Operating Manual. Model 25200A Refrigerant Recovery Unit. (not for use in automotive R-134a applications)

Similar documents
Operating Manual. Model 25200B/25202B Refrigerant Recovery Unit. (Not for use in automotive R-134a applications)

Refrigerant Recovery, Recycling and Recharging Station

RG6000. Refrigerant Recovery Machine. Operating Manual. 99 Washington Street Melrose, MA Phone Toll Free

TP-MM1 Refrigerant Recovery Machine

Vortex Dual. Refrigerant Recovery Machine

RecoverXLT Oil-Less Universal Refrigerant Recovery System. (For serial numbers and higher)

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

RecoverXLT2-AP Oil-Less Universal Refrigerant Recovery System Operation and Maintenance Manual

High Performance Oilless Commercial Refrigerant Recovery Unit. User Manual

OPERATING INSTRUCTIONS

OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N

Operation and Maintenance Manual

High Performance Oilless Commercial Refrigerant Recovery Unit. User Manual Rev. 4 November 2010

RecoverXL and RecoverXLT Oil-Less Universal Refrigerant Recovery Systems Operation and Maintenance Manual

2 GAL AIR COMPRESSOR OPERATOR S MANUAL 1/3HP/2-GALLON IMPORTANT: READ THIS OPERATOR S MANUAL BEFORE USING

R E D I C O N T R O L S

High Performance Oilless Commercial Refrigerant Recovery System. User Manual REV E 06/30/03

Model 3600-R410A. Part No Instruction Operation & Maintenance

Instruction Manual Recovery Station

Refrigerant Recovery System Model 3600 Part No

100C Air Compressor Kit

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI COMPRESSORS - MODEL NUMBERS

BEFORE HANDLING REFRIGERANTS, READ MATERIAL SAFETY DATA SHEET FROM REFRIGERANT MANUFACTURER.

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

444C DUAL PERFORMANCE VALUE PACK

PC1131 Electric Air Compressor

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

IMPORTANT SAFETY INSTRUCTIONS

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

200 PSI HIGH-FLOW AIR SOURCE KIT

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

400C & 450C DUAL PERFORMANCE VALUE PACKS

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

JAVAC EVO-HS REFRIGERANT RECOVERY MACHINE

OPERATION AND MAINTENANCE INSTRUCTION MANUAL

AMP Oil Free Manual AMP 50-8-TC AMP 50-6-D AMP General User and Maintenance Instructions

Portable Oil Lube Air Compressors

Vortex Dual. Refrigerant Recovery Machine. English Español Français Deutsch Italiano Nederlands Svenska 中文

OPERATOR S MANUAL 1.5 HP/6-GALLON 6 GAL AIR COMPRESSOR IMPORTANT: READ OPERATOR S MANUAL BEFORE USING. Toll Free Helpline:

VERTICAL AIR COMPRESSORS

20 GAL OIL FREE AIR COMPRESSOR

8-gallon Air Compressor. Owner s Manual

DeVILBISS AIR POWER COMPANY. OWNERS MANUAL FOR PERMANENTLY LUBRICATED AIR COMPRESSOR (For Home Use Only) MODEL NO. DFAC153 SPECIFICATION CHART

Standard Gas Countertop Griddle

Fieldpiece. Refrigerant Recovery Machine OPERATOR'S MANUAL. Model MR45

Fieldpiece. Refrigerant Recovery Machine OPERATOR'S MANUAL. Model MR45

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

COMPRESSOR MANUAL. (888)

6 GAL PORTABLE OIL FREE AIR COMPRESSOR

4 and 8 Station PDS Control Installation & Operators Manual

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

Section 3- Repair and Calibration Procedures

REDI CONTROLS, INC. Model RS-503/13-C3. RECOVERY SYSTEM for Very High Pressure Refrigerants R-13, R-23, R-503, & SUVA-95

Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST Industrial Drive, Orlinda, TN 37141

POWER FLUSH KIT INSTRUCTIONS

2 Gallon Air Compressor

Owner s Manual & Safety Instructions

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

IMPORTANT SAFETY INSTRUCTIONS

Gas Countertop Hot Plates

2 Gallon, 100 PSI Oilless

BGA158 Series CE Approved Class A Shutoff Gas Valve

XpressFill XF2500 Counter Pressure Filler. Operating Instructions

VERTICAL AIR COMPRESSORS

MODEL NUMBER: P PORTABLE COMPRESSOR

GAS FRYER Instruction Manual Model #5099NS

Safety Powder Spray Systems

Yoke Block Instruction Manual

MODEL NUMBER: P PORTABLE COMPRESSOR

6 GAL OIL-FREE HORIZONTAL COMPRESSOR

2 Gallon Oil Free Air Compressor

Digital Vacuum Regulator

5 GAL PORTABLE OIL FREE AIR COMPRESSOR

UNIVERSAL GAS FRYER Instruction Manual Model #8065NS

2-Liter Pressure Cup. Instructions - Parts List C

Oil-Free Air Compressor

TECHNICAL INFORMATION

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

PC 1010 Electric Air Compressor

Budget Range Operators Handbook

OPERATION MANUAL NTF-15

Dual Solenoid Gas Valve Installation

INSTALLATION GUIDE Gas Rangetops

SILENTAIRE TECHNOLOGY

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor

XpressFill XF4500C Counter Pressure Can Filler. Operating Instructions

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

Air Compressor Electric Handheld

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

OPERATION MANUAL NTF-60 Plus

Transcription:

Operating Manual Model 25200A Refrigerant Recovery Unit (not for use in automotive R-134a applications)

Refrigerant Recovery Unit Model: 25200A Series Type of Equipment: Recovery Refrigerants: R-12, R-22, R-134a, R-401A, R-401B, R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-408A, R-409A, R-410A, R-500, R-502, R-507 WARNING LISTED Refrigerant Recovery Equipment 12Y2 DESIGN PRESSURE: High 435 psig Low 336 psig PRESSURIZED TANK CONTAINS REFRIGERANT. OVERFILLING OF THE TANK MAY CAUSE VIOLENT EXPLOSION AND POSSIBLE INJURY OR DEATH. Safety devices require the use of only the following Robinair UL listed tanks: 17571 (30 lb. tank) and 17572 (50 lb. tank). Do not recover refrigerants into a non-refillable storage container! Federal regulations require refrigerant to be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA. CAUTION: TO REDUCE THE RISK OF INJURY, care should be taken when moving this equipment. ALL HOSES MAY CONTAIN REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury. Wear proper protective equipment, including safety goggles. Disconnect hoses with extreme caution. HIGH VOLTAGE ELECTRICITY INSIDE PANELS. RISK OF ELECTRICAL SHOCK. Disconnect power before servicing unit. Refer to the instruction manual. TO REDUCE THE RISK OF FIRE, avoid the use of an extension cord because the extension cord may overheat. However, if you must use an extension cord, the cord shall be No. 14 AWG minimum and keep the cord as short as possible. Do not use this equipment in the vicinity of spilled or open containers of gasoline or other flammable substances. Use this equipment in locations with mechanical ventilation that provides at least four air changes per hour or locate the equipment at least 18 inches above the floor. Make certain that all safety devices are functioning properly before operating the unit. Before operating, read and follow the instructions and warnings in the operating manual. Use only with refrigerants R-12, R-22, R-134a, R-401A, R-401B, R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-408A, R-409A, R-410A, R-500, R-502, R-507. This equipment is not designed for any other purpose than recovering refrigerants! Do not mix refrigerant types. CAUTION: SHOULD BE OPERATED BY QUALIFIED PERSONNEL. Operator must be familiar with air conditioning and refrigeration systems, refrigerants and the dangers of pressurized components. ATTENTION! Ce réservoir sous pression contient du frigorigéne liquide. S il est surchargé, ce réservoir peut exploser et causer des blessures ou la mort. Les dispositifs de sécurité exigent l utilisation exclusive de biuteilles de réfrigérant rechargeables agrées. Ceci inclut la piéce Robinair N 17571 (bouteille de 30 lb/14kg). Débrancher avant la maintenance. Pour réduire le risques d incendie, éviter d utiliser une rallonge car elle preésente des risque de surchauffe. En cas d utilisation, il faut une rallonge N 14 AWG min. Ne pas utiliser cet équipement prés de réservoirs d essence debordants ou ouverts. Utiliser cet équipement dns des endroits pourvus d une ventillation mecanique qui prévoit au moins quatre renouvellements d air par heure, ou placer l équipement a 45 cm au moins au-dessus du sol. Utiliser seulement du frigorigéne R-12, R-22, R-134a, R-401A, R-401B, R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R- 408A, R-409A, R-410A, R-500, R-502, R-507. OPERATING NOTES At temperatures exceeding 120 F/49 C, wait 10 minutes Rated in accordance with ARI 740-9 between recovery jobs. R-12, R-134a R-22 R-500 R-502 This equipment has been certified by ARI to meet EPA s 4.50 5.60 3.00 5.00 Liquid Recovery Rate (lbs./min.) minimum requirements for recovery and recycling equipment 0.25 0.33 0.25 0.40 Vapor Recovery Rate (lbs./min.) intended for use with all HCFC-22 appliances and other high 15.00 15.00 15.00 15.00 Shutoff Vacuum (in. Hg) pressure appliances containing less than 200 pounds. U.S. Patents: 5,005,375; 5,203,177; 5,209,077. U.S. and Foreign Patents Pending. Manufactured by Robinair, SPX Corporation, Montpelier, OH 43543-9905 USA 2 1997 Robinair, SPX Corporation

Introduction TABLE OF CONTENTS Glossary of Terms...3 Operating Guidelines...3 Set Up Instructions...4 Figure 1 Top View of Unit...4 Figure 2 Front View of Unit...5 Figure 3 Hose Connections...5 Operating Instructions...6 Recovery Procedures...6 Tank-to-Tank Transfer...7 TANK FULL or HIGH PRESSURE...7 Self-Clearing Procedures...8 Maintenance...9 Replacement Parts...9 Troubleshooting Tips...10 Flow Diagram...12 Wiring Diagram...13 Limited Warranty...15 GLOSSARY OF TERMS A/C-R A/C-R System Unit Tank Air conditioning or refrigeration The air conditioning or refrigeration system being serviced The refrigerant recovery unit The refillable refrigerant tank OPERATING GUIDELINES The voltage at the unit must be +10% of the unit s rated voltage. Extension cords must be a minimum of 14 AWG and kept as short as possible. To minimize mixing of refrigerants, the self-clearing procedure must be performed after each recovery operation. The low side gauge on the unit allows you to monitor system pressure and stop recovery when a deep enough vacuum has been reached. The high side gauge on the unit allows you to monitor the refillable tank pressure. When changing from liquid to vapor, the unit may switch back and forth several times before staying on vapor. You may notice the liquid and vapor lights switching and hear the solenoids opening and closing. This is normal and does not affect the unit or its operation. Present UL approval addresses refrigerants R-12, R-22, R-134a, R-401A, R-401B, R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-408A, R- 409A, R-410A, R-500, R-502 and R-507. Model 25200A Refrigerant Recovery Unit 3

OFF VIBRATION FREE PSI 80 VIBRATION FREE PSI Set Up Instructions TANK FULL VAPOR HIGH PRESSURE ON SYSTEM 40 50 PRESSURE 60 70 TANK 200 PRESSURE 250 300 EQUALIZE ABCO KANTLEAK SELF-CLEAR NORMAL VALVE 1 VALVE 2 ABCO KANTLEAK RECOVER 30 20 10 0 IN. HG. VAC. ROBINAIR 30 120 110 90 100 COMPRESSOR 100 150 50 ROBINAIR 0 500 450 350 400 INST0095 Figure 1 Top View of Unit The unit comes with four 60 Enviro-Guard hoses with ball valves. Either blue hose may be used where blue hose connections are called for, and either red hose may be used for red hose connections. CAUTION! Be sure ball valves on hoses are in the closed position before connecting them. 1. Connect the hoses as follows: Hose Standard End connects to: Ball Valve End connects to: First Blue Hose TANK fitting on unit port on tank First Red Hose TANK VAPOR fitting on unit VAPOR port on tank Second Blue Hose SYSTEM VAPOR fitting on unit SYSTEM VAPOR port Second Red Hose SYSTEM fitting on unit SYSTEM port 2. Connect the yellow overfill cable to the corresponding fitting on the recovery tank. 3. Plug the unit into the proper electrical outlet. The fan will start running immediately. The unit is ready for operation. 4 1997 Robinair, SPX Corporation

Set Up Instructions TANK TANK VAPOR SYSTEM VAPOR SYSTEM INST0099 Figure 2 Front View of Unit Liquid Valve VALVE Vapor VAPOR VALVE Valve Float Cable FLOAT CABLE TYPICAL TYPICAL A/C-R SYSTEM A/C-R SYSTEM Blue Hose RED Red Hose HOSE BLUE HOSE TANK TANK SYSTEM SYSTEM VAPOR VAPOR Red Hose RED HOSE Blue Hose BLUE HOSE Vapor Port (typically low side) VAPOR PORT (TYPICALLY LOW SIDE) Liquid Port (typically high side) PORT (TYPICALLY HIGH SIDE) INST0096 Figure 3 Hose Connections Model 25200A Refrigerant Recovery Unit 5

Operating Instructions RECOVERY PROCEDURE WARNING Always wear safety goggles when working with refrigerants. Use only authorized refillable refrigerant tanks with tank float switch devices. Disconnect hoses with extreme caution! All hoses may contain refrigerant under pressure. Read and follow all warnings at the beginning of this manual before operating the unit. 1. Connect the hoses as described in the Set Up Instructions. 2. Open the and VAPOR valves on the recovery tank. Open the ball valves on all four hoses. 3. Look at the system pressure gauge on the unit to be sure there is refrigerant pressure in the system. If there is no pressure, there is no refrigerant to be recovered. Note: By taking the ambient temperature and using a pressure/temperature chart, you can use this pressure to determine the type of refrigerant in the system. 4. Be sure Valve 2 on the control panel is pointing toward RECOVER. Also, toggle the Valve 2 switch so that the RECOVER light comes on. (See Figure 1.) 5. Turn Valve 1 to EQUALIZE for two to five seconds. This equalizes pressure on the high and low side of the compressor for easier startups. Then turn Valve 1 back to the NORMAL position. (See Figure 1.) 6. Press the COMPRESSOR switch to ON. The compressor light will come on and you will hear the compressor start. (See Figure 1.) A float chamber monitors refrigerant being recovered and automatically adjusts the unit to handle either liquid or vapor refrigerant. This provides for the most efficient recovery. The amber lights on the control panel indicate the state ( or VAPOR) of the refrigerant currently entering the unit. 7. The blue gauge labeled SYSTEM PRESSURE shows the current system pressure throughout the recovery process. When the system pressure reaches an adequate vacuum level, press the COMPRESSOR switch to OFF. The recovery process is complete, but the unit must be cleared before disconnecting all hoses (see Self-Clearing Procedure). 6 1997 Robinair, SPX Corporation

TANK-TO-TANK TRANSFER Operating Instructions If you are recovering refrigerant from one refillable tank into another, the color of the hoses used for SYSTEM and SYSTEM VAPOR may not match the color of the liquid and vapor valves on the tank you are pulling refrigerant from. Be sure the hose for SYSTEM is connected to the liquid valve of the tank and the hose for SYSTEM VAPOR is connected to the vapor valve of the tank. 1. Connect the hoses as follows: Hose Standard End connects to: Ball Valve End connects to: First Blue Hose TANK fitting on unit port on tank refrigerant is being transferred into First Red Hose TANK VAPOR fitting on unit VAPOR port on tank refrigerant is being transferred into Second Blue Hose SYSTEM VAPOR fitting on unit VAPOR port on tank refrigerant is being transferred from Second Red Hose SYSTEM fitting on unit port on tank refrigerant is being transferred from 2. Follow Steps 1 through 7 in the Recovery Procedure. TANK FULL OR HIGH PRESSURE If during the recovery or self-clearing process, the TANK FULL or HIGH PRESSURE light comes on, check that all appropriate valves are open and that the float cable is connected. If they are and either light is still on, follow these steps. 1. Press the COMPRESSOR switch to OFF. 2. Close both valves on the refillable tank and close both valves on the red and blue hoses connected to the tank. 3. Disconnect the red hose, the blue hose and the float cable from the refillable tank. 4. Replace this tank with an empty refillable tank. 5. Reconnect the hoses and the float cable as described in the Set Up Instructions. Then follow the steps in either the Recovery Procedure or the Self-Clearing Procedure. If after completing the above steps, either light is still on, call the Technical Support Line at (800) 822-5561. Model 25200A Refrigerant Recovery Unit 7

Operating Instructions SELF-CLEARING PROCEDURE CAUTION! Do not mix refrigerant types. Always perform the self-clearing procedure after each recovery. Beginning each job with a clean unit will help eliminate mixing of different refrigerant types. 1. Close the ball valves on the red and blue hoses connected to the A/C-R system. Disconnect these hoses from the system s access ports. 2. Close the blue valve on the tank and the ball valve on the blue TANK hose. Disconnect the TANK hose from the tank. 3. Check to be sure the red TANK VAPOR hose is still connected to the red VAPOR fitting on the tank. Both the tank s red VAPOR valve and the ball valve on the red TANK VAPOR hose should be open. 4. Turn Valve 2 on the control panel to SELF-CLEAR. Toggle the Valve 2 switch to the SELF-CLEAR position. (See Figure 1.) 5. Turn Valve 1 on the control panel to EQUALIZE for two to five seconds. This equalizes pressure on the high and low side of the compressor for easier start-ups. Then turn Valve 1 back to the NORMAL position. (See Figure 1.) 6. Press the COMPRESSOR switch to ON. You will hear the compressor start and the compressor light will come on. (See Figure 1.) 7. Let the compressor run for one to two minutes, then press the COMPRESSOR switch to OFF. Unplug the unit from the electrical source. 8. Close the red VAPOR valve on the tank and the ball valve on the red TANK VAPOR hose. Disconnect the TANK VAPOR hose and the float cable from the tank. WARNING Disconnect hoses with extreme caution! All hoses may contain refrigerant under pressure. 9. While the hoses are still connected to the unit, slowly open the ball valve on each hose to relieve any pressure in the hose. Close the ball valves, then disconnect the hoses from the unit. 10. Coil the float cable, power cord and hoses and store them in the builtin storage pocket. 8 1997 Robinair, SPX Corporation

Maintenance Your unit has been designed for minimal maintenance. The compressor should be evaluated for wear after 2,500 hours of use. Call Robinair s Technical Support Line, (800) 822-5561, for the location of an authorized Robinair service center near you. For a minimal cost, you can trade your used compressor for a remanufactured one, which is covered by the same warranty as new compressors. The compressor manufacturer replaces all seals and any other components showing wear, then tests units to new compressor specifications before supplying them to our service centers. REPLACEMENT PARTS 115v 230v Check Valve 1 /8 MP x 1 /8 MP RA19282 RA19282 Check Valve 1 /4 MFL x 1 /8 MP RA19287 RA19287 Check Valve 1 /8 MP x 1 /4 MFL RA19288 RA19288 Ball Valve 2 (3-Way) RA18767 RA18767 Ball Valve 1 (2-Way 90 o ) RA19291 RA19291 Crankcase Pressure Regulator RA19341 RA19341 System Pressure Gauge 41675 41689 Tank Pressure Gauge 41676 41690 Capacitor RA19342 RA19342 Switch Compressor RA19343 RA19343 Switch Recover/Self-Clear RA19060 RA19060 High Pressure Cut-Out RA19104 RA19104 Ball Valve Hose 60 Red RA19344 RA19344 Ball Valve Hose 60 Blue RA19346 RA19346 Relay, DPST RA17459 RA17459 Compressor RA19302 RA19314 Relay, Compressor Start RA19347 RA19348 Indicator Light, Red RA17106 RA19349 Indicator Light, Amber RA17107 RA19351 Solenoid RA19006 RA19088 Fan RA17416 RA17516 Relay, SPDT RA19133 RA19134 Float Chamber RA19337 RA19337 CAUTION! Clean the shroud and/or base with standard soap and water only. Industrial solvents found in most cleaners and degreasers can cause the plastic to crystallize and become brittle. Model 25200A Refrigerant Recovery Unit 9

Troubleshooting Tips Compressor light illuminates but compressor does not start Compressor head presssure is too high Turn Valve 1 to the EQUALIZE position for a couple of seconds before starting Compressor thermal protector has tripped Allow the compressor to cool before re-starting Compressor light does not illuminate and compressor does not start TANK FULL light is on Attach the float cable to the float connector on the tank or replace the full tank with an empty tank HIGH PRESSURE light is on The high side pressure switch has tripped; turn Valve 1 to EQUALIZE for a couple of seconds to reduce the high side pressure COMPRESSOR switch is not on Press the COMPRESSOR switch to ON Compressor runs but does not move refrigerant Valve 2 is not in the RECOVER position Turn Valve 2 to RECOVER The RECOVER light for Valve 2 is not illuminated Toggle the Valve 2 switch to illuminate the RECOVER light The ball valves on the hoses are not open Open the ball valves Valve 1 is in the EQUALIZE position Turn Valve 1 to NORMAL 10 1997 Robinair, SPX Corporation

Troubleshooting Tips During recovery unit shuts off on high pressure The refillable tank valves are not open Open the tank valves Valve 2 is not in the RECOVER position Turn Valve 2 to RECOVER Unit will not pull down to appropriate vacuum level There is a leak in the A/C system Fix the leak Valve 1 is in the EQUALIZE position Turn Valve 1 to NORMAL TOLL-FREE TECHNICAL SUPPORT LINE 1-800-822-5561 (United States and Canada) Model 25200A Refrigerant Recovery Unit 11

Flow Diagram TO SYSTEM VAPOR SOL6 CV4 STRAINER CRANKCASE PRESS. REG. OILLESS COMPRESSOR CV3 HPS SOL4 SOL5 SOL1 SOL2 BV1 CV1 CV2 SYSTEM PRESSURE GAUGE SOL3 CAP TUBE TO SYSTEM INST0406 FLOAT CHAMBER TO TANK BV2 TO TANK VAPOR TANK PRESSURE GAUGE CONDENSER COIL 12 1997 Robinair, SPX Corporation

Wiring Diagram L N 110 V FLOAT SWITCH FLOAT RELAY COMPRESSOR START 1 5 DPST RELAY FLOAT RELAY 4 3 1 3 2 HIGH PRESSURE CUT-OUT 1 1A HIGH PRESSURE R 0 1 2 TANK FULL R FLOAT CHAMBER MOV LIQ/VAP RELAY 1 5 A RECOVERY SOL1 N.C. SOL5 N.C. SOL6 N.C. LIQ/VAP RELAY 2 A VAPOR 4 6 8 4 3 A 5 6 DPST RELAY SOL4 N.C. DPDT SWITCH 1 3 2 A SOL3 N.C. SELF-CLEARING 2 4 DPST RELAY COMPRESSOR ON A SOL2 N.C. 3 4 START 2 RELAY START CAPACITOR COMPRESSOR FAN INST0407 Model 25200A Refrigerant Recovery Unit 13

Notes 14 1997 Robinair, SPX Corporation

Limited Warranty This product is warranted to be free from defects in workmanship, materials, and components for a period of one year from date of purchase. All parts and labor required to repair defective products covered under the warranty will be at no charge. The following restrictions apply: 1. The limited warranty applies to the original purchaser only. 2. The warranty applies to the product in normal usage situations only, as described in the Operating Manual. The product must also be serviced and maintained as specified. 3. If the product fails, it will be repaired or replaced at the option of the manufacturer. 4. Warranty service is provided by our network of authorized service centers. Call the toll-free Technical Support Line, (800) 822-5561, for service authorization and the location of the nearest service center. Do not ship or deliver units to a service center without authorization. Do not ship units to the factory. 5. Warranty service claims are subject to factory inspection for product defect(s). The factory or service center personnel are the sole determiners of warranty coverage. 6. The manufacturer shall not be responsible for any additional costs associated with a product failure including, but not limited to, loss of work time, loss of refrigerant, and unauthorized shipping and/or labor charges. 7. All warranty service claims must be made within the specified warranty period. Proof-of-purchase date must be supplied to the manufacturer. 8. Use of this recovery equipment with unauthorized refrigerants will void our warranty. Authorized refrigerants are listed on the equipment or are available through our Technical Service Department. This Limited Warranty does not apply if: The product, or product part, is broken by accident. The product is misused, tampered with, or modified. The product is used for recovering any substance other than the specified refrigerant type. Model 25200A Refrigerant Recovery Unit 15

CONVERSION TABLE OZ. LBS. 0.5 0.03 1.0 0.06 1.5 0.09 2.0 0.13 2.5 0.16 3.0 0.19 3.5 0.22 4.0 0.25 4.5 0.28 5.0 0.31 5.5 0.34 6.0 0.38 6.5 0.41 7.0 0.44 7.5 0.47 8.0 0.50 8.5 0.53 9.0 0.56 9.5 0.59 10.0 0.63 10.5 0.69 11.0 0.69 11.5 0.72 12.0 0.75 12.5 0.78 13.0 0.81 13.5 0.84 14.0 0.88 14.5 0.91 15.0 0.94 15.5 0.97 16.0 1 lb. Call toll-free Technical Support Line 800-822-5561 in the continental U.S. or Canada. In all other locations, contact your local distributor. To help us serve you better, please be prepared to provide the model number, serial number, and date of purchase. To validate your warranty, you must complete the warranty card attached to your unit and return it within ten days from date of purchase. NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS If your unit needs repairs or replacement parts, you should contact the service center in your area. For help in locating a service center, call the toll free technical support line. Due to ongoing product improvements, we reserve the right to change design, specifications and materials without notice. ROBINAIR SPX Corporation 1224 Robinair Way Montpelier OH 43543-9905 USA Ph. 419-485-5561 Fax 419-485-8300 16 119738 (8/97) Printed In USA 1997 Robinair, SPX Corporation