Model 130M Pneumatic Controller

Similar documents
RC 195 Receiver-Controller

Powers Controls RC 195 Single Input Receiver-Controller

Powers Controls RC 195 Multiple Input Receiver- Controller

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters

Bubble Tube Installations

256 Pneumatic Pressure Indicator

OPERATING AND MAINTENANCE MANUAL

Model 106 DPI "Micro-switch" Installation and Operating Instructions

C1 Series Pneumatic Controllers and Transmitters

Exercise 2-3. Flow Rate and Velocity EXERCISE OBJECTIVE C C C

Fisher C1 Pneumatic Controllers and Transmitters

DPC-30 DPC-100. Reference Manual

CRYOGENIC TANK SERVICES - CHART RECORDER MANUAL

SSR. Smart Valve Positioner.

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Mounting and Operating Instructions EB 8546 EN. Supply Pressure Regulator Type Fig. 1 Supply pressure regulators

ABB measurement & analytics data sheet. JAA, JAF and JAG Pneumatic indicating controllers

UNITY 2. Uni-DAAMS Manual. Version 1.3 (Changes to Section 1.1) March 2010

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Powers Controls D Day-Night Thermostats

4194 Series Differential Pressure Indicating Controllers

KF Series (Field Mount type) Pressure (Temperature) Indicating Controller. Model: KFP, KFT. User s Manual

Operator: Save these instructions for future use!

! WARNING. Model PFC-1-G (direct acting) PFC-1-GR (reverse acting) Modulating Pneumatic Liquid Level Controls INSTRUCTION MANUAL MM-110B

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Pressure Dump Valve Service Kit for Series 3000 Units

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

632 AccuPro Set-up & Operation

MANUAL BE SERIES Test Benches

DS05C,D,G Dial Set Pressure Regulating Valves

HS653 Negative Pressure Ventilation Controller

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Misaligned Folds Paper Feed Problems Double Feeds Won t Feed FLYER Won t Run iii

CTC 1000 Series One-Pipe, Pneumatic Room Thermostat, Single Temperature

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

WIKA INSTRUMENT CORPORATION

INSTRUCTION MANUAL. January 23, 2003, Revision 0

High Precision Gauge Pressure Indicators

C645A-E Pressure Switches

Electropneumatic Transducer (I/P) Installation, Operation and

SSL. Smart Valve Positioner.

P-5215 Differential Pressure Transmitter

Pressure Dump Valve Service Kit for Series 2300 Units

icreasepro Creaser Operators Manual

Reset Volume Controller 2 Reversing Relay 3 Air Valve Actuator 4 Lower-of-Two-Pressures Relay 4 Diverting Relay 5 Higher-of-Two-Pressures Relay 5

O P E R ATING INSTRUCTIONS FOR MODEL SPR-45 Automatic Screen and Stencil Printer

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

Model 4000 Pressure Controller

accidents which arise due to non-observance of these instructions and the safety information herein.

1500 Follow Spot Yoke

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

Universal Valve Company Inc

Fisher 4194 Differential Pressure Indicating Controllers

with O 2 Controller Instruction Manual

Universal Valve Company Inc

PNEUMATIC PRESSURE CONTROLLERS

VERSA BIKE RACK INSTRUCTIONS

TECHNICAL DATA ZTR Model 312

The Discussion of this exercise covers the following points:

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

36H SERIES Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

ACV-10 Automatic Control Valve

BUBBLER CONTROL SYSTEM

Index Table. Model 794. Installation, Operating and Maintenance Instructions

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

Type 4708 Supply Pressure Regulator

MEGR-1627 Instruction Manual

Float Operated Level Controllers

CentriFlow Meter Integrated Air Entrainment System

Type 4708 Supply Pressure Regulator

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

300 Held Drive Northampton Pa

MyControl Bathing System Signature Series

7130 Lancer Rear Drive Magnetic Commercial Indoor Cycling Bike

Operating Instructions for Cobra and Lynx Duct Leakage Testers

WIND CLIPPER KTS ILLUM SCALE INC DEC CLIPPER WIND SYSTEM

Basic Pneumatics. Module 8: Pressure control valves. Academic Services PREPARED BY. April 2012

S4W PRO ROBOT. User Manual. paddlepalace.com

SERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER

Propane Conversion Kit Instructions

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION MANUAL

User Manual GRI- 1500Li

Budget Range Operators Handbook

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Tire Inflation Cage Kit For servicing only single piece automotive, and most light truck tire/wheel assemblies

A32W PRO ROBOT. User Manual. paddlepalace.com P P

Read Before Operating!

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

Operating Procedures for GripTight 15.5 SDR & IPS Test Plugs

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

Troubleshooting Guide: 640 Pediatric Exam Table with Midmark Scale

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Installation Instructions

Installation Instructions

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Design and Application Details MICRO-RATIO Valves

Transcription:

Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate manual control unit. These components fit in individual adjacent locations in a shelf, and either or both can be removed without interferring with any of the other instruments. If either the controller or its manual unit is removed from the shelf, the process can be controlled by the remaining component. Both have jack-plug pneumatic connections with built-in check valves, so that they can be removed from the shelf without disconnecting any piping. For panel, shelf, and controller installation details, see Instruction MI 017-410 (standard shelf) or MI 017-412 (short shelf). For principle of operation, schematic diagram, and other details, see Technical Information Sheet TI 29-201a. A Siebe Group Company

MI 017-450 May 1978 Installation Standard Specifications Output Signal: 20-100 kpa or 3-15 psi Measurement Signal: 20-100 kpa or 3-15 psi Set-Point Signal: 20-100 kpa or 3-15 psi Air Supply Pressure: 140-150 kpa (20-22 psi) Air Consumption Manual Operation: 1.0 m 3 /h (0.6 ft 3 /min) Automatic Operation: 0.5 m 3 /h (0.3 ft 3 /min) Ambient Temperature Limits: 20 to +65 C (0 to 150 F) Control Modes Model 130M- 2: Proportional Model 130M- 3: Proportional plus Derivative Model 130M- 4: Proportional plus Reset Model 130M- 5: Proportional plus Reset plus Derivative Control Model Limits: Proportional, 5-500% Reset and Derivative actions, 0.01-50 minutes NOTE Ranges are listed in kpa and psi. For alternative ranges in kg/cm 2 or bar, divide applicable kpa values by 100. Installation Piping to Rear of Shelf All connections at shelf are 1/4 NPT. Tie in signal lines to connections at correct location of controller, as identified on rear of shelf. All signals are 20-100 kpa or 3-15 psi. NOTE Illustrated is rear of Model 102 shelf. With Model 101 (short) shelf, connections at rear have same identifications, but locations are different; for locations, see label above connections. 2

Installation MI 017-450 May 1978 Individual Air Shutoff for Each Shelf Position Instrument Identification (as specified in sales order) Rear of Shelf Use 4 x 6 mm or 1/4 inch OD metal tubing External Reset (Optional) Set-Point Readout (Optional) Measurement Air Supply Regulate to a fixed pressure between 140 and 150 kpa (20 and 22 psi) Use 8 x 10 mm or 3/8 inch OD metal tubing Output Optional Connections An optional reset connection (connection A in illustration above) and/or set-point readout connection (connection B ) is provided when specified in sales order. Wiring to Rear of Shelf If controller has optional recorder, alarm lights, or alarm actuator, wiring to rear of shelf is required. See Instruction MI 017-475 for recorder details and MI 017-470 for alarm details. 3

MI 017-450 May 1978 Operation Operation Components on Front of Instruments Instrument Identification Marked as specified in sales order. With optional alarm lights, nameplate is backlighted when alarm goes on. Set-Point Measurement Dial Dial is graduated as specified in sales order. Set-Point Index Measurement Pointer Output Pointer Transfer Switch To switch between automatic and manual control (see details on Page 4). Final Operator Direction Label Arrow indicates direction to turn wheel to close final operator. (Arrow can be positioned to face either direction.) Set-Point Adjustment Knob Knob can be locked in place with optional set screw on side. Memory Pointers Pointers are adjustable so that a desired output or a desired output range is indicated. Manual Output Adjustment Wheel 4

Operation MI 017-450 May 1978 Components at Instrument Control Panel To expose control panel, withdraw controller part way (see page 7). Derivative Adjustment, 0.01-50 minutes Reversing Switch Output increases with either increasing (INC) or decreasing (DEC) input. Proportional Band Adjustment, 5-500% Reset Adjustment, 0.01-50 minutes Latch to raise plastic cover for access to all adjustments shown. Optional Recorder To Effectively Eliminate Reset and/or Derivative Actions Turn reset adjustment to MAX position. Reset time = approx. 200 min. Turn derivative adjustment to 0.01 minutes. Do not use setting in black area. 5

MI 017-450 May 1978 Operation Transfer Switch The transfer switch provides for switching between automatic and manual control without upsetting the process. The switch can be moved freely between AUTO and MAN without special precautions (except controllers without reset circuit; see 3rd paragraph below). Set-Point Index Measurement Pointer Transfer Switch Output Pointer Output Adjustment Wheel Operation with Transfer Switch in MAN In MAN, when output adjustment wheel is rotated, output will change. Direction that wheel is turned will cause output pointer to move in same direction (left to decrease output, etc.). Arrow located above wheel is direction to turn wheel to close control valve, as specified in sales order. When transfer switch is moved to AUTO, measurement will approach the set point at reset rate. (For controllers without reset, align set-point index with measurement pointer before transferring, to prevent process upset.) Operation with Transfer Switch in AUTO In AUTO, process is automatically controlled at reading of set-point index. When transfer switch is moved to MAN, output will remain at last value of output before switching, until output adjustment wheel is rotated. 6

Operation MI 017-450 May 1978 To Remove Controller Withdraw controller approx. 35 cm (14 in) from shelf. While holding down release button on top, slide controller out of shelf. Release Button To Remove Manual Control Unit 1. Remove controller about 20 cm (8 in) from shelf (see illustration above). 2. While pushing in on manual unit (to release catch), lift up, and then slide out unit. Putting Into Operation 1. Check that all instruments in control loop are properly installed and operating. 2. Adjust reversing switch for desired control action: with increasing input, output will either increase (INC) or decrease (DEC). 3. Turn DERIVATIVE adjustment (if present) to 0.01 or to safe low value. Turn PROPORTIONAL BAND to maximum or safe high value. Turn RESET adjustment (if present) to MAX or to safe high value. 7

MI 017-450 May 1978 Operation Set-Point Index Measurement Pointer Transfer Switch Set-Point Adjustment Knob Manual Output Wheel 4. Open shutoff values and close bypass valve. Control Valve Shutoff and Bypass Valves 5. Start up on manual control as follows: a. Move transfer switch to MAN. b. Turn set-point knob so that set-point index is at desired set (control) point. c. Turn on controller air supply at rear of shelf. (Pressure must be at a fixed value between 140-150 kpa or 20-22 psi.) Blow out filter. d. Adjust output with manual output wheel so that measurement pointer is held as close as possible to set-point index. Avoid making frequent or excessive changes as this may delay balancing out of process. 6. After measurement has stabilized, measurement pointer will be in line with set-point index. Move transfer switch to AUTO. Process is now on automatic control. 7. Adjust PROPORTIONAL BAND, RESET, and DERIVATIVE controls (if present) for best process operation (see page 9). 8. To return to manual control, move transfer switch to MAN. Output will remain at last value until manual control wheel is turned. Elimination of Outside Disturbances If, on manual control, the measurement shows cycling, pulsations, or erratic performance, while the final operator is unchanged, this trouble obviously is not due to the controller. For best control performance, such outside disturbances must be eliminated or reduced to a minimum before placing the instrument on automatic control. 8

Operation MI 017-450 May 1978 Control Adjustments Control Adjustments Latch to raise plastic cover for access to adjustments. Transfer Switch NOTE Before making these adjustments, instrument must be operating in manual control. Proportional Controller (Model 130M- 2) 1. With transfer switch in MAN, set PROPORTIONAL BAND at maximum or at safe high value. 2. Move transfer switch to AUTO, and make change in set point. Observe process and output responses. 3. If cycling does not occur, adjust PROPORTIONAL BAND to half of previous value. 4. Repeat Steps 2 and 3 until cycling is observed. Then increase PROPORTIONAL BAND to twice its value. Proportional Plus Derivative Controller (Model 130M- 3) 1. Turn DERIVATIVE to 0.01 or to safe low value. 2. Adjust PROPORTIONAL BAND as described in Proportional Controller above. 3. Adjust DERIVATIVE using same procedure as Proportional Band, except doubling each setting instead of halving it. Proportional Plus Reset Controller (Model 130M- 4) 1. Turn RESET to MAX or to safe high value. 2. Adjust PROPORTIONAL BAND as described in Proportional Controller above. 3. Adjust RESET using same procedure as Proportional Band. 9

MI 017-450 May 1978 Operation Proportional Plus Reset Plus Derivative Controller (Model 130M- 5) 1. Turn RESET to MAX or to safe high value. 2. Turn DERIVATIVE to 0.01 or to safe low value. 3. Adjust PROPORTIONAL BAND as described in Proportional Controller on page 9. 4. Adjust DERIVATIVE using same procedure as Proportional Band, except doubling each setting instead of halving it. 5. Adjust RESET to final setting of Derivative in Step 4, above. Calibration Checks The transmitter and receiver assemblies can be calibrated either to the SI (20 to 100 kpa) or to the English (3 to 15 psi) signal pressure range. The two ranges are not exactly equivalent; therefore, the entire system must be calibrated in the same units. Measurement Receiver Assembly Set-point Transmitter Assembly Test Connection In OFF Position In TEST Position When test connection is in TEST position, measurement pointer reads set-point pressure, and this pressure is delivered to test connection. 1. Withdraw controller part way and open access door on right side. If left side panel and optional recorder (if present) are removed, adjustments will be more accessible. To remove panel, loosen screw at rear, and slide out panel. To remove recorder, remove the 2 screws on pointer movement bracket, loosen the 2 screws on front of top plate, and disconnect link. By lifting up on top plate, you can ease the recorder out. 2. Attach 0-140 kpa or 0-20 psi manometer (or test gauge) to controller test connection. Use 3/32 inch ID rubber (for flexibility) tubing at test connection. 3. Move test connection to right to TEST position. 10

Operation MI 017-450 May 1978 4. With controller air supply turned on at rear of shelf, turn set-point knob so that setpoint index is at 0, 50, and 100% of scale. Note manometer reading at each setting. Readings on manometer should be 20, 60, and 100 kpa (or 3, 9, and 15 psi) respectively. (Ignore measurement pointer readings at this time.) If manometer readings are not within required accuracy, calibrate set-point transmitter assembly, as described below. 5. After set-point transmitter assembly has been calibrated, repeat Step 4, this time noting how closely measurement pointer agrees with set-point index. If measurement pointer readings are not within required accuracy, calibrate measurement receiver assembly as described on page 13. Shop Calibration A spare shelf assembly or a calibrating fixture (Part C0138SN, obtainable from The Foxboro Company) is recommended. Connect a 140 kpa or 20 psi air supply to rear of shelf or to S connection on fixture. If shelf or fixture is not available, air supply must be connected to rear of controller. Use 1/4 inch OD Polyflo tubing (or equivalent). See illustration on page 16 for cross referencing of connections at rear of shelf and rear of controller. Calibration - Set-point Transmitter Assembly Squaring Up of Linkage for Complete Calibration If parts have been replaced, or for some other reason a complete recalibration is necessary, square up linkage before actual calibration. If set-point index does not have full scale travel, note amount of error and turn set-point knob to move index to 50% of scale. Loosen set-point knob clamp screw and slip index on its shaft by amount of error +2%, in direction to get full scale travel. Tighten clamp screw. Repeat during calibration if necessary. 1. With calibrating equipment set up as shown on page 10, rotate span adjustment screw so that about four turns of spring are visible between upright support and spring spacer. 2. Turn set-point knob so that manometer reading is 60 kpa or 9 psi. 3. Rotate zero adjustment screw so that moving plate and upright support are parallel (about 32 mm or 1 1/4 inch apart). Hold output at 60 kpa or 9 psi by adjusting setpoint knob. 4. Turn set-point knob so that set-point index is at midscale. 11

MI 017-450 May 1978 Operation 5. Loosen index clamp screw and slip index on its shaft so that angel between index and index drive lever is about 80. Retighten clamp screw. 6. Turn set-point knob so that index is at midscale. 7. Adjust length of link so that output is 60 kpa or 9 psi. Calibration Procedure When viewing zero and span adjustments as shown in illustration, turn adjustments clockwise to decrease output. 1. With calibrating equipment set up as shown on page 10, turn set-point knob so that set-point index is at 0% of scale. 2. Rotate zero adjustment screw so that output reading on manometer is 20 kpa or 3 psi. 3. Turn set-point knob so that set-point index is at 100% of scale. 4. Output should be 100 kpa or 15 psi. If it is not, use span adjustment to move output about halfway toward correct value. 5. Repeat Steps 1 through 4 until outputs for 0% and 100% of scale are correct. 6. Turn set-point knob so that set-point index is at midscale. If output is not 60 kpa or 9 psi, adjust length of link as follows: Adjust length so that output pressure changes by 10 times amount of error, in direction of error. For example, if output reads 8.8 psi, adjust link so that output reads 6.8 psi. 12

Operation MI 017-450 May 1978 7. Loosen set-point knob clamp screw and move index drive lever (see above diagram) so that output is approx. 60 kpa or 9 psi. Retighten screw. 8. Loosen index clamp screw and slip set-point index on its shaft to midscale. Retighten screw. 9. Repeat Steps 1 through 8 until readings are correct for 0, 50, and 100% of scale. 10. Check calibration of measurement receiver assembly (Step 5, page 10). Calibration - Measurement Receiver Assembly Squaring Up of Linkage for Complete Calibration If parts have been replaced, or for some other reason a complete recalibration is necessary, square up the linkage before the actual calibration. 1. With calibrating equipment set up as shown on page 10, turn set-point knob so that manometer reading is 60 kpa or 9 psi. (If transmitter assembly is in calibration, setpoint index will be at midscale.) 2. Rotate span adjustment screw so that about four turns of spring are visible between upright support and spring spacer. 3. Rotate zero adjustment screw so that moving plate and upright support are parallel (about 32 mm or 1 1/4 inch apart). 4. Loosen pointer clamp screw and slip pointer on its shaft so that angle between pointer and pointer drive lever is about 80. Retighten clamp screw. 5. Adjust length of link to move pointer to midscale. 13

MI 017-450 May 1978 Operation Calibration Procedure When viewing zero and span adjustments as shown in illustration above, turn adjustments clockwise to increase pointer readings. If controller is equipped with optional recorder, it is recommended that recorder link be disconnected before calibration (see Instruction MI 017-475 for recorder details). 1. With calibrating equipment set up as shown on page 10, turn set-point knob so that manometer reading is 20 kpa or 3 psi. 2. Use zero adjustment to set measurement pointer at 0% of scale. 3. Turn set-point knob so that manometer reading is 100 kpa or 15 psi. 4. Measurement pointer should be at 100% of scale. If it is not, use span adjustment to move pointer about halfway toward 100% of scale. 5. Repeat Steps 1 through 4 until pointer reads correctly when 20 and 100 kpa (or 3 and 15 psi) are applied to element. 6. Turn set-point knob so that manometer reading is 60 kpa or 9 psi. If measurement pointer does not read 50% of scale, adjust length of link as follows: adjust length to move pointer 10 times amount of error in direction of error. For example, if pointer is at 49% of scale, adjust link so that pointer moves to 39% of scale. 7. Loosen pointer clamp screw and slip measurement pointer on its shaft to midscale. Retighten clamp screw. 8. Repeat Steps 1 through 7 until measurement pointer reads correctly when 20, 60, and 100 kpa (or 3, 9, and 15 psi) are applied to element. Adjustment of Stops Illustrated is receiver assembly; transmitter assembly is similar. High Limit Stop Adjustment 1. Receiver Assembly Apply 100 kpa or 15 psi to receiver element. Transmitter Assembly Turn set-point knob so that set-point index is at 100% of scale. 2. Rotate high limit stop until it just touches moving plate, then back off 1/4 turn. 14

Operation MI 017-450 May 1978 Low Limit Stop Adjustment (Transmitter Assembly Only) 1. Turn set-point knob so that set-point index is at 0% of scale. 2. Rotate low limit stop until it just touches moving plate, then back off 1/4 turn. High Limit Stop Low Limit Stop (on transmitter assembly only) Damping Adjustment (Receiver Assemblies Only) To adjust, remove all damping by turning screw fully counter-clockwise. Then slowly turn screw clockwise until pulsations of pointer are barely visible. Use minimum amount of damping. 15

MI 017-450 May 1978 Operation Pneumatic Connection Identifications The illustration below identifies the user connections at the rear of the shelf and the corresponding tubing connections at the rear of the controller. External Reset (Optional) Connecting Tubing and Plug Output Set-point Readout (Optional) External Reset (Optional) Output Measurement Supply Set-point Readout (Optional) Measurement Supply 16

Operation MI 017-450 May 1978 To Remove Right Side Panel Normally there should be no need to remove the right side panel. However, the replacement of certain parts (pneumatic circuit board, batch switch, and so forth) does require the removal of this panel. 1. Remove five screws from plate on top of controller. 2. Remove screw at rear of panel (left screw facing rear of controller). 3. While holding up top plate, lift out side panel. Do not try to slide out panel. 4. When reinstalling panel, note that it fits into grooves in both top and bottom plates. Right Side Panel Screws at Top of Controller Top Plate Screw at Rear of Panel 17

MI 017-450 May 1978 Operation ISSUE DATES DEC 1976 The Foxboro Company 33 Commercial Street Foxboro, MA 02035-2099 United States of America http://www.foxboro.com Inside U.S.: 1-888-FOXBORO (1-888-369-2676) Outside U.S.: Contact your local Foxboro Representative. Facsimile: (508) 549-4492 A Siebe Group Company Foxboro is a registered trademark of The Foxboro Company. Siebe is a registered trademark of Siebe, plc. Copyright 1976-1978 by The Foxboro Company All rights reserved MB 100 Printed in U.S.A 0578