Guide to Safety at Sports Grounds. Worked Example A: Football/Rugby

Similar documents
Guide to Safety at Sports Grounds. Worked Example C: Racecourse

The NorTherN IrelaNd GuIde To SafeTy at SporTS GrouNdS

MANAGEMENT OF PERSISTENT STANDING AT THE CARDIFF CITY STADIUM UPDATE REPORT FIVE

Sports Grounds Safety Authority (SGSA) Guidance regarding the handling of pyrotechnics (flares, smoke bombs and fireworks) in sports grounds

NATIONAL GROUND GRADING - CATEGORY H

NATIONAL GROUND GRADING - CATEGORY G

Chapter 11 Pre-dimensioning and circulation

MANAGEMENT OF PERSISTENT STANDING AT THE CARDIFF CITY STADIUM UPDATE REPORT SIX

Crowd Management Measures. FA Good Practice Guide for Football Clubs

Ground Grading Criteria & Summary

ASSOCIATION OF RUNNING CLUBS EVENT PLANNING AND RISK ASSESSMENT

NATIONAL GROUND GRADING - CATEGORY F

Notts Varsity Event Venue information- an accessible guide! Motorpoint Arena (ice hockey and basketball)

Cove Rangers Football Club. Supporter and Customer Charter

NOTTS COUNTY FC VISITING SUPPORTER GUIDE

CHAPTER 5: GENERAL SITE AND BUILDING ELEMENTS

The FA Cup, The FA Trophy, The FA Vase and The FA Youth Cup Competitions

England v West Indies Royal London ODI. Tuesday 19 September 2017

RCA GUIDE TO SAFETY AT RACECOURSES


Designing Pedestrian Facilities for Accessibility. Module 3 Curb Ramps & Blended Transitions

FINAL EXPRESS TERMS FOR PROPOSED BUILDING STANDARDS OF THE CALIFORNIA DEPARTMENT OF PUBLIC HELATH

JOINT GROUND CRITERIA. Version 1.13 June 2016

2017/18 Visiting Supporters Guide

Notts County FC SLO welcome pack

MAIDSTONE UNITED ADVERTISING AND SPONSORSHIP: 2017/18 SEASON

City of Los Angeles Department of Building & Safety Disabled Access Section Supplemental Plan Review Checklist No. 8 RECREATION FACILITIES

LONDON BOROUGH OF LEWISHAM. Minutes of The Millwall Football Club Safety Advisory Group The Den, Zampa road, London SE16 Thursday 25th February 2016

Access Statement for Glamorgan County Cricket Club (Domestic Matches)

MANAGEMENT OF PERSISTENT STANDING AT THE CARDIFF CITY STADIUM

ADA Access Standards for Swimming Pools, Wading Pools, and Spas

Netball. Developing the Right Sports Hall. Sports Data Sheets

GUIDE TO SAFETY AT RACECOURSES

2014 FACILITIES REQUIREMENTS

Travelling Supporters Advice

Club Roles and Responsibilities Version 2.1 July 2017

Chapter 5. General Site and Building Elements

AlburyCity Events Case Study A-League 2014

Small. Regulation Reference: (see page 23 for link to the regulation)

Travelling Supporters Advice

BICETSER RUFC HEALTH & SAFETY POLICY

Canadian Championships in Men s & Women s Artistic Gymnastics

higher education exhibition 2018 Wednesday 13 June 09:30 14:30

How to plan an event. Step 1: First things first. Step 2: How to make it all happen?

BMA INFORMATION BULLETIN No. 96

2018 SIX NATIONS CHAMPIONSHIP DEBENTURE GUIDE WRU.WALES/TICKETS

Guidelines for Hosting World Para Alpine Skiing International Classification

Developing the Right Sports Hall

Driveway Design Criteria

P.O. Box 1749 Halifax, Nova Scotia B3J 3A5 Canada Item No. 8.1(i) Transportation Standing Committee of Council November 23, 2017

PONTELAND RUGBY FOOTBALL CLUB

Specific training needs should be identified and met at an early stage depending on the type of event. #

Speed Limit Policy Isle of Wight Council

Elite Canada in Men s & Women s Artistic Gymnastics

transport consultancy Stadia & Venues

CHAPTER FIFTEEN Mini Motocross & Junior Motocross (Off Road)

Swim Ireland Risk Assessment Guidance Document for Clubs and Regions

JUNE 2018 NEWSLETTER NEWCASTLE UNITED DISABILITY NEWS NEWSLETTER FOR NEWCASTLE UNITED S DISABLED SUPPORTERS AROUND THE WORLD

IMO. 4 February 1999 Original: ENGLISH RECOMMENDATION ON HELICOPTER LANDING AREAS ON RO-RO PASSENGER SHIPS

AFC WIMBLEDON FIRST TIME VISITOR GUIDE AFC WIMBLEDON FIRST TIME VISITOR GUIDE SEASON 2018/ 19

Safety Risk Assessment Working at Height: Mobile Tower Scaffold

NON-PERSONAL HEARING THE FOOTBALL ASSOCIATION. and ASTON VILLA FC THE DECISION AND REASONS OF THE FA REGULATORY COMMISSION

CHAPTER FIFTEEN Mini Motocross & Junior Motocross (Off Road)

Global EHS Powered Industrial Truck and Pedestrian Safety

dpd Seattle Permits Tip Getting a Grip on Handrails PURPOSE OF HANDRAILS

Entry Treatments. Traffic Advisory Leaflet 2/94 August Introduction. Design. Vertical Deflections. Locations

Design and Installation of Low Level Cycle Signals

VISITING VICARAGE ROAD VISITING SUPPORTERS GUIDE 2018/19

Personal Emergency Evacuation Plan Questionnaire for Disabled Staff

Global Lift ADA Compliance

Objective: To exhibit best practices in customer service as it relates to key management.

Aluminum Sheeting Guide (ASG)

Elite Canada in Men s & Women s Artistic Gymnastics

UEFA Stadium Infrastructure Regulations

Lancashire Lightning v Yorkshire Vikings Vitality Blast Friday 20 July Gates open 4:30pm Start time 6:30pm

Update to DOTD Roundabout Design Policy

HEALTH AND SAFETY POLICY

Lord s Tours Terms and Conditions - Private or Group Bookings

PUBLIC SPA CHECKLIST. Planning and Building Department City of Mississauga 300 City Centre Drive, 3th Floor Mississauga ON L5B 3C1

Race Management Policies for World Sailing Events Fleet Racing Updated for Oceania & Australian Laser Regattas

VISUAL AIDS FOR DENOTING OBSTACLES

VISITING SUPPORTERS ADVICE Chelsea v Leicester City 22 nd December 2018 Kick Off: 15:00 CHELSEA FOOTBALL CLUB

POOL AND SPA REPLASTERING AND/OR REMODELING REQUIREMENTS

CHAPTER FIFTEEN 15 MINI MOTOCROSS & JUNIOR MOTOCROSS

What to consider when designing seating in natatoriums. BY SCOTT W. HESTER

Redevelopment Principles & Sports Proposals Conflict With Local Needs

CROSS COURSE INSTRUCTION DOCUMENT

The Field of Play. Only the lines indicated in Law 1 are to be marked on the field of play.

HOME FANS GUIDE 2017/18

Circular Turning Space. 8 Significant Changes to the ICC A

NATIONAL GROUND GRADING - CATEGORY A

Saskatchewan Health S A WHIRLPOOL DESIGN/OPERATIONAL T C H E W STANDARDS. Updated 02/00

ECB WOMEN S CRICKET SUPER LEAGUE ( WCSL ) HOST MINIMUM QUALITY STANDARDS

DISTRIBUTION: Electronic Recipients List TRANSMITTAL LETTER NO. (17-01) MINNESOTA DEPARTMENT OF TRANSPORTATION. MANUAL: Road Design English Manual

The course suits resolute horses and runners on the loop need to be agile to take the sharp turn.

NOTTS COUNTY FC FIRST TIME FAN GUIDE

Guidance for Officials. Officiating Youth Football (Mini Soccer, 9 v 9 & 11 v 11)

2018 FHSAA Competitive Cheerleading Championships

MOTOCROSS CIRCUIT SAFETY GUIDELINES

BARRIER TRIALS REGULATIONS 2018/2019 SEASON. BARRIER TRIALS - Sha Tin, Happy Valley and Conghua Training Centre ( CTC )

Transcription:

Guide to Safety at Sports Grounds 1

Introduction As has been long established, the principal objective of the is to provide guidance on the calculation of how many people can be safely accommodated within a ground while it is hosting an event, sporting or otherwise. Such a calculation is the most important step towards the achievement of reasonable safety. This Worked Example shows the capacity calculations for a typical ground designed to host sports such as football or rugby and should be read in conjunction with Chapter 2 and Figures 1 and 2 of the Guide. It is recognised that capacity calculations can be presented in different formats, for example as spreadsheets. However all the steps identified here must nevertheless be followed. For further guidance on capacity calculations may be found on the SGSA website in the form of Worked Examples for a cricket ground (Worked Example B) and a racecourse (Worked Example C), together with Annex A on the assessment of the (P) factors and Annex B on the assessment of (S) factors. Both the and this Worked Example are compiled and published by the Sports Grounds Safety Authority, Fleetbank House, 2-6 Salisbury Square, London EC4Y 8JX www.sgsa.org.uk Sports Grounds Safety Authority 2018 All rights reserved 2

WEA.1 Introduction This example shows a football or rugby ground offering reserved seating on both sides of the pitch, and terraces for standing at each end. All the spectator accommodation is covered. The circulation system is restricted so that spectators can enter only the stand or terrace for which they have purchased tickets. The calculations that follow are based upon the stages outlined in Chapter Two of the. The step numbers cited correspond with the steps set out in Figure 1 (seated accommodation) and Figure 2 (standing accommodation). North Terrace West Stand East Stand South Terrace E = exit gate T = turnstile or ticket check point 3

WEA.2 West Stand a. Step 1 calculate the number of usable seats This step is explained in Sections 2.6, 12.15 and Figure 1 of the Guide. The West Stand contains two sections with the following numbers of seats: Main tier: 1536 + 8 wheelchair spaces + 8 helpers = 1552 Executive: 288 + 4 wheelchair spaces + 4 helpers = 296 There are no damaged seats and none with restricted views. There are no rows with seats in excess of the recommended number between radial gangways. Therefore the number of usable seats in the West Stand is: 1848 b. Step 2 calculate the holding capacity This step is explained in Section 2.6 and Figure 1 of the Guide. The West Stand is well maintained and in good order. All seats are covered and offer reasonable sightlines. No unreserved seats are on sale. The management have assessed both the (P) and (S) factors for the stand as 1.0. Therefore the holding capacity of the West Stand is: 1848 x 1.0 = 1848 For more guidance on (P) and (S) factors see online Annexes A and B. c. Step 3 calculate the entry capacity This step is explained in Sections 2.11, 7.5 and Figure 1 of the Guide. From observation and experience it is apparent that all four automated turnstiles serving the Main Tier and the two ticket check points serving the Executive area can process the recommended maximum rate of entry, that is, 660 persons per entry point per hour. Therefore the entry capacity of the West Stand is: 660 x 6 = 3960 d. Step 4 calculate the exit capacity This step is explained in Sections 10.10 10.11 and Figures 1 and 13 of the Guide. For calculation purposes, the egress time under normal conditions from the seated accommodation to the start of the exit system referred to in the Guide as the Zone 2 travel time is set at a maximum of eight minutes. (As explained in Figure 13, under normal conditions there is no need to measure how long it might take spectators to negotiate the entire exit route.) Main tier: the start of the exit system consists of four vomitories at ground level, each measuring 1.5 wide. These vomitories lead through the concourse to four final exit gates, each of which measure 3m wide. For the purposes of calculation, the narrower width of the vomitory (1.5m) should be used, rather than that of the final exit gates (3m). All spectators other than those in the front row must step down the radial gangways in order to exit via the vomitories. On a stepped surface, the maximum flow rate used for calculation is 66 persons per metre width per minute. Therefore the exit capacity of the West Stand s main tier is: (4 x 1.5) x 8 x 66 = 3168 4

Executive area: normal egress is via four exits at the rear of the executive seating area, each 1.2m wide, leading into a hospitality lounge and from there down stairs to two exit gates, each measuring 3.0m wide. These factors, combined with observation of crowd flow and spectator behaviour, lead the ground management to apply the maximum flow rate 66 people per metre width per minute for the purposes of calculation. The Zone 2 travel time for the Executive area (that is the time set for spectators to reach the start of the exit system under normal conditions) is eight minutes. (As explained in Figure 13, under normal conditions there is no need to measure how long it might take spectators to negotiate the entire exit route.) Therefore the exit capacity of the Executive area is: (4 x 1.2) x 8 x 66 = 2534 Therefore the total exit capacity of the West Stand is: 3168 + 2534 = 5702 e. Step 5 calculate the emergency exit capacity This step is explained in Sections 2.13, 10.12 10.18, 15.8 15.12 and Figures 1 and 13 in the Guide. Main tier: all emergency exit routes pass through concourse areas with a low risk of fire. The condition and the management of the emergency exit routes are considered to be good, and it is not considered necessary to discount one emergency exit for the purpose of calculation. Therefore a maximum emergency egress time of eight minutes the same as the exit time under normal conditions is considered to be applicable. Therefore the emergency exit capacity for the Main tier = 3168 Executive area: all emergency exit routes pass through areas, parts of which are high risk, others of which are medium risk. As stated in Section 15.12, the emergency egress time for all parts of the route should therefore be set as if the whole route were subject to high risk, that is, a maximum two and a half minutes. It is not considered necessary to discount one emergency exit for the purpose of calculation. The condition and the management of the exit routes are also considered to be good. Therefore the emergency exit capacity of the executive area is: (4 x 1.2) x 2.5 x 66 = 792 Therefore the total emergency exit capacity of the West Stand is: 3168 + 792 = 3960 As stated in Section 2.13, the emergency exit capacity must include not only spectators but all people present. In this stand, however, the emergency exit capacity comfortably exceeds the total number of spectators, staff and other personnel likely to be on duty in the stand, and therefore the emergency exit capacity does not need to be re-calculated. f. Step 6 calculate the final capacity of the West Stand This step is explained in Sections 2.11 and Figure 1 of the Guide. The final capacity of the West Stand is lowest figure of those calculated, as follows: Step 2: holding capacity: 1848 Step 3: entry capacity: 3960 Step 4: exit capacity: 5702 Step 5: emergency exit capacity: 3960 Step 6: final capacity of West Stand = 1848 5

WEA.3 East Stand a. Step 1 calculate the number of usable seats This step is explained in Sections 2.6, 12.15 and Figure 1 of the Guide. The East Stand consists of one tier of 1536 seats. No seats are damaged and none has restricted views. There are no rows with seats in excess of the recommended number between radial gangways. There are spaces for 4 wheelchair users and 4 seats for helpers. Therefore the number of usable seats in the East Stand is: 1536 + 8 = 1544 b. Step 2 calculate the holding capacity This step is explained in Section 2.6 and Figure 1 of the Guide. The East stand is well maintained and in good order. All seats are covered and offer reasonable sightlines. There are no unreserved seats on sale. The management have assessed both the (P) and (S) factors for the stand as 1.0. Therefore the holding capacity is: 1544 x 1.0 = 1544 c. Step 3 calculate the entry capacity This step is explained in Sections 2.11, 7.5 and Figure 1 of the Guide. From observation and experience it is apparent that all four of the East Stand s turnstiles in the south east corner can process the recommended rate of entry, that is, 660 persons per entry point per hour. Therefore the entry capacity of the East Stand is: 660 x 4 = 2640 d. Step 4 calculate the exit capacity This step is explained in Sections 10.10 10.11 and Figures 1 and 13 of the Guide. For calculation purposes, the egress time under normal conditions from the seated accommodation to the start of the exit system referred to in the Guide as the Zone 2 travel time is set at a maximum of eight minutes. (As explained in Figure 13, under normal conditions there is no need to measure how long it might take spectators to negotiate the entire exit route.) At the front of the East Stand is a 3m wide lateral gangway. This leads to two final exit gates at the south end of the stand, each also measuring 3m in width. The exit route is on a level surface and with few changes of direction. On a level surface, the maximum flow rate used for calculation is 82 persons per metre width per minute. Therefore the exit capacity of the East Stand is: (2 x 3) x 8 x 82 = 3936 e. Step 5 calculate the emergency exit capacity This step is explained in Sections 2.13, 10.12 10.18, 15.8 15.12 and Figures 1 and 13 in the Guide. All exit routes pass through areas with a low risk of fire. It is not considered necessary to discount one emergency exit for the purpose of calculation. The condition and the management of the exit routes are also both considered to be good. Therefore a maximum emergency egress time of eight minutes the same as the exit time under normal conditions is considered to be applicable. Therefore the emergency exit capacity of the East Stand = 3936 6

As stated in Section 2.13, the emergency exit capacity of the stand must include not only spectators but all people present. In this stand, however, the emergency exit capacity comfortably exceeds the total number of spectators, staff and other personnel likely to be on duty in the stand, and therefore the emergency exit capacity does not need to be re-calculated. f. Step 6 calculate the final capacity of the East Stand This step is explained in Section 2.11 and Figure 1 of the Guide. The final capacity of the East Stand is lowest figure of those calculated: Step 2: holding capacity: 1544 Step 3: entry capacity: 2640 Step 4: exit capacity: 3936 Step 5: emergency exit capacity: 3936 Step 6: final capacity of East Stand = 1544 WEA.4 North Terrace a. Step 1 calculate the available viewing area This step is explained in Section 2.8 and Figures 2 and 15 in the Guide. The North Terrace has two rows of crush barriers, each configured continuously between radial gangways measuring 1.2m wide. The crush barriers at each end of the front row measure 5.0m in length. The four other crush barriers in the front row each measure 14.5m in length. All crush barriers have been tested to 3.0 kn/m. The risers and goings of the terrace steps measure 180mm and 380mm respectively, forming an angle of 25 degrees. Between the first row of crush barriers and the pitch perimeter barrier is a lateral gangway, 2.4m in depth. There are no restricted views. First row of crush barriers: the depth of terracing between the first row of crush barriers and the second (or rearmost) row is 1.9m. However, as stated in Figure 15, for barriers of 3.0 kn/m on a terrace with a slope of 25 degrees the maximum distance between barriers should be 1.8m. For the purpose of calculation therefore the available viewing area for this row of barriers is 1.8m rather than 1.9m. Therefore the available viewing area for the terracing behind the first row of crush barriers is: (2 x 5) + (4 x 14.5) = 68.0 x 1.8 = 122.4 square metres Second row of crush barriers: the depth of terracing behind the second row of barriers (at the rear) is 3.1m. Again, however, as stated in Figure 15, the maximum distance for calculation purposes should be 1.8m. Therefore the available viewing area for the terracing behind the second row of crush barriers is also: (2 x 5) + (4 x 14.5) = 68.0 x 1.8 = 122.4 square metres Therefore the total available viewing area for the North Terrace = 244.8 square metres 7

b. Step 2 calculate the appropriate density This step is explained in Section 2.9 and Figure 2 in the Guide. The North Terrace is fully covered, in good condition and there no sightline problems. The management considers an appropriate density for the terrace is 4.7 spectators per square metre and has assessed both the (P) and (S) factors for this area of the ground as 1.0. Therefore the appropriate density for the North Terrace is: 4.7 x 1.0 = 4.7 spectators per square metre. c. Step 3 calculate the holding capacity This step is explained in Section 2.10 and Figure 2 in the Guide. The holding capacity of the North Terrace is: 244.8 x 4.7 = 1150 d. Step 4 calculate the entry capacity This step is explained in Sections 2.11, 7.5 and Figure 2 in the Guide. From observation and experience it is apparent that all three of the turnstiles serving the North Terrace can process the recommended maximum rate of entry, that is, 660 persons per entry point per hour. Therefore the entry capacity for the North Terrace is: 660 x 3 = 1980 e. Step 5 calculate the exit capacity This step is explained in Section 10.9 10.11 and Figures 2 and 13 in the Guide. The North Terrace has two exit points, each 2.4m wide, at each end of the front lateral gangway, leading to one final exit gate 4.8m wide. The exit routes are on a level surface and with few changes of direction. The Zone 2 travel time for the terrace under normal conditions is eight minutes. (As explained in Figure 13, under normal conditions there is no need to measure how long it might take spectators to negotiate the entire exit route.) Combined with observation of crowd flow and spectator behaviour, the ground management has decided to apply the maximum flow rate for a level surface of 82 people per metre width per minute for the purposes of calculation. Therefore the North Terrace s exit capacity is: (2.4 x 2) x 8 x 82 = 3148 f. Step 6 calculate the emergency exit capacity This step is explained in Sections 2.13, 10.12 10.18, 15.9 and Figures 2 and 13 in the Guide. The emergency exit routes for the terrace pass through areas with a low risk of fire. It is not considered necessary to discount one emergency exit for the purpose of calculation. The condition and the management of the exit routes are considered to be good. Therefore a maximum emergency exit time of eight minutes the same as the normal exit time is considered to be applicable. Therefore the emergency exit capacity of the North Terrace = 3148 As stated in Section 2.13 the emergency exit capacity of the terrace must include not only spectators but all people present. In this terrace, however, the emergency exit capacity comfortably exceeds the number of spectators, staff and personnel likely to be on duty, and therefore the emergency exit capacity does not need to be re-calculated. 8

g. Step 7 calculate the final capacity of the North Terrace This step is explained in Section 2.11 and Figure 2 in the Guide. The final capacity of the North Terrace is lowest figure of those calculated: Step 3: holding capacity: 1150 Step 4: entry capacity: 1980 Step 5: exit capacity: 3148 Step 6: emergency exit capacity: 3148 Step 7: final capacity of North Terrace = 1150 WEA.6 South Terrace a. Step 1 calculate the available viewing area This step is explained in Section 2.8 and Figures 2 and 15 in the Guide. The South Terrace has two rows of crush barriers, both configured continuously between gangways measuring 1.2m wide. The crush barriers in both rows are in three different lengths: 2 x 6.3m, 2 x 11.7m, and in the centre, 1 x 24m. Between the first row of crush barriers and the pitch is a lateral gangway, 1.2m in depth, for circulation, fronted by a perimeter barrier. The crush barriers have all been tested to 5.0 kn/m. The risers and goings of the terrace steps measure 95mm and 280mm respectively, forming an angle of 20 degrees. There are no restricted views. First row of crush barriers: the depth of terracing between the first row of crush barriers and second row is 3.4m, exactly as required in Figure 15 for barriers of 5.0 kn/m on a terrace with a slope of 20 degrees. For the purpose of calculation therefore the available viewing area for this row of barriers is: (2 x 6.3) + (2 x 11.7) + (1 x 24) = 60 x 3.4 = 204 square metres Second row of crush barriers: the dimensions of the terracing behind the second row of crush barriers is the same as for the first row: 204 square metres Therefore the total available viewing area for the South Terrace = 408 square metres b. Step 2 calculate the appropriate density This step is explained in Section 2.9 and Figure 2 in the Guide. The South terrace is fully covered, in good condition and there no sightline problems. The management considers an appropriate density for the terrace is 4.7 spectators per square metre, and has assessed both the (P) and (S) factors for this area as 1.0. Therefore the appropriate density for the South Terrace is: 4.7 x 1.0 = 4.7 spectators per square metre. c. Step 3 calculate the holding capacity This step is explained in Section 2.10 and Figure 2 in the Guide. The holding capacity of the South Terrace is: 408 x 4.7 = 1917 9

d. Step 4 calculate the entry capacity This step is explained in Sections 2.11, 7.5 and Figure 2 in the Guide. From observation and experience it is apparent that both turnstiles serving the South Terrace can deliver the recommended maximum rate of entry, that is, 660 persons per entry point per hour. Therefore the entry capacity for the South Terrace is: 660 x 2 = 1320 e. Step 5 calculate the exit capacity This step is explained in Section 10.9 10.11 and Figures 2 and 13 in the Guide. The South Terrace has four vomitories at the rear, each 1.2m wide, leading into a concourse. From the concourse there are two exit gates at the rear, each 1.5m wide. The exit routes are on stepped surface and with few changes of direction. The Zone 2 travel time for the terrace under normal conditions is eight minutes. (As explained in Figure 13, under normal conditions there is no need to measure how long it might take spectators to negotiate the entire exit route.) Combined with observation of crowd flow and spectator behaviour, the ground management has decided to apply the maximum flow rate of 66 people per metre width per minute for the purposes of calculation. The four vomitories at the rear of the terrace offer a total exit width of 4.8m. However the two exits at the rear of the concourse offer a narrower total width of 3.0m. Therefore for the purpose of calculations, the narrower total width should be used for calculation. Therefore the South Terrace s exit capacity is: (2 x 1.5) x 8 x 66 = 1584 f. Step 6 calculate the emergency exit capacity This step is explained in Sections 2.13, 10.12 10.18, 15.10 and Figures 2 and 13 in the Guide. The emergency exit routes for the South Terrace pass through areas with a medium risk of fire (owing to catering outlets in the concourse). It is not considered necessary to discount one emergency exit for the purpose of calculation. The condition and the management of the exit routes are considered to be good. Therefore a maximum emergency exit time of six minutes is considered to be applicable. The emergency exit capacity is therefore (2 x 1.5) x 6 x 66 = 1188 As stated in Section 2.13 the emergency exit capacity of the terrace must include not only spectators but all people present. In this terrace, however, the emergency exit capacity comfortably exceeds the number of spectators, staff and personnel likely to be on duty, and therefore the emergency exit capacity does not need to be re-calculated. g. Step 7 calculate the final capacity of the South Terrace This step is explained in Section 2.11 and Figure 2 in the Guide. The final capacity of the South Terrace is lowest figure of those calculated: Step 3: holding capacity: 1917 Step 4: entry capacity: 1320 Step 5: exit capacity: 1584 Step 6: emergency exit capacity: 1188 Step 7: final capacity of South Terrace = 1188 10

WEA.7 Calculate the final capacity of the ground This step is explained in Sections 2.11 in the Guide. The final capacity of the ground is: West Stand: 1848 East Stand: 1544 North Terrace: 1150 South Terrace: 1188 Final capacity: 5730 WEA.8 Applying the capacity calculation Under no circumstances should more than 5730 spectators be admitted to the ground, unless remedial work and any other necessary steps have been undertaken, and the capacity calculation then re-assessed. For example, the capacity of the South Terrace could be raised if fire safety measures were introduced to the concourse area, thereby reducing the level of risk from medium to low, and if the final exit gates were widened. WEA.9 Planning for a heightened security alert This step is explained in Sections 3.18, 7.5 7.6 and Figure 7 in the Guide. Owing to a heightened security alert the management are advised to conduct manual searches of all spectators entering the ground for a particular event. This procedure is expected to reduce the rates of entry. Experience from previous occasions when similar searches have been undertaken suggest that the rate of entry will decrease to approximately 350 persons per entry point per hour. The ground management must therefore decide what is the preferred outcome and then implement the appropriate contingency plans. The options are: a. to maintain the ground s full capacity this will require additional, trained stewards to be deployed, for spectators to be advised in advance to arrive early (for example using advertisements, press notices and social media), and for all entry points to be opened early, or b. to delay the event s starting time this is to allow sufficient time for all spectators to be searched, or c. to accept a lowering of the capacity based on the anticipated reduced rates of entry. 11