ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

Similar documents
Accumulation of Hydrogen Released into an Enclosure Fitted With Passive Vents Experimental Results and Simple Models

Novel Approaches to Venting

HYDROGEN JET FIRES IN A PASSIVELY VENTILATED ENCLOSURE

Hydrogen and fuel cell stationary applications: key findings of modelling and experimental work in the HYPER project

Deborah Houssin-Agbomson, Jean-Yves Letellier, Philippe Renault, Simon Jallais

EXPERIMENTAL STUDY ON HYDROGEN EXPLOSIONS IN A FULL-SCALE HYDROGEN FILLING STATION MODEL

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

HYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES

Experimental Study of Hydrogen Release Accidents in a Vehicle Garage

Guidance on room integrity testing and its interpretation

Passive ventilation of enclosures with one vent, the uniformity criterion, and validation of pressure peaking phenomenon (unignited releases)

ACCIDENTAL HYDROGEN RELEASE IN GC-LABORATORY; A CASE STUDY

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures

A COMPARISON STUDY INTO LOW LEAK RATE BUOYANT GAS DISPERSION IN A SMALL FUEL CELL ENCLOSURE USING PLAIN AND LOUVRE VENT PASSIVE VENTILATION SCHEMES

SUMMARY OF THE EXPERIMENTAL STUDIES OF COLD HELIUM PROPAGATION ALONG A SCALE MODEL OF THE LHC TUNNEL

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

Investigation of Cargo Tank Vent Fires on the GP3 FPSO, Part 2: Analysis of Vapour Dispersion

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

A METHOD FOR ASSESSING THE CONSEQUENCES OF SMALL LEAKS IN ENCLOSURES

Drum / cylinder handling

Influence of rounding corners on unsteady flow and heat transfer around a square cylinder

Engineering Models for Vented Lean Hydrogen Deflagrations

THE EXTERNAL EXPLOSION CHARACTERISTICS OF VENTED DUST EXPLOSIONS.

Flow in a shock tube

Sprinkler Protection for Cloud Ceilings. SUPDET 2013 Jason Floyd, Ph.D. 28 February 2013

Injector Dynamics Assumptions and their Impact on Predicting Cavitation and Performance

EXPERIMENTAL STUDIES OF THE BEHAVIOUR OF PRESSURISED RELEASES OF CARBON DIOXIDE

INOGATE Technical Secretariat UK Experience European Standards Implementation Key Expert Phil Winnard Session 2 Georgia, October 2015

Gas Accumulation Potential & Leak Detection when Converting to Gas

Fires and Explosions: What You Need to Know to Prevent Them

SIMULATIONS OF HYDROGEN RELEASES FROM A STORAGE TANKS: DISPERSION AND CONSEQUENCES OF IGNITION

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Wind Flow Validation Summary

Interacting Turbulent Plumes in a Naturally Ventilated Enclosure

REQUIREMENTS FOR VALIDATION OF MATHEMATICAL MODELS IN SAFETY CASES

Measurement of Representative Landfill Gas Migration Samples at Landfill Perimeters: A Case Study

Effect of airflow direction on human perception of draught

ERCBH2S Frequently Asked Questions.

Investigation of the Early Inflation Characteristics of a Complex Folded Knee Airbag with the New Corpuscular Method in LS-DYNA

SAFETY OF LABORATORIES FOR NEW HYDROGEN TECHNIQUES

Sea and Land Breezes METR 4433, Mesoscale Meteorology Spring 2006 (some of the material in this section came from ZMAG)

Flammability of Hydrocarbon/CO 2 Mixtures: Part 1. Ignition and Explosion Characteristics. Abstract. 1. Introduction

Multiple sources of buoyancy in a naturally ventilated enclosure

Journal of Applied Fluid Transients, Vol 1-1, April 2014 (3-1)

REPORT INVESTIGATION OF 3M CLEAN AND STRIP DISKS IN EXPLOSIVE ATMOSPHERES. Client: 3M Norge A/S. Authors: Bjørnar A. Johnsen Geir H.

Internal Explosion Methodologies

- Comparison of Long and Wide Enclosures

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW

HYDROGEN RELEASES IGNITED IN A SIMULATED VEHICLE REFUELLING ENVIRONMENT

CARRIAGE OF DIRECT REDUCED IRON (DRI) BY SEA CHANGES TO THE IMO CODE OF SAFE PRACTICE FOR SOLID BULK CARGO

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

Learn more at

AF100. Subsonic Wind Tunnel AERODYNAMICS. Open-circuit subsonic wind tunnel for a wide range of investigations into aerodynamics

Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

Effect of 180 bends on gas/liquid flows in vertical upward and downward pipes

Currents measurements in the coast of Montevideo, Uruguay

Determination of the Design Load for Structural Safety Assessment against Gas Explosion in Offshore Topside

Aalborg Universitet. Published in: Proceedings of Offshore Wind 2007 Conference & Exhibition. Publication date: 2007

The Influence Of Vessel Volume And Equivalence Ratio In Vented Gas Explosions

Natural ventilation of an enclosure containing two buoyancy sources

Fire test of ventilated and unventilated wooden façades

SIO 210 MIDTERM, 26 October 2009.

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012

Flammability Chart. Gas Formula Ignition

Experimental determination of deflagration explosion characteristics of methane air mixture and their verification by advanced numerical simulation

Atmospheric Rossby Waves in Fall 2011: Analysis of Zonal Wind Speed and 500hPa Heights in the Northern and Southern Hemispheres

Level MEASUREMENT 1/2016

Hydrogen Bubble Dispersion and Surface Bursting Behaviour

Circular No. 3/ March To the members. Dear Sirs,

STANDARD PROCEDURE OF A TIGHTNESS TEST OF A SOLAR COLLECTOR BOX. (EUROSUN 2000 SOLAR CONGRESS)

Best Practices for Installation of Gaseous Sample Pumps

Simulations of hydrogen releases from high pressure storage systems

FIRE AND EXPLOSION HAZARDS WITH THERMAL FLUID SYSTEMS

Transient Analyses In Relief Systems

Helium Mass Spectrometric Leak Detection In Large Size Process Plants

DF-310E PROCESS ANALYSERS APPLICATIONS FEATURES

Transferring and Storage

DEFINING HAZARDOUS ZONES ELECTRICAL CLASSIFICATION DISTANCES

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

Flow transients in multiphase pipelines

Ocean Observatories Initiative. Coastal & Global Scale Nodes. Hydrogen Safety. OOI Surface Mooring Hydrogen Safety Review

High Integrity Pressure Protection Systems HIPPS

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code

VENTED CONFINED EXPLOSIONS INVOLVING METHANE/HYDROGEN MIXTURES

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

(a) Calculate the speed of the sphere as it passes through the lowest point of its path.

A Study on the Effects of Wind on the Drift Loss of a Cooling Tower

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration

Health and Safety Executive/Local Authorities Enforcement Liaison Committee (HELA)

Calibration Requirements for Direct Reading Confined Space Gas Detectors

CFD Modelling of LPG dispersion

SPONTANEOUS IGNITION PROCESSES DUE TO HIGH-PRESSURE HYDROGEN RELEASE IN AIR

Improving the Effectiveness of LEV A HSL perspective

Two phase discharge flow prediction in safety valves

Transcription:

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS Hooker, P. 1, Willoughby, D. 2, Hall, J. 3 and Hoyes, J. 4 1 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K, philip.hooker@hsl.gsi.gov.uk 2 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K, deborah.willoughby@hsl.gsi.gov.uk 3 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K, jonathan.hall@hsl.gsi.gov.uk 4 Mathematical Sciences Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K, james.hoyes@ hsl.gsi.gov.uk ABSTRACT This paper reports experimental results from a series of experiments in which gaseous hydrogen was released into a 31 m3 enclosure and the hydrogen concentrations at a number of points within the enclosure were monitored to assess whether hydrogen accumulation occurred and whether a homogeneous or stratified mixture was formed. The enclosure was located in the open air and therefore subject to realistic, and therefore variable, wind conditions. The hydrogen release rate and the passive vent arrangements were varied. The experiments were carried out as part of the EU Hyindoor Project. 1.0 INTRODUCTION Hydrogen energy applications often require that systems be used indoors or in enclosures (e.g. fork lift trucks in a warehouse, fuel cells located in a room, or hydrogen stored and distributed from a gas cabinet). The release of hydrogen in such facilities can potentially lead to its accumulation, the formation of a flammable hydrogen-air mixture and subsequent ignition. Existing knowledge gaps in the behaviour of indoor hydrogen releases are to be addressed as part of the three year HyIndoor project. This paper reports the initial results from an experimental programme to investigate the accumulation and dispersion behaviour of hydrogen released within an enclosure fitted with passive ventilation. The objective of the experiments at HSL is to provide concentration data that can be used by HSL and other Hyindoor partners to test the validity of predictive mathematical models and simple engineering tools. In particular, the experiments are to investigate; the influence of the wind on the dispersion regimes (mixing versus displacement regime), where the wind would have a negative impact and how this could be mitigated, and how the dispersion/accumulation behaviour of choked flow hydrogen releases differs from that arising from sub-sonic releases of equivalent mass flow-rate. 2.0 EXPERIMENTAL ARRANGEMENT 2.1 Enclosure and hydrogen release system The experimental set-up consists of a 31 m 3 enclosure with cross sectional area of 2.5 m by 2.5 m and a length of 5 m. Five similar vents (0,83 m width and 0,27 m height) are located on the sides of the enclosure and a circular vent of same area is located on the roof; these can be closed or opened as required. The enclosure can withstand an internal over-pressure of at least 0.2 bar and is fitted with explosion relief panels in the roof in case of accidental ignition of the hydrogen air mixtures. 1

Figure 1. Sketch of the HSL 31 m 3 test facility Up to the time of writing this paper, the hydrogen releases have been at low pressure via mass flow controllers and a pipe outlet with a 10mm internal diameter. The release pipe is located centrally within the enclosure, directing upwards with the release point 0.5 m above the floor level. The hydrogen releases are operated remotely from a control cabin some distance from the enclosure. A schematic of the release system is shown in Figure 2 and a photograph of the release point is shown in Figure 3. Figure 2. Schematic of the Hydrogen supply system 2

2.2 Instrumentation Figure 3. Photo of the hydrogen release point within the enclosure The enclosure was fitted with the following instrumentation. 27 electrochemical cell oxygen sensors were mounted on suspending wires within the enclosure, in layers at three different heights from the floor (1 m, 1.75 m and 2.25 m), as shown in Figure 4. Additional oxygen sensors were placed within the open vents as required. The hydrogen concentration was then calculated from the oxygen depletion that was detected by each sensor. 14 thermocouples (Type K) were mounted within the enclosure as shown in Figure 5. Thermocouples were also peened into the centre of each of the 6 walls of the enclosure (i.e. the four walls, the ceiling and the floor) and an additional thermocouple was placed within each open vent as required. Pressure transmitters were installed on the hydrogen supply pipeline. Bidirectional probes connected to differential pressure transmitters (+/- 19.6 Pa) were installed for some of the later runs in an attempt to detect flow through the open vents. In addition, the weather conditions close to the enclosure were monitored (i.e. wind speed, wind direction, temperature and humidity). 3

Figure 4. Positions of oxygen detectors within enclosure (for hydrogen concentration measurements) 3 PRELIMINARY RESULTS Figure 5. Positions of thermocouples within enclosure The following is an initial, somewhat qualitative, discussion of the key results observed so far in the HSL experiments for this project. A summary of the preliminary results from key experiments is given in Table 1. The hydrogen release rate is given in Normal litres per minute (Nl/min) which is the flow normalised to 1 atmosphere and 0 C. The average hydrogen concentration values given in the table are the arithmetic means of the values from the sensors functioning at each of the three levels within the enclosure for a period judged to be at steady-state. Note that for some short duration experiments the steady-state was not yet reached, and for some experiments involving two or more open vents the wind effects meant that only a quasi-steady-state was reached. 4

Table 1. Summary of preliminary results of experiments Test Number Vents Open (see Figure 1) Flow Rate (Nl/min) Average H2 @ 1m (%) Average H2 @ 1.75m (%) Average H2 @ 2.25m (%) Average Wind Speed (m/s) Average Wind Direction Release duration (s) 1 V2, V1 150 0.7 0.7 0.6 4.7 20⁰ to vent 734 2 V2, V1 150 1.2 1.3 1.6 3.0 Parallel to vent 478 3 V2, V1 300 1.9 2.1 3.0 3.1 Parallel to vent 409 4 V2, V1 150 0.7 0.7 0.6 2.4 34⁰ to vent 1763 5 V2, V1 300 1.7 1.9 2.4 2.5 34⁰ to vent 1219 6 V2, V1 600 2.4 2.7 3.1 2.5 22⁰ to vent 1181 7 V1 150 1.9 2.2 2.8 2.3 25⁰ to vent 1823 8 V1 150 4.3 4.8 7.1 5.1 Opposite side to vent 1863 9 V1 250 7.3 8.8 11.8 2.8 Opposite side to vent 1776 10 V1, V2, V4 800 2.7 3.1 4.4 2.9 17⁰ to one upper vent, opposite side to lower vent 12 V1, V2, V4 1200 2.7 2.9 3.6 4.1 19⁰ to one upper vent, opposite side to lower vent 560 835 13 V4 & V5 800 2.5 3.5 4.6 3.8 22⁰ to upper vent 1138 14 V4 & V5 1000 2.4 4.6 6.2 3.3 27⁰ to upper vent 951 15 V4 & V5 1200 2.5 5.6 7.6 3.1 19⁰ to upper vent 1020 16 V1 150 6.0 7.0 9.5 3.5 Opposite side to vent 2960 17 V3, V6 (chimney) 800 0.7 9.3 9.5 1.3 Opposite side to bottom vent 18 V4, V6 (chimney) 800 0.6 2.5 5.7 2.3 Almost parallel to bottom vent 19 V6 (chimney) 150 7.5 8.4 9.9 2.7 On to same end as roof vent 20 V6 (chimney) 130 5.6 6.4 8.2 2.0 On opposite side to roof vent 660 600 2350 2656 3.1 Experiments with Single Open Vents In one experiment (Test 16), hydrogen was released at 150 Nl/min for 50 minutes into the enclosure, which had one open vent at high level in one of the side-walls (Vent 1) on the opposite side to that into which the wind was impinging. It appears that a concentration gradient was established within the enclosure down to a level of 1m, the level of the lowest measurement. However, it is also evident that there is a delay until the hydrogen layer descends to the 1 m level compared to the higher levels. The concentration traces that exhibit spiking behaviour are from those sensors closest to the open vent and therefore more susceptible to wind activity. These features are shown in Figure 6. 5

Figure 6. Hydrogen concentrations within the enclosure, 150 Nl/min single upper vent, minimal influence of wind It is worthy of note that the maximum concentration appears to be reaching between 9 and 10% v/v hydrogen. This compares reasonably well with a uniform concentration of about 9% v/v predicted by the Linden model, which accounts for buoyancy-driven flow but neglects the influence of wind [1]. A similar experiment was carried out at the same hydrogen flow rate of 150 Nl/min and the same vent arrangement but on this occasion a variable wind with an average velocity of 2.5 m/s was incident at 25º to the open vent (Test 7). This resulted in a considerably lower hydrogen concentration within the enclosure at the quasi-steady-state which was well-established within the 30 minute duration of the test. This is demonstrated in Figure 7 where the actual volume averaged concentration is about 2 to 3 % v/v. For a release rate of 150 Nl/min a uniform concentration of about 2.5% correlates to a ventilation rate of approximately 10 air changes per hour (ACH) [2]. This compares with the value of 2.8 ACH predicted by the Linden model. 6

Figure 7. Hydrogen concentrations within the enclosure, 150 Nl/min single upper vent, marked influence of wind blowing into open vent In another experiment (Test 19), a flow rate of 150 Nl/min of hydrogen was released into the enclosure, which was ventilated only through a vent in the ceiling. The ceiling vent had the same area as the upper side-wall vent discussed above. Initial indications are that the maximum concentration is similar to, or slightly higher than, that for the side-wall vent without incident wind. 3.2 Experiments with more than one open vent In all experiments where more than one vent is open and both vents are at the upper level, the maximum hydrogen concentration has been lower than that predicted using the Linden model, indicating that wind-driven ventilation dominates. In these cases, predictions from wind-driven ventilation models such as Quadvent [4] appear to be in better agreement with the measurements. However, where there is one lower vent open on one side and an upper vent open on the other side, with the wind incident on the upper vent, the wind appears to be able to overwhelm the effect of buoyancy as considered previously by Linden et al [3]. An experiment (Test 15) was carried out in which hydrogen was released at 1200 Nl/min into the enclosure with one upper open and one lower vent open. The wind was incident on the upper vent although the wind speed was variable. Figures 8, 9 and 10 show a period of the experiment in which the buoyancy is overwhelmed by opposing wind. Figure 8 shows the hydrogen concentration at the 1 m level, Figure 9 shows the hydrogen concentration at the vents (indicating flow into and out of the enclosure) and Figure 10 shows the wind speed for the same period (both the raw data and a 30 point rolling average). It appears that while the wind speed is sufficiently high, the flow is into the enclosure via the upper vent and out of the enclosure via the lower vent. This appears to result in higher concentrations than when buoyancy is allowed to dominate with the maximum wind speed and maximum concentration coinciding at about 550 seconds, after which the concentration decreases once again. 7

Figure 8. Hydrogen concentration within the enclosure at the 1 m level, 1200 Nl/min, one upper vent, one lower vent, wind blowing into the upper vent Figure 9. Hydrogen concentration at the upper and lower vents, 1200 Nl/min, one upper vent, one lower vent, wind blowing into the upper vent 8

Figure 10. Wind speed during the experiment, 1200 Nl/min, one upper vent, one lower vent, wind blowing into the upper vent 4 CONCLUSIONS A number of experiments have been carried out in which hydrogen has been released into an enclosure that can be equipped with a number of open vents. A considerable amount of data has been generated that can be used in the future to further understand the accumulation of hydrogen within an enclosure fitted with passive ventilation. Where there is a single vent and the wind is not incident upon it, the measured maximum hydrogen concentration appears to agree reasonably with that predicted by the buoyancy-based Linden model. Where wind is incident upon an open vent, this appears to result in a lower concentration than that predicted by the Linden model. However, when wind is incident upon an upper vent the wind may overwhelm buoyancy in a negative sense and change the distribution of hydrogen within the enclosure, with the net flow being out of a lower vent. 5 FURTHER WORK Hydrogen releases will be performed in choked flow regime to allow comparison of the dispersion / accumulation behaviour with sub-sonic releases at similar flow rates to some of the sub-sonic releases discussed above. Some hydrogen concentration measurements will be made at heights of less than 1 m above the floor to further assess any layering effects. Further, more rigorous, analysis of test data will be carried out by HSL and other Hyindoor partners. 9

6 ACKNOWLEDGEMENTS The Hyindoor project is funded by the Fuel Cells and Hydrogen Joint Undertaking, a public-private partnership between the European Commission, fuel cell and hydrogen industries represented by the NEW Industry Grouping and the research community represented by the Research Grouping N.ERGHY. 7 REFERENCES 1. Linden, P.F., Lane-Serff, G.F. and Smeed, D.A. (1990). Emptying filling boxes: the fluid mechanics of natural ventilation. J. Fluid Mech., 212, 309-335 2. Personal communication, James Hoyes, 2013 3. Hunt, G.R. and Linden,P.F.. Displacement and mixing ventilation driven by opposing wind and buoyancy. J. Fluid Mech., 527:27 55, 2005. 4. Ivings, M.J., Clarke, S., Gant, S.E., Fletcher, B., Heather, A., Pocock, D.J. (2008). Area classification for secondary releases from low pressure natural gas systems, HSE Research Report RR630. HSE Books, www.hse.gov.uk/research/rrpdf/rr630.pdf 10