NRGS Installation Instructions Level electrode NRGS A Siebe Group Product 1

Similar documents
NRGS 16-1 NRGS 16-1 S

AK 45. Installation Instructions Condensate Drain Valve AK 45. A Siebe Group Product 1

GESTRA Steam Systems AK 45. Installation Instructions Condensate Drain Valve AK 45

GESTRA. GESTRA Steam Systems CB 1... CB 2... Installation Instructions Swing Flap Non-Return Valves CB 1..., CB 2...

GESTRA Steam Systems BK 45 BK 45U BK 46. English. Installation Instructions Steam Traps BK 45, BK 45U, BK 46

Installation Instructions Control Valve with ZK Radial Stage Nozzle

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Instruction Manual Contact Pressure Vacuum Gauge

Installation, use and maintenance instructions. Gas burner (5)

HBLT-A1 LIQUID LEVEL SENSOR

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Tightness controls TC 1 3 and TC 4

Mounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6

Flow controller Type ED/CCB311 Instruction manual

Features. Up to 6 switch points Minimum degree of protection IP65 Optional temperature sensor PT1000 or thermostat Potted electrical contacts

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Magnetic level switch type MR783 Instruction Manual

VR46.5V(A)/VR86.5V(A) SERIES

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Instruction Manual Differential Pressure Transmitter

Position switches FP series

Installation, operating and maintenance Instructions for Seemag bypass level indicator

OPERATING INSTRUCTIONS

Type BBS-03, BBS-05, BBS-06, BBS-25

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

C-Flow Coriolis Mass Flow Meters

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Level switches Series LD Vibrating fork level switch for liquids and solids

Level switches Series LD Vibrating fork level switch for liquids and solids

Differential pressure controls, Type MP 54, 55 and 55A

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Gas Pressure Regulator HON 300

Pressure switch and Thermostat CAS

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

Expansion Thermometers Stainless Steel Series, Model 70

KGW - ISOTHERM. Operating Instructions. Level controlling device for liquid nitrogen LEVEL CONTROL LN2

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

BCVi43 Blowdown Control Valve

Installation and Operating Instructions Bypass Flow Meter DST

ph measuring system for hygienic process applications

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Types and approvals. Page 1/6. Data Sheet

Differential Pressure Control Types MP 54, MP 55 and MP 55A

Pressure switches and thermostats, type KPS

Prewired position switches FA series

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Manual Power relay SR853

Operating Instructions

Data sheet. Pressure switches and thermostats Type KPS 10/2003 DKACT.PD.P10.E B0782

Instruction Manual Differential Pressure Transmitter

Pressure switch and Thermostat Type KPS

Dual Solenoid Gas Valve Installation

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

High-performance submersible pressure transmitter For level measurement Model LH-10

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0

Product information. Capacitive. Level detection in liquid VEGACAP 62 VEGACAP 63 VEGACAP 64 VEGACAP 66 VEGACAP 69. Document ID: 29983

Inverted Bucket Steam Trap IB 16A-7

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Instruction Manual. Standard Surge Eliminator. Standard X. Flushable X - X

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

DWR6-205, DWR16-205, DWR6-206 Safety Pressure Limiters

INSTRUCTION MANUAL Pressure Relief Device LPT

Pressure transmitters EMP 2

4/2 way Pneumatic Solenoid Valve

INSTRUCTION MANUAL COMPACT PRESS. SWITCHES SERIES PCS & PCA

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Declaration of Conformity as per Directive 97/23/EC

Pressure switch and Thermostat KPS

Pressure controls, differential pressure controls type RT

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters

QPL... Pressure Switches. Siemens Building Technologies HVAC Products

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Valve Proving System VDK 200 A S02

Pressure relief valve

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Operating Instructions

Valve Proving System VDK 200 A S06*

Instruction Manual Contact Pressure Gauge

SPECIFICATIONS ATTENTION

Safety Valves. Product Information. It s all at Albion

Pressure Dump Valve Service Kit for Series 2300 Units

Flamco Flamco-Fill STA Flamco-Fill STM

PSG 901. Pressure Switch for Gas. elektrogas.com EE141-07/12

Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Gas density monitor With integrated transmitter Model GDM-100-TI

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Old documentation - Only for your information! Product is not available anymore!

Declaration of Conformity as per Directive 97/23/EC

Compact pressure switches for gas and air

Transcription:

NRGS 16-2 Installation Instructions 810212-00 Level electrode NRGS 16-2 A Siebe Group Product 1

Dimensions 173 500, 1000, 1500 337.5 140 Fig. 1 2

NRGS 16-2 A B C 40 1" BSP DIN 228 N10 0.5 50 14 65 70 N8 Fig. 2 Fig. 3 3

NRGS 16-2 MAX 70 C MAX 95 % D E F G H I J Fig. 4 P O N M L Fig. 5 K 4

Legend A B C D E F G H I J K L M N O P Electrode thread 1" BSP, DIN 228 Seating surface Joint ring (of stainless steel 1.4301) D 33 x 39 to DIN 7603 Housing screws M4 Cable entry PG 9/PG 16 Housing cover LED Low level alarm LED Low level alarm LED Pump ON DIP switch Measuring range Button Test Terminal strip PE connection Terminal strip Test Thermal fuse T max 102 C Screw 5

Contents Important Notes Page Safety Note...7 Danger... 7 Warning... 7 Explanatory Notes Scope of supply...8 System description... 8 Function...8 Design...8 Technical data... 9, 10 Installation NRGS 16-2... 10, 11 Table Functions... 11 Examples of installation... 17 Wiring NRGS 16-2...12 Standard Setting Factory setting... 13 Switch selection of measuring range... 13 Commissioning Warning...14 Wiring check... 14 Application of mains voltage... 14 Checking of switching functions... 14 Checking of low level alarm... 14 Annex Warning...15 Fault finding list...15 Declaraction of conformity... 16 6

Important Notes Safety Note Use compact system for level monitoring type NRGS 16-2 only for level indication. Installation must only be performed by qualified staff. Qualified staff are those persons who through adequate training in electrical engineering, the use and application of safety equipment in accordance with regulations concerning electrical safety systems, and first aid & accident prevention have achieved a recognised level of competence appropriate to the installation and commissioning of this device. Danger When loosening the electrode live steam or hot water might escape. This presents the danger of severe injury. It is therefore essential not to dismantle the electrode unless the boiler pressure is verified to be zero. Warning The terminal strip of the NRGS 16-2 is live during operation. This presents the danger of electric shock. Cut off power supply before fixing or removing the housing cover. 7

Explanatory Notes Scope of Supply NRGS 16-2 1 Compact system type NRGS 16-2 1 Joint ring (of stainless steel 1.4301) D 33 x 39 DIN 7603 1 Installation Instruction System Description The compact system NRGS 16-2 works according to the conductivity measurement principle. With the NRGS 16-2 a maximum of 3 levels can be signalled in conductive liquids: Low level alarm, pump ON, pump OFF with one normally open contact The NRGS 16-2 has a level switch integrated in the electrode case for the controlling of all functions. An external switching device is not required. The NRGS 16-2 has two electrode rods for the detection of low water level. The signalling of the low-level alarm is effected via two separate switching channels. Function The conductivity of the liquid is used to signal the liquid level. Some liquids are conductive, which means that they allow an electric current to flow through them. For the safe functioning of this device a minimum conductivity of the liquid to be measured is required. The conductivity measurement method can detect two conditions: electrode rod submerged/ exposed or switchpoint reached/ not reached. Before installation, the length of the electrode rod must be adapted to the switching levels, e. g. for max./min. alarm, controlling of a valve or pump. Design NRGS 16-2: Screwed design 1" BSP, DIN ISO 228. Fig. 1 8

Technical Data Type Approval N TÜV. WR/WB. 97-392 Max. service pressure 32 bar g at 238 C Connections Screwed 1" BSP, DIN ISO 228 Flanged DN 50, PN 40, DIN 2635 Materials Case Die cast aluminium 3.2161 (G AlSi8Cu3) Stem S. S. 1.4571 (CrNiMoTi 17 12 2) Flange Forged steel 1.0460 (C 22.8) Measuring electrodes S. S. 1.4571 (CrNiMoTi 17 12 2) Electrode insulation PTFE Spacer disc PTFE Lengths supplied 1500 mm 1000 mm 1500 mm Mains supply 230 V +/ 10 %, 50/60 Hz 115 V +/ 10 %, 50/60 Hz 224 V +/ 10 %, 50/60 Hz (option) Power consumption 5 VA Fuse Thermal fuse T max = 102 C Sensitivity Range 1: 10 µs/cm Range 2: 0.5 µs/cm Electrode voltage 10 V ss Output 2 volt-free relay contacts. 1 volt-free normally open contact. Max. contact rating with a switchting voltage of 24 V, 115 V and 230 V a. c.: ohmic 4 A, inductive 0.75 A at cos ϕ 0.5. Max contact rating with a switching voltage of 24 V d. c.: 4 A Contact material: silver, hard-gold plated 9

Technical Data - continued Indicators and adjustors 2 red LEDs for signalling Low water, 1 green LED for signalling Pump ON, 1 four-pole DIP switch for changing sensitivity, 1 button TEST for functional checking of low level alarm Cable entry Cable gland with integral cable clamp 1 x PG 19 1 x PG 16 Protection IP 65 to DIN 40050 Max. admissible ambient temperature 70 C (158 F) Weight approx. 1.8 kg Installation NRGS 16-2 1. Determine required measuring lengths of electrode rods and enter data in table 1 Fig. 2. 2. Cut electrode rods 1, 2, 3 and 4 accordingly. The electrode rods 1 and 2 (low level limiter) must have the same length. 3. Deburr faces of electrode tips. 4. Strip off 50 mm of PTFE insulation from the ends of electrode tips. 5. Check seating surfaces of threads or flange provided on vessel or boiler standpipe. Fig. 3 6. Place joint ring C onto seating surface B of electrode Fig. 2. Use only joint ring (of stainless steel 1.4301) D 33 x 39 to DIN 7603 supplied with electrode. 7. Apply a light smear of silicone grease (e. g. DOW Corning 111 Compound) to electrode thread A. 8. Screw level electrode into threads or flange provided on vessel or boiler standpipe and tighten with a 41 mm open-end spanner. The torque required is 140 Nm when cold. 10

Installation - continued Table 1 Function Function Electrode rod Length [mm] Low-level alarm 1 Low-level alarm 2 e. g. Pump ON 3 e. g. Pump OFF 4 Attention The seating surfaces of the threads or flange provided on the vessel or boiler standpipe must be accurately machined. Fig. 3 Do not bend electrode rod when mounting. Do not lag electrode body. Note For the approval of the boiler standpipe with connecting flange the relevant local and national regulations must be considered. See four examples of installation on page 17. Tools Open-end spanner 41 mm A. F. Bolt cutter Hacksaw Flat file, medium cut 11

Wiring NRGS 16-2 Use multi-core flexible cable with min. conductor size 1.5 mm 2 for wiring. 1. Unscrew screws D, remove housing cover F Fig. 4 2. Unscrew union nuts of cable entry E. The electrode terminal can be turned through +/ 180. 3. Loosen screw P with 17 mm open-end spanner but do not remove. Fig. 5 4. Turn electrode terminal into desired direction (+/ 180 ). 5. Tighten screw P slightly. 6. Remove terminal strip L from board. 7. Connect terminal strip according to wiring diagram, connect PE connection M. 8. Plug in terminal strip. 9. Replace housing cover F, fasten screws D and install cable entry. Wiring diagram Fig. 6 Mains Attention Fuse supply cables with T 250 ma. Tools Screwdriver for cross head ( Phillips ) screws, size 1 Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680 Open-end spanner 17 mm A. F. 12

Standard setting Factory setting The compact system is delivered with the following factory settings: Measuring range 10 µs/cm Switch selection of measuring range The measuring range can be switch selected between 0.5 µs/cm and 10 µs/cm by means of DIP switch J : 1.Unscrew screws D at the electrode terminal, remove cover F, Fig. 6 DIP switch 1 4 OFF Measuring range 0.5 µs/cm DIP switch 1 4 ON Measuring range 10 µs/cm 2.Replace cover F and fasten screws D Attention Do not damage the electronic components when operating DIP switch. Tools Screwdriver for cross head ( Phillips ) screws, size 1 Screwdriver for slotted screws, size 2.5; completely insulated according to VDE 0680 13

Commissioning Warning The terminal strip of the NRGS 16-2 is live during operation. This presents the danger of electric shock. Cut off power supply before removing or replacing housing cover. Wiring check 1. Check whether the system NRGS 16-2 has been wired according to wiring diagram Fig. 6. 2. Check whether mains supply corresponds to the wiring carried out on the equipment. Application of mains voltage 1. Switch on mains supply and check the correct functioning of the equipment at the corresponding switchpoints. LEDs G, H, I are provided for visual check of switchpoints. Fig. 5 Remove housing cover F to check LEDs G, H, I. See Wiring Check correlation of switching functions 1. Check the switching function Low level alarm of the electrode rods 1 and 2. For this test the level in the vessel must fall below the low level mark. The low-level alarm must then be activated by the level switch. 2. Check the switching function Pump ON and Pump OFF. See table 1. Check low-level alarm The function of the low-level alarm can be simulated by pushing the button TEST K. Fig. 5 The low-level alarm must then be activated. 14

Annex Warning The terminal strip of the NRGS 16-2 is live during operation. This presents the danger of electric shock. Cut off power supply before removing or replacing housing cover. Fault finding list Switchpoint Pump ON has been exceeded no function Fault: Mains voltage has not been applied. Remedy: Apply mains voltage. Wire equipment according to the wiring diagram. Fault: The thermal fuse has failed. Remedy: In case of defective thermal fuse the mains voltage has not been connected to terminal N : Replace defective thermal fuse (Order No. 051629). The ambient temperature must not exceed 70 C. Switchpoint Pump OFF has been exceeded no function Fault: The electric conductivity is too low. Remedy: Switch DIP switch J to 0.5 µs/cm. Fault: The electrode housing does not have earth connection to the boiler. Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel 1.4301) 33 x 39 to DIN 7603. Do not insulate compact system with hemp or PTFE tape! Fault: Electronic board is defective. Remedy: Replace board (Order No. 391423). Level has fallen below switchpoint Low water no function Fault: The electrode rods have earth contact. Remedy: Change installation position. Fault: The vent hole in the protection tube does not exist, is obstructed or flooded. Remedy: Check protection tube and, if necessary, provide vent hole. Fault: The isolating valves of the external measuring pot (optional) are closed. Remedy: Open isolating valves. Switchpoint has been reached incorrect function Fault: The switching function has not been correctly allocated. Electrode rods have been cut to the wrong size. Remedy: Identify electrode supply wire and reconnect accordingly. 15

Annex - continued Declaration of conformity We hereby declare that the equipment NRGS 16-2 conforms to the following European guidelines: LV guideline 73/23/EWG version 93/68/EWG EMC guideline 89/336/EWG version 93/68/EWG which are based on the following harmonised standards: LV standard EN 60947-5-1: 1991 EMC standard EN 50 081-2, EN 50 082-2 This declaration is no longer valid if modifications are made to the equipment without consultation with us. Bremen, 28th April 1997 GESTRA GmbH Dr. Anno Krautwald Dr. Christian Politt Legend 1 2 3 4 5 6 7 8 9 10 11 12 Flange PN 40, DN 50 (2"), DIN 2527 Flange PN 40, DN 100 (4"), DIN 2527 For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered. Vent hole High water (HW) Electrode rod d = 5 mm Protection tube DN 80 Protection tube DN 100 Electrode distance 14 mm Electrode distance 40 mm Low water (LW) Reducer K-88.9 x 3.2-42.4 x 2.6 W to DIN 2616, part 2 Reducer K-114.3 x 3.6-48.3 x 2.9 W to DIN, 2616 part 2 16

Examples of installation DN 50 1" BSP 1 2 DN 50 1" BSP 1 2 4 20 20 3 5 1500 4 20 20 3 5 8 90 10 6 8 10 11 90 20 20 Fig. 7 Fig. 8 10 1" BSP 6 10 11 11 1 2 ¾" BSP 1" BSP 1 2 DN 20 20 4 DN 100 24.5 24.5 3000 9 3 20 20 90 20 4 5 7 8 10 12 DN 20 ME 20 5 10 Fig. 9 Fig. 10 DN 20 17

GESTRA Gesellschaften GESTRA Companies Sociétés GESTRA Sociedades Gestra Società GESTRA Vertretungen weltweit Agencies all over the world Représentations dans le monde entier Representaciones en todo el mundo Agenzie in tutto il mondo España Siebe GESTRA Instrument ESPAÑOLA & Valve S.A. Division GESTRA Luis Cabrera, ESPAÑOLA 86-88 S.A. Luis E-28002 Cabrera, Madrid 86-88 E-28002 Tel. 34Madrid 91 / 5 152 032 Tel. Fax 003491/4136747; (91) 5152032 5152036 Fax E-mail: (91) gestra@gestra.es 4136747 France France Siebe Instrument & Valve Division Flowserve Flow Control S. A. S. GESTRA S.A.R.L. 10 Avenue du Centaure, BP 8263 18, rue André Pontier F-95801 CERGY PONTOISE CEDEX F-94 130 Nogent-sur-Marne Tél. 0 03 31 / 34 43 26 60 Tél. 01.45.14.14.45 Fax 00331/34432687 Fax 01.48.73.41.20 E-mail: gnation@flowserve.com Great Britain Italia Siebe Instrument & Valve Division GESTRA Italgestra (U.K.) S.r.l. LTD. 9-11 Via Carducci Bancroft 125 Court Hitchin, l-20099 Hertfordshire, Sesto San Giovanni SG5 1PH (MI) Tel. 00 (0 14 3962) 02 / 43 2416 1081 12.1 Fax 00 (0 14 3962) 02 / 42 2403 1096 12.460 E-mail: info@italgestra.it Italia Polska Siebe GESTRA Instrument POLONIA & Spolka Valve Division z o.o. GESTRA Ul. Schuberta POLONIA 104, P. O. Spolka Box 71 z.o.o. Ul. PL-80-172 Oplotki, Gdansk 1, P. O.B. 727 PL-80-958 Tel. 00 48 58 Gdansk / 306 105002 oder 306 10 10 Tel. Fax 00 (58) 4831 5801 / 306 26 10 03 oder 306 33 00 Fax E-mail: (58) gestra@gestra.pl 31 18 52 Portugal Portugal Siebe Instrument & Valve Division GESTRA PORTUGUESA VALVULAS LDA. GESTRA PORTUGUESA VALVULAS LDA. Av. Dr. Antunes Guimarães, 1159 Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 P-4100 Porto, Tel. 0035122/6198770 Tel. (2) 6 10 75 51 Fax 00351 22 / 6 10 75 75 Fax (2) 6 10 75 57 E-mail: gestra@gestra.pt USA Siebe Instrument & Valve Division GESTRA INC. 10 York Avenue West Caldwell, N.Y. 07006 Tel. (2 01) 4 03-15 56 Fax (2 01) 4 03-15 57 Siebe Instrument & Valve Division ITALGESTRA S.r.l. Via Carducci 125 l-20099 S.S. Giovanni (MI) Tel. (02) 2 62 97-0 Fax (02) 26 29 74 60 GESTRA GmbH Postfach Siebe Instrument 10 54 60 & Valve Division D-28054 Bremen Münchener GESTRA GmbH Str. 77 D-28215 Hemmstraße Bremen 130 Tel. D-28215 +49 (0) Bremen 421 35 03-0 Fax Tel. +49 (0) 421 3503-0 03-393 E-mail Fax +49 gestra.gmbh@gestra.de (0) 421 35 03-393 Internet www.gestra.de A Siebe Unit of Group Flowserve Company Corporation 810212-00/1297c 1997 GESTRA GmbH Bremen Printed in Germany 18