Assessing Permeation of Gas through Polyethylene Pipe

Similar documents
Shrinkage Leakage Model Review

OCTOBER 2017 ISSUE Page 1 of 7

BLOCKAGE LOCATION THE PULSE METHOD

Reduction of Speed Limit at Approaches to Railway Level Crossings in WA. Main Roads WA. Presenter - Brian Kidd

Guidance on room integrity testing and its interpretation

September 2018 Pressure Test

2 FUSION FITTINGS FOR USE WITH POLYETHYLENE PRESSURE PIPES DESIGN FOR DYNAMIC STRESSES

Safety Monitor Requirements. September 2012

Report to the Joint Standing Committee on Inland Fisheries and Wildlife

Appendix C Field Testing of Pipelines

Aberdeen Significant Error Review ITE Independent Report. Eur Ing Keith Vugler CEng FInstMC

Gas Pressures FAQs. Why only 19 mbar inlet pressure and 15 mbar outlet pressure? MOV: meter outlet valve ECV: emergency control valve

IGEM/TD/2 Edition 2 with amendments July 2015 Communication 1779 Assessing the risks from high pressure Natural Gas pipelines

DN 50 REGULATOR SUTON 5000A1 REGULATOR SUTON 5000D1

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

Micro Channel Recuperator for a Reverse Brayton Cycle Cryocooler

PROJECT L6 GREYHOUND RACING

Bus and Transit Lane Review Update

Application of pipeline risk assessment to proposed developments in the vicinity of high pressure Natural Gas pipelines

Best Practice RBI Technology Process by SVT-PP SIMTECH

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges

PUBLISHED PROJECT REPORT PPR850. Optimisation of water flow depth for SCRIM. S Brittain, P Sanders and H Viner

Committee on NFPA 85

Investigation of Thermal Effects of CO 2 on Earth-Atmosphere System

Increased Project Bankability : Thailand's First Ground-Based LiDAR Wind Measurement Campaign

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP

Efficient Pigging of Gathering Lines. Energy Management Workshop for Upstream and Midstream Operations

Permitted MSS Emissions Tracking, Recordkeeping, and Reporting. Presented by ACES April 24, 2008

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS

Safety Monitor Requirements Revised. February 2018

ADVANCES in NATURAL and APPLIED SCIENCES

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands

Blue cod 5 (BCO5) pot mesh size review

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

SAFETY PHILOSOPHY FOR SERVICE LINES AND GAS INSTALLATION

EFFECTIVE DESIGN OF CONVERTER HOODS. 111 Ferguson Ct. Suite 103 Irving, Texas U.S.A. 400 Carlingview Dr. Toronto, ON M9W 5X9 Canada.

Modeling Diffusion Rates of a Gas in an Enclosed Space

1800CPB2 Service Regulators

Economic Impact Study: NFL International Series London, 28 October 2012

Performance Literature for J48. Gas Pressure Regulators 2½ 6 Sizes. Catalogue

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

Buoyancy Control Calculated Cost Allowance for 1 Year Study Cost Estimate

INTRODUCTION Porosity, permeability, and pore size distribution are three closely related concepts important to filter design and filter performance.

The leakages on the water pipes

REDUCING EMISSIONS WHEN TAKING COMPRESSORS OFF-LINE

Instruction Manual. Pipe Friction Training Panel

Recommendation to the Minister of Energy by the Gas Industry Co on the Specification for Reticulated Natural Gas

HIPPS Development Project

FlexAct BT (Bag Tester) Validation November, 2015

Thermoplastic Road Marking Applicator

CONTROL VALVE SEAT LEAKAGE

PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015)

Becker* Products Below Ground Ball Valve Regulators

A STUDY OF THE LOSSES AND INTERACTIONS BETWEEN ONE OR MORE BOW THRUSTERS AND A CATAMARAN HULL

CASE STUDY. Elvington To Brayton Barff Air valve replacement Program

Flow and Mixing in the Liquid between Bubbles

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

Gas Pressure Boosting A Guide

Gas Gathering System Modeling The Pipeline Pressure Loss Match

John Gurden, J P Kenny Ltd Onshore Pipeline and the Landfall Valve Installation (LVI) Design. Knowledge of the Corrib Onshore Pipeline Project

COMPARING PLUG & SEAT REGULATORS & CONTROL VALVES. Lamar Jones. Equipment Controls Company 4555 South Berkeley Lake Road Norcross, GA 30071

The Protection of Silos From Over. Pressurisation During Filling

SANDRINGHAM GOLF LINKS PROJECT

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Network Regulator Maintenance Operatives LS (Non-Accredited)

A quantitative risk analysis method for the natural gas pipeline network

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

Experiment 8: Minor Losses

A GUIDE TO RISK ASSESSMENT IN SHIP OPERATIONS

Participation in Structured Swimming Lessons : 0-13 Years

User Information Sheet 015

ERCBH2S Frequently Asked Questions.

Safety Monitor and Firm Gas Monitor Requirements. September 2007

Global Buckling Design for Flexible Flowlines

Performance Literature for 60DJ, 80DJ & 150DJ Gas Pressure Regulators ¼, ⅜ and ½ Sizes. Catalogue

Best Practice Guidance for Assessing the Financial Performance of Fishing Gear: Industry-led gear trials

Risks Associated with Caissons on Ageing Offshore Facilities

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Brass Check Valve RDL

LEAK FREQUENCY MODELLING FOR OFFSHORE QRA BASED ON THE HYDROCARBON RELEASE DATABASE

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

ENHANCED PARKWAY STUDY: PHASE 2 CONTINUOUS FLOW INTERSECTIONS. Final Report

1800CPB2 Pilot-Loaded Service Regulators

Litter Strategy Monitoring Wave 55 November 2011 Report

INTEGRITY MANAGEMENT OF STRESS CORROSION CRACKING IN GAS PIPELINE HIGH CONSEQUENCE AREAS

Gas National Transmission System. April Maintenance Programme. April March Draft Version 1.0

Prediction of the long-term insulating capacity of cyclopentane-blown polyurethane foam

# Post Consultation and Submissions Resource Consent Conditions for Surfing Impact Mitigation August 2016

Banksia Securities Limited ACN: (Receivers and Managers Appointed)(In Liquidation) ("BSL")

A new concept in the storage of liquefied chemical and petrochemical gases Zero leakage Zero fugitive emissions

Cycling and Walking Investment Strategy & Local Cycling and Walking Infrastructure Plans

By E. Smith - BP Amoco Exploration, Sunbury, England, and J. McAleese - City University, London, England

CONTROL VALVE TESTING

HS2 Ltd HS2 London to West Midlands Route Corridor Reviews Journey Time Analysis. January 2012

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Transcription:

Assessing Permeation of Gas through Polyethylene Pipe REPORTS

Introduction Gas Distribution Networks (GDNs) regularly review the Shrinkage and Leakage model (SLM) to further enhance the reporting of Shrinkage gas. During 2017 we regularly met with interested parties through the Shrinkage forum 1 to help identify opportunities for improvement of the SLM and also discuss matters directly related to the evaluation of Shrinkage Gas. Towards the end of the year, we published an annual report 2 for consultation with interested parties which included our planned commitments to review areas of the SLM and published our 2018 approach. Our Commitment 2018 Approach Potential Impact on Shrinkage Modelling Following discussions with Stakeholders GDNs will investigate the potential impacts of PE permeation. We will further investigate the accuracy of the existing MP Leakage calculation. We will continue to investigate the opportunity of reflecting the benefits of Remediated Pipes in the SLM. We will review the suitability of the existing Own Use Gas calculation within the SLM. GDNs will review the calculations within the model to determine whether PE permeation is inclusive within the current leakage rates. If this factor is found to be absent from the current rates, GDNs will engage with industry experts to review the impact of PE permeation on the Shrinkage and Leakage model. GDNs will engage with industry experts to determine the preferred approach for refreshing the MP Leakage calculation. GDNs are currently finalising the overall remediation capture process and ensuring all associated supporting evidence is available, with a view to developing an industry consultation on a modification to the SLM. We will continue to investigate the results of low carbon preheating trials and determine if they can be used as a basis for revising the Own Use Gas (OUG) calculation. We will also consult industry experts to understand if other methods of calculating OUG are available. If it is concluded that a separate PE permeation rate should be applied to the calculation of fugitive emissions from PE pipes, then this will result in an increase in total leakage although this is anticipated to be a relatively small amount due to the nature of this factor. Feedback from the AUG expert suggests that pressure and leakage are proportional to one another, however, MP leaks are more likely to be rectified sooner. Any proposed change will target improvement to the MP leakage calculation. Remediation is a process for maintaining our pipe assets with minimal impact on our customers. If it is proven that remediation is effective in driving down leakage, future Shrinkage calculations may include a correction for remediated mains in order to improve the accuracy of the SLM. Whilst the results of the low carbon preheating trials have still to be fully reviewed, it is anticipated that the estimates of OUG will change. Figure 1 - Summary of 2018 GDN Commitments As part of the GDNs approach for 2018, we are committed to reviewing the leakage rates within the SLM to ensure any impact of the permeation of gas through polyethylene (PE) pipe is accurately reflected. The GDNs will engage with industry experts to review the impact of PE permeation on the current SLM. 1 https://www.gasgovernance.co.uk/sf 2 https://www.gasgovernance.co.uk/shrinkage/consultations

Executive Summary Gas Permeation through PE refers to the diffusion of gas through the wall of the pipe and is affected by factors such as the differential pressure between the fluid within the pipe and the surrounding atmosphere, the wall thickness of the pipe, density of PE and temperature. Approximately 75% of total Medium pressure and Low pressure mains in the UK gas networks are of PE material, therefore it is imperative that gas permeation through gas pipelines is reviewed to ensure its impact is accurately reflected in the current SLM. The view of GDNs is that decay tests previously carried out include the impact of permeation and this study seeks to test that assumption. The report published following the National Leakage Test 2002/3 3 (NLT) describes the method used to carry out the 849 leakage tests on different sections of gas mains and services. The report details the test procedure and confirms that the sections of mains and services which were being tested were subject to being capped and isolated, with the rider from an upstream section of the network not under test conditions, would be connected to the test section in order to maintain pressure and prevent depressurisation. The leakage test method which was used was the Pressure Decay Method. This method measures the decrease in pressure within the pipe which is a consequence of gas exiting the pipe irrespective of the route i.e. gas escaping through joints, permeation etc. The pressure in the main was not allowed to decay prior to the leakage test being carried out therefore ensuring that the test conditions matched those the pipe would see in service. As a result, the GDNs are certain that permeation of gas through the wall of PE pipes was captured during the NLT 2002/3 and subsequently the current leakage rates which are used in the SLM include gas permeation. Current Leakage rates National Leakage Test 2002/3 The current SLM uses leakage rates defined from the 2002/3 National Leakage Test Programme (NLT) where 849 sections of pipe were tested for leakage. Following these tests, leakage rates were defined for the various pipe materials and diameters. As a result the leakage rate attributed to PE pipes are 63.51 cubic metres of gas, per km, per annum. 3 Report on the 2002/3 National Leakage Test Programme, Kirsty Nelson, Advantica Limited

The methodology used for the NLT to determine the rate at which gas leaks from the sections of pipe included the process of capping and isolating sections of pipe followed by pressurisation of the section to 30 mbar. Whilst the section of main was capped and isolated, a rider from the upstream main (pipe not under test conditions) was used to maintain a steady pressure within the test main to prevent the test section depressurising. Following the capping and isolation of the test section, the pipe pressure was allowed to decay due to leakage whilst the pressure and temperature was continuously recorded. Diffusion of gas through PE pipe takes a considerable amount of time to occur. As the pressure in the main was not allowed to decay prior to the test, the rate of diffusion of gas through permeation of the PE pipe would remain constant. This ensures that the test reflects the appropriate in-service conditions for the pipe leakage test. On the contrary, if the section of pipe which was under test conditions was subject to depressurisation prior to the test being carried out, this may have disturbed the process of permeation which could have had a minor impact on the leakage results obtained. The test method, a Pressure Decay method, measured the reduction in pressure of the pipe during the test period, which would include the reduction of pressure which resulted from the permeating gas through the pipe wall. Given the evidence of the test procedure and methodology, the GDNs conclude that permeation of gas through the wall of PE pipes was captured during the NLT 2002/03 and that the current leakage rates which are used in the SLM include gas permeation. Energy UK report The Energy UK report 4 references permeation of gas through PE pipes with estimates greater than the current leakage rates for total leakage through PE mains. The figures quoted within the report suggested that over the course of a year, 1km of 2 PE pipe will account for slightly more than 450 cubic metres of permeated gas, a quantity which greatly exceeds the current leakage rate of 63.51 cubic metres per km, per year. This estimation was carried out based on tests done at much higher pressures and temperatures and then extrapolated down to lower pressures, assuming a direct correlation. The GDN s have commented on these claims in a response to the Energy UK report 5. Permeation of gas through PE pipe under low pressure conditions (25-75 mbar) would be extremely difficult to measure due to the very small quantities estimated to diffuse through the pipe wall using the current technology. It s likely that any such tests that are completed under alternative conditions 4 https://www.gasgovernance.co.uk/sites/default/files/ggf/energy%20uk%20grg%20shrinkage%20 study%20final.pdf 5 https://www.gasgovernance.co.uk/sites/default/files/ggf/joint%20gdn%20response%20to%20ene rgy%20uk%20grg%20shrinkage%20study_0.pdf

i.e. higher pressures and temperatures with the results extrapolated down, would not reflect reality due to the contrasting results this would indicate in comparison to the extensive tests carried out during the NLT. Manufacturer data The GDNs approached the manufacturer to review the data which is held by them for permeation of gas through PE pipe. The manufacturer provided a model which included data derived from Crank & Glicksman thereom and also the American Gas Association. The GDNs carried out analysis of their network using the data provided and concluded that permeation accounts for a small proportion of leakage gas with a calculated proportion of less than 0.01% of total leakage. The calculated quantity of leakage gas caused by permeation through PE pipe indicates a value of less than 0.1% of the current leakage rate of PE which is in use within the SLM, the remainder of the PE leakage rate being compromised of other leakage as evidenced in the NLT report. Conclusion The GDN s are committed to enhancing the reporting of Shrinkage gas. As part of the 2017 commitments, we reviewed whether the current leakage rates which form part of the calculation of Leakage gas include the quantity of gas which has permeated through the wall of PE pipes. Upon reviewing the NLT 2002/03 report, it is clear that prior to the leakage test being carried out on a section of pipe, the pressure in the section was maintained using a rider from an upstream part of the network which was not under test conditions. This allowed the pressure in the test section to remain pressurised therefore allowing for permeation of gas to take place during the course of the pressure decay test. To conclude, the GDNs feel that permeation of gas through PE pipe is currently included within the current leakage rates which are used within the current SLM.