves differently and the effect of the throttling process is stronger because of increased loss of exergy when the temperature of the gas cooler is above the critical temperature. (Cavallini et al., 2005; Cecchinota, et al., 2005) This leads to a relatively high gas cooler refrigerant exit temperature and thus high vapor quality at the evaporator entrance, (Cavallini et al., 2005) especially in a system without a suction line heat exchanger. One method to improve 744 system performance is to use two-stage compression, and two-stage expansion. The object of this investigation and paper is to experimentally show performance improvement of double expansion over single expansion in a two-stage compression system for an air-conditioning application. In addition, the feasibility of using a fixed orifice for the bypass valve was studied and the results are presented. 2. SYSTEM DESCIPTIONS 2.1 Baseline System The transcritical vapor compression 744 systems presented in this paper are denoted as the baseline system and the mechanical subcooling system. The baseline system consists of the following components: a two-stage hermetic compressor with microchannel intercooler, a microchannel gas cooler, a tube-in-fin evaporator, slab suction line heat exchanger (SLHX) and an electronic expansion valve. The ideal cycle is shown in the p-h diagram in Figure 1. The numbers correspond to the following ideal processes.

2171, Page 2 The refrigerant undergoes an isentropic compression (1-2) to an intermediate pressure, isobaric heat extraction in the intercooler (2-3), isentropic compression to the high-side pressure (3-4), isobaric heat extraction in the gas cooler (4-5), and isobaric heat exchange with the low pressure refrigerant in the SLHX (5-6). The refrigerant then is subject to an isenthalpic expansion in the expansion valve (6-7) and isobaric heat addition in the evaporator (7-8). After the evaporator, the refrigerant is superheated isobarically in the low-side of the SLHX before returning to the compressor (8-1). 2.2 Mechanical Subcooling System The mechanical subcooling system includes the components of the baseline system with the addition of a slab internal heat exchanger (IHX) and an additional electronic expansion valve. The ideal mechanical subcooling cycle is shown in the p-h diagram in Figure 1b with the numbers corresponding to the following ideal processes. Similar to the baseline ideal cycle, the refrigerant undergoes an isentropic compression (1-2) to an intermediate pressure, isobaric heat extraction in the intercooler (2-3), isentropic compression to the high-side pressure (3-4), and isobaric heat extraction in the gas cooler (4-5). After the gas cooler, part of the refrigerant flow is separated from the total flow, and expanded isenthalpically to the intermediate pressure (5-10). The total flow rate and the separated flow rate are denoted as m r, and m b, respectively in Figure 1b. The separated refrigerant is used to isobarically extract heat (10-3) from the remaining refrigerant exiting the gas cooler (5-6) in the IHX. This flow is recombined with the main flow at the inlet to second stage of the compressor, where it is ideally mixed with the refrigerant exiting the intercooler (point 3). After the isobaric heat exchange at the high-side IHX, the main refrigerant flow isobarically exchanges heat in the SLHX (6-7) with the low pressure side of the SLHX. It is then isenthalpically expanded in the main expansion valve (7-8) and undergoes isobaric heat addition in the evaporator (8-9). After the evaporator, the refrigerant is superheated isobarically in the low-side of the SLHX before returning to the compressor (9-1). 6 5 4 7 6 5 m r 4 P 3 2 P m r - m b 10 m b 3 2 8 9 1 7 8 1 h (a) Figure 1 Baseline (a) and mechanical subcooling (b) ideal cycle p-h diagrams h (b) 3. EXPEIMENTAL FACILITY The experimental facility used for all experiments consists of two environmental chambers.. The outdoor chamber contained the gas cooler, intercooler, and compressor, while the evaporator was mounted in the indoor chamber. There are several welded Type-T thermocouples attached to each chamber surface. The heat transmission losses through the chamber surfaces during an experiment were determined from temperature differences between the interior and the exterior of the chambers in combination with the UA values determined from chamber calibration experiments. During a test, the ambient conditions inside the chambers were maintained at specified values. The power consumption of all electrical devices operated in the chambers was measured with Watt transducers. By combining the reading of the Watt transducer, the heat loss through the walls, ceiling, floors and the latent portion of the evaporator capacity, it was possible to determine the capacity on the evaporator. The capacity on the evaporator

2171, Page 3 determined by this method is called the chamber energy balance. The chamber energy balance on the gas cooler/intercooler could not be determined because the amount of heat added to the chamber from the compressor was not known. All refrigerant air heat exchangers were installed in open-loop wind tunnels housed inside the chambers. Before and after each heat exchanger, four by four thermocouple grids consisting of welded Type-T thermocouples were used to determine the dry-bulb air temperatures. Downstream of the air outlet temperature grids, flow nozzles were installed to determine the airflow rates in both ducts by measuring the pressure drops with differential pressure transducers. For the air side energy balance, the latent load was calculated from two chilled mirror dew point sensors. adial blowers were connected at the outlet of each duct in order to force air through the wind tunnels. The airflow rates through the ducts were controlled with variable frequency drives. The indoor and outdoor blowers exhausted the air directly into the chambers. An external 404A chiller system with evaporators mounted on the ceiling inside the outdoor chamber compensated for the heat rejected by the gas coolers intercooler and compressor. PID-controlled electric heaters were installed in both chambers to reheat the room to the specified test conditions. In order to maintain the moisture content in the indoor room at a specified condition, steam injection was used to create the latent load at the evaporator. The refrigerant-side energy balance was accomplished from temperature and pressure measurements in combination with two coriolis-type mass flow meters in series. Absolute pressures were measured at the outlet of every component. In addition, differential pressure measurements were taken across the heat exchangers to determine the absolute pressures at the heat exchanger inlets. All refrigerant-side temperatures were measured with ungrounded Type-T immersion thermocouple probes. Shake down tests were performed before running baseline tests. It was found that the refrigerant, chamber and air capacity measurements matched within 10%, most within 5%. This investigation focused on three conditions based on the air temperatures at the gas cooler and evaporator entrances: 27.8 C gas cooler, 26.5 C evaporator, denoted as the low condition; 35 C gas cooler, 27 C evaporator, denoted as the moderate condition and 42 C gas cooler, 32 C evaporator, denoted as the high condition. All three conditions did not have dehumidification. 4. COP IMPOVEMENT The experimental results from the mechanical subcooling system are shown in the following contour plots. All results are compared at the cooling capacity and the maximum COP of the baseline system. For each condition, it can be seen that the COP depends on both the high-side pressure and the bypass mass flow rate. The contours show how the COP varies from the maximum COP for each operation condition. Each contour plot is based on a minimum of twenty data points. At the maximum COP for the low condition the mechanical subcooling system had an 8% increase over the baseline system COP and a bypass mass flow rate of 1%. This 1% bypass mass flow rate contributes to a refrigerant temperature difference in the high-side of the IHX and point (7) in Figure 1b moves to the left, which then translates into higher COP by looking at the entire system. The darkest area in Figure 2, where the maximum COP occurs, shows that the optimum bypass flow rate is between 0% and 15% of the total mass flow rate.

2171, Page 4 Figure 2 COP contours for the low condition For the moderate condition, at the maximum COP, there is a 6% increase in COP over the baseline system and has a bypass mass flow rate of 21% of the total mass flow rate. In Figure 3, the second highest contour is at 98% of the maximum and has a bypass mass flow rate of 15% to 30%. Figure 3 COP contours for the moderate condition For the high condition the maximum COP was 8% higher than the baseline system and had a bypass mass flow rate of 22%. The highest contour at approximately the maximum COP has a bypass mass flow rate of 15% to 24% and is shown in Figure 4.

2171, Page 5 Figure 4 COP contours for the high condition The contour plots show that the system is more sensitive to optimizing the high-side pressure than the bypass mass flow rate to achieve optimum COP. This is seen by the narrow width along the pressure axis and wider along the bypass mass flow rate axis of the maximum COP section in the plots. The low condition has the steepest decent from the maximum COP dropping at 5% per contour. The moderate condition is less steep dropping approximately 2% per contour and the high-condition has the shallowest decent, only dropping 1% per contour from the maximum. This shows that as the ambient air temperatures increases, the sensitivity of the optimum high-side pressure and bypass mass flow rate to find the maximum COP decreases. From these plots, it can also be seen that the optimization of the high-side pressure is more critical because variations from the optimum pressure have a larger effect on the COP than adjusting the bypass mass flow rate. 5. BYPASS VALVE OPEATION This section exams more closely the operation of the bypass valve in the mechanical subcooling system with SLHX. The manufacturer s manual for the stepper motor electric expansion valve that was used as the bypass valve in the experiments gave an equation relating the voltage fed to the expansion valve and the percent opening of the expansion valve. This equation was used to determine the valve opening for representative bypass mass flow rate data for each condition. The results were plotted and shown in Figure 5. The plot shows that each condition follows a different linear trend for the bypass mass flow rate percent. The points of maximum COP for each condition are also marked on the figure and do not correspond to the same point for all the conditions. The low condition is significantly different since the maximum is at 1% bypass. As seen by the contour curves in Figure 2 the bypass can vary from 0% to 16% at the optimum high-side pressure. At the high end of this range, at 15%, the opening of the bypass valve is the not at the maximum COP point for the moderate condition, though appears to have the same opening as the high conditions. The high and moderate conditions have about the same optimum bypass mass flow rate percent; however the valve opening is different and the nominal mass flow rate is different.

2171, Page 6 Calculated Bypas Valve Opening [%] 10 9 8 7 6 5 4 3 2 1 0 Low Condition Moderate Condition High Condition Point of Maximum COP for each condition 0 5 10 15 20 25 30 Bypass Mass Flow ate Percent Figure 5 Bypass valve opening for bypass mass flow rate measured One option for the bypass valve is to use a fixed orifice instead of an electronic expansion device. This would decrease the amount of controls and extra power needed to operate the system, and also decrease the cost of the system components. The issue with an fixed orifice is that it is a fixed diameter and will not be able to be optimized for all conditions. The deviations from the optimum and maximum COP were investigated using a correlation for a short tube orifice and the results are presented below. The single-phase orifice equation to predict the mass flow rate through a short tube was corrected for two-phase flow and 744 to be (Liu et al., 2004): m A s 2 high f ( P P ) (1) where A s is the cross sectional area in m 2, is the density of the fluid entering the orifice in kg/m 3, and P f is the adjusted downstream pressure in MPa. In this case, P high is the pressure at the exit of the gas cooler, Pcro and P f is given by the correlation (Liu, et al, 2004): L 1. 6326 0.42405 P P 0.77213 086505 D 0.40453 P 4.7025 T 0.12293 0.00006 / f c D (2) where D D / 7. 03mm, P Phigh / P, and c T ( Thigh Tc ) / T. P c c and T c are the critical pressure and temperature of 744, 7.38MPa and 31.03 C respectively. D and L are the dimensions of the short tube used to develop the correlation. In this case, T high is the refrigerant temperature at the exit of the gas cooler, Tcro. Equations (1) and (2) were developed to predict the flow of 744 through a short tube with the following constraints. The high-side pressure ranged between 7.55 to 10.24 MPa, the low-side pressure ranged between 3.03 to 5.02 MPa and the high-side temperature ranging between 35.3 and 45.5 C. While the low-side pressure in the bypass valve in this investigation is outside this range, between 5.4 and 8.4 MPa, using this correlation can give an idea as to whether a fixed orifice will work for the bypass valve. The mass flow rates in the study were also significantly higher. The study experimented with many different lengths and diameters of the short tubes and it was shown that the effect of the length was minimal while the effect of the diameter strongly influences the mass flow rate(liu et al., 2004). Therefore, in the following illustration the length was set as one of the lengths used in the study leaving only the diameter as an unknown.

2171, Page 7 Using the Tcro and Pcro from the maximum COP point for the moderate condition and the corresponding mass flow rate, the diameter needed was calculated to be 0.3664 mm. Using the Tcro and Pcro from the maximum COP point for the high condition and the corresponding mass flow rate, the diameter needed was calculated to be 0.3352 mm. The Tcro for the low condition at maximum COP was below the critical temperature at 30 C ambient temperature; therefore it cannot be used in equation (2). For illustration purposes, the temperature was raised by 2 degrees to 32 C. Using the Pcro and adjusted Tcro from the maximum COP point for the low condition and the corresponding mass flow rate, the diameter needed was calculated to be 0.2389 mm. In Table 1, the results for each of the found optimized diameters is summarized. The table shows a comparison of the predicted bypass mass flow rate which was calculated from the equation (1). The actual mass flow rate value was the measured flow rate and is necessary to satisfy the balance between the flow rates (total and bypass) for maximum COP. For each condition, an optimal diameter was found using the actual bypass mass flow rate. Using this diameter, a mass flow rate was found for the other two conditions, denoted as predicted mass flow rate in the table, and compared to the actual bypass mass flow rate. The actual and the predicted mass flow rates differ whenever the diameter used in the calculations is not the optimized diameter for that condition. Condition diameter is optimized for Low Moderate High Table 1 Summary of results from predicted fixed orifice diameter Condition Diameter [mm] Predicted mass flow rate [g/s] Actual mass flow rate [g/s] Predicted bypass mass flow rate percent Actual bypass mass flow rate percent COP difference from maximum based on change in percent of bypass mass flow rate Low 0.2389 2.0 2.0 9% 9% - Moderate 0.2389 2.3 5.3 9% 21% -5% High 0.2389 2.9 5.8 11% 22% -2% Low 0.3664 4.6 2.0 20% 9% -5% Moderate 0.3664 5.3 5.3 21% 21% - High 0.3664 6.8 5.8 25% 22% -1% Low 0.3352 3.9 2.0 10% 9% - Moderate 0.3352 4.5 5.3 17% 21% -2% High 0.3352 5.8 5.8 22% 22% - The low condition diameter predicts a mass flow rate of 2.9 g/s for the high condition with Tcro and Pcro from the maximum COP point for the high condition. This corresponds to 11% bypass mass flow rate and would drop the COP by 2% for the same high-side pressure. The moderate condition diameter predicts a mass flow rate of 6.8 g/s for the high condition. This corresponds to about 25 % bypass mass flow rate percent and would drop the COP by 1% for the same high-side pressure. The diameter from the low condition predicts a mass flow rate of 2.3 g/s for the moderate condition with Tcro and Pcro from maximum COP point for the moderate condition. This corresponds to about 9% bypass mass flow rate and drops the COP by 5% for the same high-side pressure. The diameter from the high condition predicts a mass flow rate of 4.5 g/s. This corresponds to about 17% bypass mass flow rate and would drop the COP by 2% for the same high-side pressure. Using the optimum diameter found for the moderate condition, and the Pcro and modified Tcro from the low condition, the predicted mass flow rate is 4.6 g/s. This corresponds to about 20% bypass mass flow rate and would drop the COP by 5% for the same high-side pressure. Using the optimum diameter found for the high condition the predicted mass flow rate is 3.9 g/s. This corresponds to about 10% bypass mass flow rate and is within the maximum COP area in Figure 2 for the same high-side pressure. The results show that the optimized diameter for maximum COP for one condition cannot predict the mass flow rate for maximum COP for the other conditions. This begs the question: for which condition should the system be optimized? One option is to optimize for the high condition because it has the smallest variations of the investigated operation conditions. This is based purely on a numbers standpoint. From an engineering standpoint, the actual usage of a system must be taken into account. Therefore, the system should be optimized for the most common condition to occur. Additionally, variations from the optimum may be acceptable in the final design and must also be considered.

2171, Page 8 6. CONCLUSIONS The following conclusions are made based on the above analysis. The experiments showed 6%-8% increase in COP. For the mechanical subcooling system, the COP depends on high-side pressure and bypass mass flow rate. Also, as the ambient air temperatures increases, the sensitivity of the optimum high-side pressure and bypass mass flow rate to find the maximum COP decreases. The high-side pressure is more sensitive and can be optimized using a COP maximizing equation based on the gas cooler air exit temperature. The bypass electronic expansion valve may be replaced by a fixed orifice but can only be optimized for one condition. For the conditions and data presented, the maximum loss in COP is 5%. NOMENCLATUE AF Air Flow ate (m 3 /hr) Subscripts As Cross sectional Area (m 2 ) high high-side COP Coefficient of Performance (-) reduced D Diameter (mm) r total h Enthalpy (kj/kg) b separated IHX Internal Heat Exchanger (-) L Length (mm) m, m mass flow rate (g/s) p Pressure (MPa) Pcro Gas Cooler efrigerant Exit Pressure (MPa) Density (kg/m 3 ) SLHX Suction Line Heat Exchanger (-) Tcro Gas Cooler efrigerant Exit Temperature ( C) EFEENCES Baek J S, Groll E A, Lawless P B., 2005, Theoretical performance of transcritical carbon dioxide cycle with twostage compression and intercooling, Proc. IMechE, Vol 219 Part E: p. 187 195. Cavallini A, Cecchinato L, Corradi M, Fornasieri E, Zilio C., 2005, Two-stage carbon dioxide cycle optimization: a theoretical and experimental analysis, Int J efri,. 28: p. 1274 1283 Cecchinota L, Corradi M, Fornasieri E, Zilio C., 2005, Theromodynamic analysis of different two-stage transcritical carbon dioxide cycles. Preprints of Thermophysical Properties and Transfer Processes of efrigerants II Vicenza Conference, 301 308 Liu J P, Niu Y M, Chen Z J, Chen X F., 2004, Experimentation and correlation of 744 two-phase flow through short tubes. Exp. Thermal and Fluid Sci., 28: p. 565 573 ACKNOWLEDGEMENT The authors would like to thank Sanyo Electric Co., Ltd. and the Air Conditioning and efrigeration Center (ACC) at the University of Illinois at Urbana-Champaign for supporting this project.