A c o n c e p t u a l c o m p a r a t i v e s t u d y o f F L E X s t r a t e g i e s t o c o p e w i t h e x t e n d e d S B O.

Similar documents
A comparative study of FLEX strategies to cope with Extended Station Blackout (SBO)

The Nitrogen Threat. The simple answer to a serious problem. 1. Why nitrogen is a risky threat to our reactors? 2. Current strategies to deal with it.

Loss of Normal Feedwater Analysis by RELAP5/MOD3.3 in Support to Human Reliability Analysis

Integrated Coping Strategies for Beyond-Design-Basis External Events

ACCIDENT MANAGEMENT AND EPR AT DUKOVANY NPP

ASVAD THE SIMPLE ANSWER TO A SERIOUS PROBLEM. Automatic Safety Valve for Accumulator Depressurization. (p.p.)

Human Reliability Analysis of Ultimate Response Guideline in a Compound Disaster. Hyatt Regency Tokyo, Japan April 16, 2013

CONTENTS OF THE PCSR CHAPTER 1 - INTRODUCTION AND GENERAL DESCRIPTION

Enhancing NPP Safety through an Effective Dependability Management

Safety and efficiency go hand in hand at MVM Paks NPP

TEPCO s Safety Assurance Philosophy on Nuclear Power Generation Plants

PRA Methodology Overview

Extensive Damage Mitigation Guidelines (EDMG)

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER P: REFERENCE OPERATING CONDITION STUDIES (PCC)

If -~l N ---- "Soli T Khericha/SLK2/LMITCO/INEEL/US" 7VEFL To: Glenn Kelly t. Date: From:

An Improved Modeling Method for ISLOCA for RI-ISI and Other Risk Informed Applications

Review and Assessment of Engineering Factors

Engineering & Projects Organization

THE CANDU 9 DISTRffiUTED CONTROL SYSTEM DESIGN PROCESS

IAEA Training in Level 2 PSA MODULE 8: Coupling Source Terms to Probabilistic Event Analysis (CET end-state binning)

Distributed Control Systems

Containment Isolation system analysis and its contribution to level 2 PSA results in Doel 3 unit

PI MODERN RELIABILITY TECHNIQUES OBJECTIVES. 5.1 Describe each of the following reliability assessment techniques by:

HIGH WIND PRA DEVELOPMENT AND LESSONS LEARNED FROM IMPLEMENTATION Artur Mironenko and Nicholas Lovelace

Safety Analysis: Event Classification

How to reinforce the defence-indepth in NPP by taking into account natural hazards?

Nuclear safety Lecture 4. The accident of the TMI-2 (1979)

NOT PROTECTIVELY MARKED. REDACTED PUBLIC VERSION HPC PCSR3 Sub-chapter 16.2 PSA Results and Discussion NNB GENERATION COMPANY (HPC) LTD

CHAPTER 28 DEPENDENT FAILURE ANALYSIS CONTENTS

NUBIKI Nuclear Safety Research Institute, Budapest, Hungary

Advanced LOPA Topics

Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance

Correlation of Equipment Failures in Seismic PRAs

EXPERIMENTAL SUPPORT OF THE BLEED AND FEED ACCIDENT MANAGEMENT MEASURES FOR VVER-440/213 TYPE REACTORS

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS. A high-capacity EBA system [CSVS] [main purge]

Workshop Information IAEA Workshop

System Operating Limit Definition and Exceedance Clarification

DISTRIBUTION LIST. Preliminary Safety Report Chapter 7 Safety Systems UK HPR1000 GDA. GNS Executive. GNS all staff. GNS and BRB all staff CGN EDF

THE NITROGEN INJECTION THREAT IN PWR REACTORS

Ranking of safety issues for

Tools and Methods for Assessing the Risk Associated with Consequential Steam Generator Tube Rupture

Considerations for the Practical Application of the Safety Requirements for Nuclear Power Plant Design

Severe Accident Management Programmes for Nuclear Power Plants

OBJECTIVE 6: FIELD RADIOLOGICAL MONITORING - AMBIENT RADIATION MONITORING

Assessing Combinations of Hazards in a Probabilistic Safety Analysis

SENSITIVITY ANALYSIS OF THE FIRST CIRCUIT OF COLD CHANNEL PIPELINE RUPTURE SIZE FOR WWER 440/270 REACTOR

System Operating Limit Definition and Exceedance Clarification

Effects of Delayed RCP Trip during SBLOCA in PWR

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER F: CONTAINMENT AND SAFEGUARD SYSTEMS 7. CONTAINMENT HEAT REMOVAL SYSTEM (EVU [CHRS])

Study on Human Errors in DCS of a Nuclear Power Plant

AP1000 European 19. Probabilistic Risk Assessment Design Control Document

Available online at ScienceDirect. Procedia Engineering 100 (2015 ) 24 32

DP Station Keeping Event Bulletin

SAFETY APPROACHES. The practical elimination approach of accident situations for water-cooled nuclear power reactors

Proposed Abstract for the 2011 Texas A&M Instrumentation Symposium for the Process Industries

Verification and validation of computer codes Exercise

A study on the relation between safety analysis process and system engineering process of train control system

Three Approaches to Safety Engineering. Civil Aviation Nuclear Power Defense

Workshop Information IAEA Workshop

A quantitative software testing method for hardware and software integrated systems in safety critical applications

Probabilistic safety assessment of fire hazards

Using LOPA for Other Applications

Purpose. Scope. Process flow OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT

Every things under control High-Integrity Pressure Protection System (HIPPS)

HEALTH AND SAFETY EXECUTIVE HM NUCLEAR INSTALLATIONS INSPECTORATE

Use of Computational Fluid Dynamic Fire Models to Evaluate Operator Habitability for Manual Actions in Fire Compartments

Reliability of Safety-Critical Systems Chapter 10. Common-Cause Failures - part 1

FUNDAMENTAL SAFETY OVERVIEW VOLUME 2: DESIGN AND SAFETY CHAPTER I: AUXILIARY SYSTEMS 2. VOLUME AND CHEMICAL CONTROL (RCV [CVCS])

Power Supply Facilities Failure (Units 3-4 Temporary M/C (A), etc.) March 22, 2013 Tokyo Electric Power Company

Implementing IEC Standards for Safety Instrumented Systems

Recent Research on Hazards PSA

Dynamic Context Quantification for Design Basis Accidents List Extension and Timely Severe Accident Management

10. SYSTEM ANALYSIS. The assessment consist of two elements: Safety Analysis Report and an independent Review of Safety Report.

The Best Use of Lockout/Tagout and Control Reliable Circuits

IEM on Severe Accident Management in the light of the accident at the Fukushima Daïchi NPP

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by

Understanding safety life cycles

PROCEDURE. April 20, TOP dated 11/1/88

APPENDIX B AN EXAMPLE RISK CALCULATION

Advanced Training for DP Operators

Training Fees 3,400 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Modification of the CNS Helium Injection Logic

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI

Impact on People. A minor injury with no permanent health damage

NE 405/505 Exam 2 Spring 2015

(C) Anton Setzer 2003 (except for pictures) A2. Hazard Analysis

C1960. Multi-recipe profile recorder/controller. Measurement made easy

Nuclear Safety. Module 3 DEFENSE IN DEPTH. Reacu03.ppt. Slide!

Questions & Answers About the Operate within Operate within IROLs Standard

LECTURE 3 MAINTENANCE DECISION MAKING STRATEGIES (RELIABILITY CENTERED MAINTENANCE)

Gas Network Craftsperson

Failure Modes, Effects and Diagnostic Analysis

Hazardous Waste Training Plan. Supersedes: 02/15/16 (Rev.02) Preparer: Owner: Approver: EHS Team Member EHS Team Member EHS Manager

IAEA SAFETY STANDARDS for protecting people and the environment

MAHB. INSPECTION Process Hazard Analysis

Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

IAEA Headquarters in Vienna, Austria 6 to 9 June 2017 Ref No.: CN-251. Ivica Bašić, Ivan Vrbanić APoSS d.o.o.

Section 1: Multiple Choice

-. 30ýv. Entergy ARKANSAS NUCLEAR ONE - UNIT I IMPROVED TECHNICAL SPECIFICATIONS SUBMITTAL. 05/01101 Supplement Volume 2 of 2. (Sections 3.7 and 3.

Transcription:

A c o n c e p t u a l c o m p a r a t i v e s t u d y o f F L E X s t r a t e g i e s t o c o p e w i t h e x t e n d e d S B O Hak Kyu Lim KEPCO International Nuclear Graduate School (KINGS) Probabilistic Safety Assessment and Management Conference, PSAM 14, 16-21 September 2018, Los Angeles, CA

Contents Introduction Using Small / Large Mobile GTG and Primary FLEX PUMP under APR1400 Extended SBO HEPs Calculation Using CBDTM and THERP for Small / Large Mobile GTG : HEPs and CDFs s

Introduction The Fukushima NPP accident in 2011 showed that SBO lasted for several days, the so-called extended SBO, and finally resulted in core damage. Since that accident, nuclear industries developed onsite and offsite equipment concept that provides an additional layer of defense in depth, called diverse and flexible mitigation strategies (FLEX). The implementation difficulty and effectiveness of various strategies developed for extended SBO may not be same. In this study, two strategies for recovery of electric power using mobile generators are examined. In Korea, KHNP introduced multi-barrier accident coping strategy (MACST). FLEX in this presentation means MACST. Slide # 3

Introduction This presentation will give overview on 1 2 3 To cope with APR1400 extended SBO using small / large mobile gas turbine generator (GTG) and primary FLEX pump. To calculate HEPs for small mobile GTG and large mobile GTG using Cause-Based Decision Tree (CBDT) and Technique for Human Error Rate Prediction (THERP) methods. of HEPs and CDFs Comparative study of FLEX strategies with small mobile GTG and large mobile GTG for APR1400 extended SBO, based on core damage frequency. Slide # 4

Extended SBO In the APR1400, extended SBO involves complete loss of ac electric power to the Class 1E and non-class 1E switchgear buses as well as the failure of a non-class 1E AAC source. Under the extended SBO condition, the only dc battery is available for the turbine driven auxiliary feedwater pump (TDAFWP) which supply water to the steam generator (SG). The capacity of dc battery is 8 hours and within this period plant safety needs to be recovered. Challenges under extended SBO 1 2 RCS heat removal RCS inventory control RCP seal integrity Slide # 5

Crediting FLEX A small mobile GTG could be connected to class 1E 480V ac bus to recover dc power for maintaining secondary heat removal when TDAFWP are unavailable after battery depletion. A large mobile GTG could be connected to one division of the 4.16 kv class 1E buses and the purpose is to recover ac power to maintain the secondary heat removal, feed and bleed operation and containment heat removal. One primary FLEX pump could be connected to direct vessel injection (DVI) via the safety injection (SI pump) line to inject borated water into the core to maintain RCS seal integrity. Large Mobile GTG Small Mobile GTG Figure: Connection point of Mobile Generators Figure : Connection Line of Primary FLEX Pump Slide # 6

Event Tree: Large GTG Figure: Event Tree for Extended SBO Using Large Mobile GTG and Primary FLEX Pump Mitigations ac power recovery RCS make up by Primary FLEX Pump Slide # 7

Success Criteria: Large GTG Table : Success criteria for Extended SBO using Large Mobile GTG and Primary FLEX Pump No Event Name Description 1 AAC AAC power source aligned to one Class 1E 4.16 kv ac bus. 2 SHR-TDP 1 of TDAFPs to associated SG and 1 MSADV or 1 MSSV on associated SG. 3 RCPSEAL RCP seal remains intact. 4 RAC-8HR Offsite power restored within 8 hours following an LOOP event. 5 GTG-AC 6 M-SHR AC power resorted within 8 hour following battery depletion which is aligned to 4.16 kv safety class 1 AC bus. AFW flow from AFWST after depletion of battery to associated SG and 1 MSADV or 1 MSSV on associated SG. 7 BLEED 2 of 4 POSRVs need to open. 8 FEED 1 of 4 SI pumps provides DVI injection. 9 EX-INJECTION Primary FLEX pump injects sufficient water to RCS inventory. 10 LHR 1 of CS (containment spray) pumps to associated CS nozzle or 1 of SC (shutdown coo ling) pumps to associated IRWST cooling. Slide # 8

Event Tree: Small GTG Figure: Simplified Event Tree for Extended SBO Using Small Mobile GTG and Primary FLEX Pump Mitigations dc power recovery RCS make up by primary FLEX pump Slide # 9

Success Criteria: Small GTG Table : Success criteria for Extended SBO Using Small Mobile GTG and Primary FLEX Pump No Event Name Description 1 AAC AAC DG power source aligned to one Class 1E 4.16 kv ac bus. 2 SHR-TDP 1 of TDAFPs to associated SG and 1 MSADV or 1 MSSV on associated SG. 3 RCP SEAL RCP Seal remains intact. 4 RAC-8HR Offsite power restored within 8 hours following an LOOP event. 5 GTG-DC dc power restored within 8 hrs following battery depletion. 6 EX-INJECTION Primary FLEX pump injects sufficient water to RCS inventory. 7 M-SHR AFW flow from AFWST after depletion of battery to associated SG and 1 MSA DV or 1 MSSV on associated SG. Slide # 10

FLEX Procedures Step No. Step 01 Step 02 Step 03 Step 04 Step 05 Step 06 Step 07 Step 08 Step 09 Step 10 Step 11 Step 11-a Step 12 Step 13 Step 14 Step 15 Step 16 Step 17 Step 18 Step 19 Table : Proposed FLEX deployment and installation procedures Description of Actions Diagnose the plant abnormal conditions and perform abnormal procedure guideline. Verify reactor trip occurrence and perform post trip actions. Check LOOP occurrence and perform emergency operating procedures If the operator fails to activate EDG, then declare an SBO Operator check AAC DG availability. If not available extended SBO is declared. Operator load sheds dc bus to preserve battery for vital instrumentation & control STA may instruct the operator to deploy and install FLEX equipment. FLEX equipment deployment route are reviewed. Deployment of mobile GTG in front of the auxiliary building. Operator checks status of the circuit. Connect powerline from mobile GTG to class 1E bus. Perform pre-operational check of large GTG. Energize mobile GTG. Check procedure if the vital bus is not restored Deployment and staging of primary FLEX pump. Connect primary FLEX pump to IRWST line Connect primary FLEX pump hose line to SI injection line via DVI. Perform pre-operational check for primary FLEX pump. Start primary FLEX pump. Check procedure if RCS inventory is not recovered. Slide # 24

Timing After 8 hours from the start of SBO, the mobile GTG is required unless offsite power recovery. Figure : Timing analysis for extended SBO T delay = 90 mins. Delay time includes diagnose the situation and begin the deployment of the mitigating strategies equipment, measured from the time of SBO. T cog T exe T w = 4 mins. Cognition time includes the time for operators to receive enough indication, evaluate the written instructions, and take any necessary preparatory decision to begin the deployment actions. = 150 mins. Execution time which includes FLEX equipment transportation, installation, start and repower the vital buses along with inclement weather. = 236 mins. Time available for recovery. Slide # 12

HEP Calculation Human failure events, namely operator fails to deploy and install a small GTG, a large GTG and primary FLEX pump under APR1400 extended SBO, were considered to calculate human error probabilities, HEPs. Cognitive portion of HEPs (P cog & P CR ) were calculated using CBDTM. Execution portion of HEPs (P exe & P ER ) were calculated using THERP. Figure : HFEs Probability Assessment P cog : Cognition HEP, P exe : Execution HEP, P CR : Cognitive Recovered HEP and P ER : Execution Recovered HEP Slide # 13

Cognition Error Probability Table: Cognitive HEP without recovery, P cog CBDTM Failure Mechanism Branch HEP p c a : Availability of information a 0.0 Notes: Operator can access to all information and required indication to operate a plant in the main control room (MCR). p c b : Failure of attention m 1.5 10-2 Notes: In general, within 2 hours from SBO initiation, the workload is assumed to be high. It may be necessary to monitor parameters and indicators continuously rather than one time check under SBO. It's is assumed that the indicator to be checked is always displayed on the front panel of the MCR because all of the controls in the modern control room are expected to be located in the front of the room. It is also predicted that operators concentrate on emergency operating guideline (EOG) and performs EOG-driven actions after the reactor trip. Thus, operators cannot wait for alarms to respond until the related parameter are mentioned in the EOG step. p c c : Misread/ miscommunicate data a 0.0 Notes: It is assumed that required indicator on the control board such as layout, demarcation, labelling, and others is always located easily. With the advanced digital I&C interface in the MCR, the indication is assumed to be "good". It also is predicted that formal communications will always be used when the specified value is transferred between operators. p c d : Information misleading b 3.0 10-3 Notes: All cues are not as stated for these HFEs and the EOG may provide contingency actions which are instructions on how to proceed. p c e : Skip a step in procedure g 6.0 10-3 Notes: It's assumed that it's always transparent for operators to proceed with the relevant instruction or stand-alone numbered step on the EOGs. The operator is required to use an additional procedure in addition to the EOG, so "multiple" branch is selected for these HFEs. For this operator action, related procedure step is "not graphically distinct". p c f : Misinterpret Instruction a 0.0 Notes: It is generally assumed that the wording of the procedures will be standard, clear. The step presents all information required to identify the actions directed and their objects. p c g : Misinterpret decision logic a 1.6 10-2 Notes: It is assumed that the operators are trained and practiced about specified scenario to perform. p c h : Deliberate Violation a 0.0 Notes: The operators are always assumed to believe in the adequacy of instruction presented. Initial P cog (without recovery) 4.0 10-2 Slide # 22

Recovery of Cognition Error Table: Cognitive recovered, P CR Shift Technical Adviser (STA) review is possible to recover failure of attention (p c b), information misleading (p c d) and misinterpret decision logic (p c g). In addition, the extra crew can review the steps in the procedures (p c e). For an initial estimate, a value of 0.1 was used. For complete independence, the factor is the HEP itself (p c e case). Branch Initial HEP Self- Review Extra Crew STA Review Shift Change ERF Review DF Multiply By Final Value p c a a 0.0 NC 0.5 NC X X 1.0 0.0 p c b m 1.5 10-2 0.1 NC 0.1 X X MD 0.16 2.4 10-3 p c c a 0.0 NC NC 0.1 X X 1.0 0.0 p c d b 3.0 10-3 NC 0.5 0.1 X X MD 0.15 4.5 10-4 p c e g 6.0 10-3 0.1 0.5 NC X X 0.5 3.0 10-3 p c f a 0.0 NC 0.5 0.1 X X 1.0 0.0 p c g a 1.6 10-2 NC 0.5 0.1 X X MD 0.16 2.6 10-3 p c h a 0.0 NC 0.1 0.1 X X 1.0 0.0 Sum of recovered p c a through p c h = Total of cognitive recovered P CR 8.45 10-3 For p c a, p c c, p c f, & p c h, we multiplied the initial HEPs by 1 as no recovery factors are identified. The dependency factor (DF) was increased from zero dependence (ZD) to moderate dependence (MD). This is because MD is usually assessed between the shift technical advisor (STA) and the operators for tasks in which the STA is expected to interact with them. For p c b, p c d and p c g decision trees, the conditional HEPs values for MD were calculated using failure equation Pr[F "N" F "N-1" ] = (1+6N)/7 which represent probabilities of failure on Task "N" given failure on the immediately preceding task, "N-1. Slide # 23

THERP Table : THERP Execution performance shaping factors Environment Lighting Portable Heat/humidity Radiation Atmosphere Hot/Humid Green Normal Special Requirements Tools Required Parts Clothing Required Available Complexity of response Execution Complex Equipment Accessibility (Cognitive) Equipment Accessibility (Execution) Main control room Auxiliary Building Accessible Accessible Figure : THERP stress decision tree The execution stress level was considered high and modifier 5 value was used. Slide # 25

Execution Error Probability Table : P exe without recovery for small mobile GTG Table : Execution recovered, P ER for small mobile GTG Step No. 09 10 Procedure THERP Error Action type Table Item Deployment of small GTG in front of auxiliary building. Operator checks status of circuit. HEP Stress factor EOM 20-7b 1 4.17 10-4 High EOC 20-13 1 1.3 10-3 High EOM 20-7 2 3.75 10-3 High EOC 20-10 6 1.3 10-3 High Total Step HEP 8.59 10-3 2.53 10-2 Critical Step No. 09 10 Recovery Step No. 13 13 Action Deployment of small GTG in front of auxiliary building. Check procedure if vital bus is not restored Operator checks status of circuit. Check procedure if vital bus is not restored HEP (Critical) HEP (Rec) DF. Cond. HEP (Recovery) Total for Step 8.59 10-3 1.68 10-5 1.28 10-2 MD 1.96 10-3 2.53 10-2 4.95 10-5 1.28 10-2 MD 1.96 10-3 11 Connect powerline to 480V for small GTG. EOM 20-7b 2 1.25 10-3 High EOC 20-12 13 1.30 10-2 High 7.13 10-2 11 Connect powerline to 480V for small GTG. 7.13 10-2 1.40 10-4 12 Energize mobile small GTG. EOM 20-7b 2 1.25 10-3 High EOC 20-12 11 6.3 10-3 High 3.78 10-2 12 13 Check procedure if vital bus is not restored Energize mobile small GTG. 1.28 10-2 MD 1.96 10-3 3.78 10-2 7.40 10-5 13 Check procedure if vital bus is not restored EOM 20-7b 2 1.25 10-3 High EOC 20-11 2 1.3 10-3 High 1.28 10-2 13 Check procedure if vital bus is not restored 1.28 10-2 MD 1.96 10-3 Total Unrecovered, P exe 1.43 10-1 Total Recovered, P ER 2.80 10-4 The calculated P exe without recovery and execution recovered, P ER for small mobile GTG values are 1.43 10-1 and 2.8 10-4 respectively. Slide # 26

Execution Error Probability Table : P exe without recovery for large mobile GTG Table : Execution recovered, P ER for large mobile GTG Step No. Procedure THERP Error Action type Table Item HEP Stress factor Total Step HEP Critical Step No. Recovery Step No. Action HEP (Critical) HEP (Rec) DF Cond. HEP (Recovery) Total For Step Accident Sequence 09 10 11 11-a 12 Deployment of large GTG in front of auxiliary building Operator checks status of circuit. Connect powerline to class 1E 4.16kV for large GTG. Perform preoperational checking of large GTG. Energize mobile large GTG. EOM 20-7b 1 4.17 10-4 High EOC 20-13 1 1.3 10-3 High EOM 20-7 2 3.75 10-3 High EOC 20-10 6 1.3 10-3 High EOM 20-7b 2 1.25 10-3 High EOC 20-12 13 1.30 10-2 High EOM 20-7b 1 4.17 10-4 High EOC 20-12 11 6.30 10-3 High EOM 20-7b 2 1.25 10-3 High EOC 20-12 11 6.3 10-3 High 8.59 10-3 2.53 10-2 7.13 10-2 3.36 10-2 3.78 10-2 09 10 11 11-a 12 13 13 13 13 Deployment of large GTG in front of auxiliary building Check procedure if vital bus is not restored Operator checks status of circuit. Check procedure if vital bus is not restored Connect powerline to class 1E 4.16kV for large GTG. Check procedure if vital bus is not restored Perform pre-operational checking of large GTG. Check procedure if vital bus is not restored Energize mobile large GTG. 8.59 10-3 1.68 10-5 1.28 10-2 MD 1.96 10-3 2.53 10-2 4.95 10-5 1.28 10-2 MD 1.96 10-3 7.13 10-2 1.40 10-4 1.28 10-2 MD 1.96 10-3 3.36 10-2 6.59 10-5 1.28 10-2 MD 1.96 10-3 3.78 10-2 7.40 10-5 13 Check procedure if vital bus is not restored EOM 20-7b 2 1.25 10-3 High EOC 20-11 2 1.3 10-3 High 1.28 10-2 13 Check procedure if vital bus is not restored 1.28 10-2 MD 1.96 10-3 Total Unrecovered, P exe 1.76 10-1 Total Recovered, P ER 3.46 10-4 The calculated P exe without recovery and execution recovered, P ER for large mobile GTG values are 1.76 10-1 and 3.46 10-4 respectively. Slide # 27

of HEPs Table : of HEP Results HEP Results Summary P cog P exe Total HEP Small Mobile GTG Without Recovery 4.0 10-2 1.43 10-1 8.73 10-3 With Recovery 8.45 10-3 2.80 10-4 Large Mobile GTG Without Recovery 4.0 10-2 1.76 10-1 8.80 10-3 With Recovery 8.45 10-3 3.46 10-4 NEI 16-06 Guide HEP Results Summary FLEX Generator Without Recovery 2.0 10-3 1.18 10-1 5.35 10-3 With Recovery 2.9 10-4 5.06 10-3 Slide # 31

(Assumed) BE Data There is no failure data available for portable equipment while there are sources of generic failure rates for permanently-installed equipment at NPPs. In this study, failure probability of diesel generator and combustion turbine generator are used as failure probability of a small mobile GTG and a large mobile GTG, respectively. Table : Basic Event Data Considered for FLEX Strategies Basic Event Description Probability Data Source EIEPL-S-PP01 Portable pump fails to load run 9.80 10-4 Component Reliability Data Sheets 2015 Update (Table 2-10) EIEPM-S-PP01 Portable pump unavailable due to maintenance 7.51 10-3 NUREG/CR- 6928 (Table 6-1) EIEPR-S-PP01 Portable pump fails to run 1.98 10-3 Component Reliability Data Sheets 2015 Update (Table 2-10) EIEPS-S-PP01 Portable pump fails to start 2.17 10-3 Component Reliability Data Sheets 2015 Update (Table 2-10) EIMP-PP01--HOSE Failure to Portable pump hose 5.89 10-6 SAND 2006-7723 GTTGL-L-GTG Large GTG fail to run for 1hr 5.79 10-3 Component Reliability Data Sheets 2015 Update (Table 3.-8) GTTGM-L-GTG Large GTG unavailable due to maintenance 5.00 10-2 NUREG/CR-6928 (Table 6-1) GTTGR-L-GTG Large GTG fail to run 8.49 10-3 Component Reliability Data Sheets 2015 Update (Table 3-8) GTTGS-L-GTG Large GTG fail to start 5.12 10-2 Component Reliability Data Sheets 2015 Update (Table 3-8) GTBSY-S-SW01 AC bus faults switchgear of GTG 9.55 10-7 Component Reliability Data Sheets 2015 Update (Table 5-19) GTBSY-P-SW01 DC bus faults switchgear of GTG 2.17 10-7 Component Reliability Data Sheets 2015 Update (Table 5-19) GT-GTG- REEL Failure of large GTG reel cable 1.20 10-6 NUREG/CR-3263 GTOPH-S-GTG Operators fails to provide 1E class DC bus 5.35 10-3 NEI-16-06 GTTGL-S-GTG Small GTG fails to run for 1 hr 3.72 10-3 NUREG/CR- 6928 GTTGS-S-GTG Small GTG fails to start 2.88 10-3 NUREG/CR- 6928 GTTGM-S-GTG Small GTG unavailable due to maintenance 1.34 10-3 NUREG/CR- 6928 GTTGR-S-GTG Small GTG fails to run 1.52 10-3 NUREG/CR- 6928 GT-SGTG-REEL Failure of Small GTG cable reel 4.00 10-8 NUREG/CR- 3263 Slide # 29

of CDFs Table : CDF Contribution using large mobile GTG Table : CDF Contribution using small mobile GTG Sequence Number ESBO- 05 ESBO- 06 ESBO- 11 ESBO- 12 ESBO- 25 ESBO- 26 Sequence (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal intact)(success of recovery offsite power within 8 hours)(failure to maintain secondary heat removal)(safety dep. For bleed OK)(safety injection for feed fails) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal intact)(success of recovery offsite power within 8 hours) (success of mobile GTG for ac power recovery)(failure to maintain secondary heat removal)(safety dep. For bleed fails) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal intact)(failure of recovery offsite power within 8 hours)(failure to maintain secondary heat removal)(safety dep. For bleed fails) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal intact)(failure of recovery offsite power within 8 hours)(failure of mobile GTG for acpower recovery) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(failure of RCP Seal )(failure of recovery offsite power within 8 hours)(failure of mobile GTG for acpower recovery) CDF Contribution (events/year) 6.48 10-14 1.03 10-10 1.49 10-13 3.72 10-8 9.29 10-11 (SBO)(failure of AAC)(failure to delivery of feedwater using turbine driven pumps) 6.93 10-7 Total 7.30 10-7 Sequence Number ESBO- 06 ESBO- 09 ESBO- 12 ESBO- 13 ESBO- 14 Sequence (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal intact)(failure of recovery offsite power within 8 hours)(failure of mobile GTG for dc power recovery) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal leakage)(success of recovery offsite power within 8 hours)(failure of primary injection of RCS inventory by primary FLEX pump) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal leakage)(failure of recovery offsite power within 8 hours)(success of mobile GTG for dc power recovery)(failure of primary injection of RCS inventory by primary FLEX pump) (SBO)(failure of AAC)(successful delivery of feedwater using turbine driven pumps)(rcp Seal leakage)(failure of recovery offsite power within 8 hours)(failure of mobile GTG for dc power recovery) CDF Contribution (events/year) 7.00 10-9 7.52 10-9 1.11 10-11 1.74 10-11 (SBO)(failure of AAC)(failure of delivery of feedwater using turbine driven pumps 6.93 10-7 Total 7.08 10-7 Based on these comparative study results, the CDF of an extended SBO with a small mobile GTG, 7.08 10-7 /year is almost same as the CDF of an extended SBO with a large mobile GTG, 7.30 10-7 /year. The frequency sequences of ESBO-12 of large GTG is 5 times higher than frequency sequences of ESBO-06 of small GTG. Slide # 30

s At the present time, there are deficient data and procedures of FLEX that may affect the HEP calculation. Due to lack of information as well as experience on FLEX equipment, only step 11-a for large GTG is considered differently from small GTG case. It makes small difference between HEPs as well as CDFs. It could not be realistic to suggest now which portable GTG is more useful. However, the error probabilities of step 9 to 13 for large GTG and small GTG would be different because the difficulties of deployment and operation of mobile GTGs are not same. It is obligatory to develop precise procedures if we want to get more accurate HEP results. Slide # 32

Even though there is no PRA, the decrease of CDF when FLEX strategy is implemented should be obvious. Because of lack of information of FLEX strategy, currently, it is not effective to perform PRA of NPP with FLEX strategy, for showing how much decrease of CDF could be achieved after FLEX strategy implementation. To develop optimized FLEX strategy implementation, such as optimization the use of portable equipment under beyond design basis accidents, the detailed information and experiences related to FLEX strategy are required. On the other side, there may also require to address any inadvertent consequences due to the implementation of FLEX equipment like impact to the existing plant design bases, physical & cyber security, etc. Slide # 23

References [1] NEI 12-06, Rev.4, Diverse and Flexible Coping Strategies (FLEX) Implementation Guide, 2016 [2] NEI 16-06, Rev.0, Crediting Mitigating Strategies in Risk-Informed Decision Making, 2016 [3] M.G. Shahinoor Islam, Lim Hak-kyu, Comparative Study of FLEX Strategies for Extended SBO Using PRA, KINGS, 2017 [4] KINGS/PR-SEP02-2018-06, HEPs Calculation for FLEX Strategies in Response to APR1400 Extended SBO, KINGS, 2018 [5] APR1400 DCD Tier 2, Chapter 8, Electric Power, 2014 [6]U.S.NRC NUREG/CR-1278, Handbook of with Emphasis on Nuclear Power Plant Applications, 1983 [7] EPRI TR-100259, An Approach to the of Operator Action in Probabilistic Risk Assessment, EPRI, 1992 [8] Prof. Chang Choong-koo, On-site FLEX Equipment, KEPCO International Nuclear Graduate School, 2018 [9] The EPRI HRA Calculator Software Manual, Version 5.0 Demo, 2013 [10] Thomas Zachariah, Using FLEX Equipment and Risk-Informed Decision Making to Maximize Safety, Regulatory Information Conference, 2017 Slide # 24