Technical ata sheet R7..R Open-close ball valves, 3-way, with flange PN 6 for open an close col an warm water systems for switching functions on the water sie an 2-point controls in air-hanling an heating systems air bubble-tight (control path ) Type overview Technical ata Type k vs [m 3 /h] [Inches] Functional ata Flow meia ol an hot water, water with max. 50% volume of glycol Temperature of meium +5... +110 1) (lower or higher temperatures on request) Rate pressure p s see «Type overview» Flow rate ypass : approx. 50% of k vs value eakage rate ontrol path : ir bubble-tight (O 1, IN3230 T3) ypass : 1% of k vs value Pipe connector Flange PN 6 to EN 1092/1 ifferential pressure Δp max losing pressure Δp s 100 kpa 600 kpa ngle of rotation 90 (Operating range 15... 90 ) Installation position Upright to horizontal (in relation to the stem) aintenance aintenance-free aterials Fitting Forge, nickel-plate brass boy Valve cone an stem hrome-plate brass Stem seal O-Ring, EP all seat PTFE, O-Ring Viton Flange ring 15 / 20: Zinc-plate steel 25... 50: luminum Flange joint surface Nickel-plate brass imensions / Weights see «imensions an weights», page 3 otorizing see the complete overview of water solutions p s [kpa] R715R 8.6 15 ¹/₂ 600 R720R 21 20 ³/₄ 600 R725R 26 25 1 600 R732R 32 32 1 ¹/₄ 600 R740R 32 40 1 ¹/₂ 600 R750R 49 50 2 600 1) The allowe meia temperature can be limite, epening on the type of actuator. The correct values can be foun in the corresponing actuator ata sheets.. www.belimo.com T5-R7..R Open-close en v1.2 09.2008 Subject to changes 1 / 3
R7..R Open-close ball valves, 3-way, with flange PN 6 Safety notes Prouct features Installation notes oe of operation Recommene mounting positions! The valve has been esigne for use in stationary heating, ventilation an air conitioning systems an is not allowe to be use outsie the specifie fiel of application, especially in aircraft or in any other airborne means of transport. It may only be installe by suitably traine personnel. ll applicable legal or institutional installation regulations must be complie with. The valve oes not contain any parts that can be replace or repaire by the user. The valve is not allowe to be ispose of as househol refuse. ll locally vali regulations an requirements must be observe. The recognize rules shoul be applie when etermining the flow characteristic of final controlling elements. The open-close ball valve is operate by a rotary actuator. The rotary actuator is controlle by an open-close signal. Open the ball valve counterclockwise an close it clockwise. The valve may be mounte either vertically or horizontally. It is not permissible, mounting the valve with the stem pointing ownwars. 90 90 Water quality requirements aintenance irection of flow The water quality requirements specifie in VI 2035 must be ahere to. all valves are relatively sensitive control evices. In orer to ensure a long service life, it is avisable to fit strainers. The ball valves an rotary actuators are maintenance-free. efore any kin of service work is carrie out on actuator sets of this type, it is essential to isolate the rotary actuator from the power supply (by unplugging the power lea). ny pumps in the part of the piping system concerne must also be switche off an the appropriate isolating fittings close (allow everything to cool own first if necessary an reuce the pressure in the system to atmospheric). The system must not be returne to service until the ball valve an the rotary actuator have been properly reassemble in accorance with the instructions an the pipework has been refille in the proper manner. The irection of flow, specifie by an arrow on the housing, is to be complie with, since otherwise the ball valve can be amage. Please ensure that the ball is in the correct position. = 100% = 0% = 0% = 100% ccessories echanical accessories escription Stem heating ZR24-1 2 / 3 T5-R7..R Open-close en v1.2 09.2008 Subject to changes www.belimo.com
R7..R Open-close ball valves, 3-way, with flange PN 6 imensions an weights imensional rawings min. Y min. X H 2) H 42 X 1) Y 1) Weight [kg] 15 101.5 45 73 80 15 55 4 x 11 230 90 1.8 20 112 47.5 79 90 15 65 4 x 11 230 90 2.4 25 132 47.5 92 100 20 75 4 x 11.5 230 90 2.5 32 143.5 52 102.5 120 17 90 4 x 14 240 100 3.4 40 149.5 52 105 130 18 100 4 x 14 240 105 4 50 165 58 121 140 18 110 4 x 14 240 110 5.6 1) inimum istance with respect to the valve centre. 2) The actuator imensions can be foun on the respective actuator ata sheet. Further ocumentations omplete overview «The complete range of water solutions» ata sheets for actuators Installation instructions for ball valves an/or actuators Notes for project planning (hyraulic characteristic curves an circuits, installation regulations, commissioning, maintenance etc.) www.belimo.com T5-R7..R Open-close en v1.2 09.2008 Subject to changes 3 / 3
70168-00001. R7..R R6..R min. X H TR.. R.. NR.. F.. FR.. RF.. min. Y mm mm TR.. R.. NR.. F.. FR.. / RF.. H X Y X Y X Y X Y X Y 90 90 R609R...R615R R709R...R715R 15 ¹/₂ 101.5 45 73 80 15 55 4 x 11 184 80 198 80 230 80 203 90 203 90 R618R...R620R R718R...R720R 20 ³/₄ 112 47.5 79 90 15 65 4 x 11 201 85 232 85 205 90 205 90 R623R...R625R R723R...R725R 25 1 132 47.5 92 100 20 75 4 x 11 201 90 232 90 205 90 205 90 R631R...R632R R731R...R732R 32 1¹/₄ 143.5 52 102.5 120 17 90 4 x 14 237 100 210 100 R639R...R640R R738R...R740R 40 1¹/₂ 149.5 52 105 130 18 100 4 x 14 237 105 210 105 R649R...R650R R748R...R750R 50 2 165 58 121 140 18 110 4 x 14 243 110 216 110 R664R...R665R 65 2¹/₂ 180.5 69 160 18 130 4 x 14 254 120 227 120 R679R...R680R 80 3 191.5 69 190 20.5 150 4 x 18 254 135 227 135
k v k v Y 100% 0% R713R R731R R725R R750R 100% 0% 0% 100% t p max ( 10 ) +5... +110 (+120 ) 100 kpa p s 600 kpa (PN 6) R609R R618R R639R R615R R632R R610R R623R R649R R620R R640R R611R R631R R664R R625R R650R R612R R679R R665R R613R R680R R709R R718R R738R R715R R732R R711R R723R R748R R720R R740R Y 100% 0% 100% 0% 0% 100% 100% 0% 0% 100%