LNVx Gas Conversion Kit Instructions

Similar documents
TB132. Gas Conversion Kits for NV & NVS Heaters. Issue 1.0 May Applies to models: NV & NVS

Installation Instructions

SL G3. Warning

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Propane Conversion Kit Instruction

Your safety and the safety of others are very important.

Propane Conversion Kit Instructions

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

Gas Conversion Kits CERAMIC HEATER SERIES (1, 2, 3, 4 Burner Units)

Propane Conversion Kit Instruction

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION MANUAL

Propane Conversion Kit Instruction

Gas Conversion Kit Pilot Ignition Heaters

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Conversion instructions from natural gas to propane

Installation Instructions For Natural Gas Conversion

36H SERIES Combination Gas Valve

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

PRESSURE REGULATOR LBM SERIES

Instructions for High Altitude Conversion

INSTALLATION INSTRUCTIONS

HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Gas Conversion Kits Push Through (Positive Pressure) Tube Heater Models

ACCESSORY KIT INSTALLATION INSTRUCTIONS

/2004 US/CA

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

installation instructions

Operator: Save these instructions for future use!

GAS KITS & ACCESSORIES 504,986M 11/2004 HIGH ALTITUDE KIT

GM-7000 Series CE Approved Gas Control Valve

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

Gas Valve Replacement Kit

MAINTENANCE PROCEDURE FOR X 650

Using propane cylinders safely

VK8515M(R) MODULATING GAS CONTROL APPLICATION DESCRIPTION SPECIFICATIONS INSTRUCTION SHEET. Electrical data

13kW Patio Heater. Assembly & User Instructions

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

UNITY 2. Uni-DAAMS Manual. Version 1.3 (Changes to Section 1.1) March 2010

VR46.5V(A)/VR86.5V(A) SERIES

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

AREA VALVE SERVICE UNITS

OPERATING INSTRUCTIONS

DANGER WARNING IMPORTANT

FIREPLACE INSTALLATION

Quick Reference Guide - Kleenmaid Gas Cooktops

GM Series Dual-Block Multi-Function Gas Control Valves

ACCESSORY KIT INSTALLATION INSTRUCTIONS

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

Crosby style JCE Safety Valve Installation, Maintenance and Adjustment Instructions CROSBY

Filling valves AL, ALM Series Automatic filling units ALOMDIW, ALOMDNW Series

Air Intake Snorkel Kit

A U T O O P E N S E R I E S C A P P R E S S O P E R A T O R S M A N U A L

DN 50 REGULATOR SUTON 5000A1 REGULATOR SUTON 5000D1

Installation Instructions

5 Gallon EVkeg Operation Manual

Booster Pump PB4-60 Replacement Kits

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition

SIT Group 710 MINISIT MULTI-FUNCTIONAL GAS CONTROL THERMOELECTRIC FLAME SUPERVISION DEVICE PRESSURE REGULATOR TEMPERATURE CONTROL PIN 0085AQ0287

Module 6. Tightness Testing

User, Installation, Servicing and Conversion Instructions. Opus 700 Gas Chargrills OG7401, OG7402, OG7403 & OG7404

Operator: Save these instructions for future use!

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

Section 3- Repair and Calibration Procedures

Rheem Spare Parts Manual Commercial gas model A Exterior 265L

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Auto-Rewind Hose Reels INSTRUCTION MANUAL FOR OXY-LPG MODEL

VK41../VK81.. GAS CONTROLS FOR COMBINED VALVE AND IGNITION SYSTEM SPECIFICATIONS APPLICATION DESCRIPTION INSTRUCTION SHEET

System Pressure Manager Standard & System Pressure Manager Plus

G96 Series BASOTROL Dual Operator Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

INSTRUCTION MANUAL. Gas Salamander

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION

ASSEMBLY INSTRUCTIONS HOODED GAS GRILL. Model:KYQ-BFT402

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

Model 130M Pneumatic Controller

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

BASIN AND WALL MIXER INSTALLATION INSTRUCTIONS

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

KTM 50 (DN ) Installation, maintenance and operating instructions

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

VR8305 Direct Ignition Combination Gas Control

Operating Instructions Model and Hydrostatic Test Pump

RIX COMPRESSORS. MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230. November 21, 2002 APPLICABILITY [ A]

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Rheem Spare Parts Manual. Commercial gas model A Exterior 265L

Transcription:

TB134 Issue 1.0 Nov 2018 Applies to models: LNVx LNVx Gas Conversion Kit Instructions +44 (0) 1460 53535 info@powrmatic.co.uk www.powrmatic.co.uk

General Information Heater conversion between gases will require a change of burner injectors, alteration of burner pressure and re-commissioning of the heater. All gas valves used on the LNVx range have Parts & Tools required pressure regulators that may be set to operate on natural gas or propane (LPG). These assembly instructions describe the parts required and procedures to be carried out when converting this heater Drill plus bits Flat head screwdriver PoziDrive screwdriver Electrical screwdriver Spanner Set MODEL Conversion Kit part number Propane (LPG) Conversion Kit Injector Washers Labels Conversion Kit part number Natural Gas Conversion Kit Injector Washers LNVx15 LNVx15LPG 4 4 3 LNVx15NG 4 4 3 LNVx20 LNVx20LPG 4 4 3 LNVx20NG 4 4 3 LNVx25 LNVx25LPG 5 5 3 LNVx25NG 5 5 3 LNVx35 LNVx35LPG 7 7 3 LNVx35NG 7 7 3 LNVx40 LNVx40LPG 8 8 3 LNVx40NG 8 8 3 LNVx45 LNVx50LPG 10 10 3 LNVx50NG 10 10 3 LNVx50 LNVx50LPG 10 10 3 LNVx50NG 10 10 3 LNVx60 LNVx60LPG 8 8 3 LNVx60NG 8 8 3 LNVx70 LNVx75LPG 10 10 3 LNVx75NG 10 10 3 LNVx90 LNVx90LPG 8 8 3 LNVx90NG 8 8 3 LNVx120 LNVx120LPG 10 10 3 LNVx120NG 10 10 3 LNVx140 LNVx140LPG 12 12 3 LNVx140NG 12 12 3 Labels Gas Safety (Installation & Use) (Amendment) Regulations It is law that all gas appliances are installed, adjusted and, if necessary, converted by qualified persons* in accordance with the current issue of the above regulations. Failure to install appliances correctly can lead to prosecution. It is in your own interests and that of safety to ensure that the law is complied with. * A gas safe registered Engineer. Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas. (Refer to tables opposite for new gas inlet pressures.) page no. 2 of 8 LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018.

Procedure WARNING: Always switch off and disconnect electricity supply and close service valve before carrying out any servicing or replacement of failed components. 1. Ensure that the gas service valve is turned OFF. 1.1 Remove rectification probe screw and withdraw. 2. Remove the burner heat shield, 3 screws. 1.2 Remove spark electrode screw and withdraw. 3. Release the outlet connection flange from the gas valve by removing the four screws. 1.3 Remove the electrical plug connections from the top of the gas valve. 4. Remove two fixing screws securing the burner assembly to the bulkhead. LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018. page no. 3 of 8

Procedure 5. Disengage from tab. 8. Remove the main burner injectors and washers. 9. Replace with the new injectors/washers for the new gas ensuring a gas tight seal. 6. Lift out burner assembly 10. Refit all other components in reverse order. 7. Remove the manifold by removing the four screws securing it to the burner assembly. page no. 4 of 8 LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018.

Commissioning and Testing Adjustments Conversion is carried out by adjusting the burner pressures to the values shown in the tables at the rear of this document. High/Low Regulation 1. Set external controls to ensure the main burner is off. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the gas valve. Lever off the plastic cover from the High/Low regulator. 2. Set external controls to turn on the main burner and maintain high fire. Adjust the burner gas pressure to the values shown in the tables at the rear of this document. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation. Repeat with the external controls set to maintain low fire. Minimum Setting. Disconnect electrical connection to the regulator and turn the burner back on and wait until the burner pressure has stabilised. Keeping the nut (C) stationary, use a 6 x 1 screwdriver to turn the slotted adjustment screw (D) clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Reconnect high/low regulator and check high fire pressure. Repeat both steps if necessary and then replace cover cap 5. Turn off the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection fluid. Replace access panel. For actual valve adjustment, follow the specific valve type detailed on the next pages. Note: High fire setting must be adjusted first after which the low fire setting can be set. Any adjustment of the high fire setting alters the minimum setting. Sigma 843 Adjustment Maximum Setting. With the controls set to high fire, use an adjustable or 10mm spanner to screw the adjustment nut (C) in to increase and out to decrease, until the required pressure is obtained. Turn the burner On and OFF several times to check the pressure setting and then turn off. Honeywell High/Low Adjustment Maximum Setting With the controls set to high fire, use an adjustable or 8mm spanner to turn the adjustment screw, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Turn the burner On and OFF several times to check the pressure setting and then turn off. Minimum Setting Disconnect electrical connection to the regulator and turn the burner back on and wait until the burner pressure has stabilised. Use a LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018. page no. 5 of 8

Commissioning and Testing screwdriver to turn the slotted adjustment screw clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Reconnect high/low regulator and check high fire pressure. Repeat both steps if necessary and then replace cover cap. Note: Minimum fire setting must be adjusted first after which the high fire setting can be set. Any adjustment of the minimum fire setting alters the maximum setting. 5. Turn off the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection fluid. Replace access panel. Shaft Cap Adjustment nut (7mm) for maximum pressure setting Adjustment nut (9mm) for minimum pressure setting O ring 6.3mm AMP terminals Cover Lever point Hexagonal adjustment screw for maximum pressure setting Internal slotted adjustment screw for minimum pressure setting Honeywell Modulating Adjustment 1. Set external controls to ensure that the main burner is off. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the gas valve. 2. Set external controls so as to turn on the main burner and maintain high fire. Compare the measured burner gas pressure to that stated on the data plate. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation. Repeat with the external controls set to maintain low fire. For actual valve adjustment, follow the specific valve type detailed on the next section. Minimum Setting. Disconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilized. Turn 9mm adjustment nut for low fire pressure clockwise to increase and counter-clockwise to decrease until the required pressure is obtained. Reconnect modulating regulator and check high fire pressure, readjust if necessary. Maximum Setting. Disconnect electrical connection of modulating regulator and turn burners back on and wait until the burner pressure has stabilised. Push shaft gently downwards to the maximum adjustment screw and hold there. Turn 7mm adjustment nut for high fire pressure, clockwise to increase and counter-clockwise to decrease, until the required pressure is obtained. Release shaft. Repeat both settings if necessary and then replace cover cap. 5. Turn off the main burner, disconnect the pressure gauge and replace the sealing screw. Turn on the main burner and test for gas soundness around pressure test joint using a leak detection fluid. Replace access panel. page no. 6 of 8 LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018.

Commissioning and Testing On/Off Regulation 1. Set external controls to ensure the main burner is off. Open the side access panel. Connect a pressure gauge to the burner pressure test point on the gas valve. 2. Set external controls to turn on the main burner. Adjust the burner gas pressure to the values shown in the tables at the rear of this document. In addition it is advisable to check the gas rate using the gas meter dial pointer ensuring that no other appliances supplied through the meter are in operation. 3. To adjust burner pressure simply unscrew the aluminium cover using a flat head screwdriver and turn the adjustment screw clockwise to increase, anti-clockwise to decrease. Final Checks In addition to setting the burner pressures, it is advisable to check the gas rate using the gas meter dial pointer. Ensure that no other appliances supplied through the meter are in operation. After setting the burner pressures, the CO/CO2 content in the flue gases as well as the flue gas temperatures can be checked and recorded by sampling in the first section of flue fitted to the flue outlet of the unit. Turn off the main burner and disconnect the pressure gauge and replace the sealing screw. Turn on the main burner as above and test for gas soundness around pressure test joint using a leak detection fluid e.g. soap solution. Remove the original data plate on the heater and replaced with new data badge supplied in the kit. Two change of gas stickers are also supplied in the kit. Place one on the side of the gas valve and one on the outside of the heater adjacent to the gas pipe entry point. Note*: Ensure the original data badge is removed and replaced with new data badge and change of gas stickers. Model 15 20 25 35 40 45 50 60 70 90 120 140 Natural Gas G20 High Fire CO2 % 8.20 8.67 8.41 8.02 8.80 8.80 8.6 8.46 9.15 7.50 8.40 8.72 FGT (nominal) C 143.8 147.6 154.5 150.5 153.2 130.7 152.0 149.7 158.6 132.0 153.0 128.0 Low Fire CO2 % 4.07 5.04 4.82 4.76 5.15 5.20 4.9 4.83 5.00 4.50 5.00 4.99 FGT (nominal) C 105.2 119.7 123.4 124.0 123.1 105.7 120.5 115.0 121.7 123.0 121.0 98.4 Propane G31 High Fire CO2 % 9.00 9.20 9.40 9.8 9.86 10.02 10.0 9.50 9.60 7.50 9.40 9.31 FGT (nominal) C 136.2 149.7 151.3 153.0 152.8 130.8 178.0 148.4 158.9 143.0 148.0 126.6 Low Fire CO2 % 4.54 5.90 5.43 5.9 5.92 5.93 5.90 5.64 6.07 4.80 5.60 5.97 FGT (nominal) C 100.7 119.0 120.3 142.0 123.7 105.0 126.0 113.0 125.9 119.0 122.0 99.8 LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018. page no. 7 of 8

Commissioning and Testing Natural Gas to Propane (LPG) Conversion Data Nominal Inlet Pressure = 37mbar, Minimum Inlet Pressure = 37mbar High Fire Low Fire MODEL Conversion Kit part number Injectors No. Size (mm) Marked Injector part number HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: 01460 53535 Fax: 01460 52341 Pressure Gas Rate Pressure Gas Rate mbar m³/h mbar m³/h LNVx15 LNVx15LPG 4 1.36 240 142401661 21.3 0.6 8.0 0.39 LNVx20 LNVx20LPG 4 1.36 240 142401661 19.8 0.8 9.5 0.57 LNVx25 LNVx25LPG 5 1.36 240 142401661 21.3 1.1 10.2 0.74 LNVx35 LNVx35LPG 7 1.60 160 142401678 22.5 1.5 11.5 1.1 LNVx40 LNVx40LPG 8 1.36 240 142401661 19.5 1.7 9.6 1.17 LNVx45 LNVx50LPG 10 1.6 160 142401678 18.4 1.9 8.8 1.31 LNVx50 LNVx50LPG 10 1.6 160 142401678 24.2 2.3 12.2 1.6 LNVx60 LNVx60LPG 8 1.6 160 142401678 25.4 2.6 12.3 1.85 LNVx70 LNVx75LPG 10 1.6 160 142401678 22.9 3.2 11.3 2.15 LNVx90 LNVx90LPG 8 2.26 580 142401667 13.5 4.0 7.2 2.91 LNVx120 LNVx120LPG 10 2.26 580 142401667 14.6 5.1 7.2 3.69 LNVx140 LNVx140LPG 12 2.26 580 142401667 13.4 5.9 6.4 4.11 Propane (LPG) to Natural Gas Conversion Data Nominal Inlet Pressure = 20mbar, Minimum Inlet Pressure = 17.5mbar High Fire Low Fire MODEL Conversion Kit part number Injectors No. Size (mm) Marked Injector part number Pressure Gas Rate Pressure Gas Rate mbar m³/h mbar m³/h LNVx15 NVx15NG 4 1.94 500 142401664 13.1 1.64 5.0 1.01 LNVx20 NVx20NG 4 1.94 500 142401664 12.3 2.17 6.0 1.49 LNVx25 NVx25NG 5 1.94 500 142401664 13.5 2.75 6.5 1.92 LNVx35 NVx35NG 7 2.54 750 142401665 13.2 3.86 5.8 2.76 LNVx40 NVx40NG 8 1.94 500 142401664 12.3 4.29 6.0 2.98 LNVx45 NVx50NG 10 2.54 750 142401665 7.4 4.97 3.5 3.43 LNVx50 NVx50NG 10 2.54 750 142401665 9.5 5.77 4.5 3.96 LNVx60 NVx60NG 8 2.54 750 142401665 10.6 6.88 5.2 4.77 LNVx70 NVx75NG 10 2.54 750 142401665 9.4 8.10 4.6 5.60 LNVx90 NVx90NG 8 3.5 1500 142401666 6.0 10.32 3.0 7.58 LNVx120 NVx120NG 10 3.5 1500 142401666 6.7 13.44 3.3 9.61 LNVx140 NVx140NG 12 3.5 1500 142401666 6.2 15.45 2.9 10.7 Every effort is made to ensure accuracy at time of going to press. However as part of continued product improvement, we reserve the right to alter specification without prior notice. page no. 8 of 8 LNVx Range Gas Conversion Kit Doc ref: TB134 issue 1.0 Nov 2018.