GESTRA Steam Systems BK 45 BK 45U BK 46. English. Installation Instructions Steam Traps BK 45, BK 45U, BK 46

Similar documents
GESTRA Steam Systems AK 45. Installation Instructions Condensate Drain Valve AK 45

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

AK 45. Installation Instructions Condensate Drain Valve AK 45. A Siebe Group Product 1

GESTRA. GESTRA Steam Systems CB 1... CB 2... Installation Instructions Swing Flap Non-Return Valves CB 1..., CB 2...

Steam trap BK 37 BK 28 BK 29 BK 37 ASME BK 28 ASME BK 29 ASME

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Steam Trap MK 25/2 MK 25/2S

Shut-Off Valve GAV 56F. Original Installation Instructions

Installation Instructions Control Valve with ZK Radial Stage Nozzle

UNA 45 UNA 46 UNA 46A

Non-Return Valve SRK 22A. Original Installation Instructions

Inverted Bucket Steam Trap IB 16A-7

Control Valve with ZK Radial Stage Nozzle ZK 210. Original Installation Instructions English

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

NRGS Installation Instructions Level electrode NRGS A Siebe Group Product 1

CA44, CA44S, CA46 and CA46S Air and Gas Traps

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

NRGS 16-1 NRGS 16-1 S

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Non-Return Valve SRK 22A

Mounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

KTM 50 (DN ) Installation, maintenance and operating instructions

Thermocirc Installation and Maintenance Instructions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

DF1 and DF2 Diffusers

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

PV4 and PV6 Piston Valves

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

S and SF Inverted Bucket Steam Traps

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

AVC32 Carbon Steel Air Vent for Steam Systems

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

AVM7 Stainless Steel Thermostatic Air Vent

Pressure Reducing Valve for Steam Type 2333 A

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

BCVi43 Blowdown Control Valve

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

BDV1 and BDV2 Blowdown / Depressurisation Valves

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

Control Valve ZK 29. Original Installation Instructions

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

Airodyn, BRair and BRoil Compressed Air Drain Traps

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

Pressure Reducing Valve DMV 750 set range: bar

Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0

Regulating valves REG-SA and REG-SB

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

Mounting and Operating Instructions EB EN. Self-operated Pressure Regulators. Type 2335 Excess Pressure Valve with pilot valve

Materials : Stainless steel ASTM A351 CF8M

776 Cryogenic Safety Valve

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

INSTALLATION AND MAINTENANCE INSTRUCTIONS IB - INVERTED BUCKET STEAM TRAPS (IB12 - IBB - IB30 IB35)

Hand-operated regulating valves in stainless steel Types REG-SA SS and REG-SB SS

6301 TYPE CAST IRON SAFETY VALVES

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Engineering Data Sheet

Transcription:

GESTRA Steam Systems BK 45 BK 45U BK 46 EN English Installation Instructions 810437-06 Steam Traps BK 45, BK 45U, BK 46

Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 PED (Pressure Equipment Directive)...4 ATEX (Atmosphère Explosible)...4 Explanatory Notes Scope of supply...5 Description...5 Function...5 Technical Data Corrosion resistance...6 Name plate / marking...6 Component Parts Component parts BK 45, BK 45U, BK 46...7 Key...8 Installation BK 45, BK 45U, BK 46...9 Danger...9 Installation instructions...9 Attention...9 Heat treatment of welds...10 Tools...10 Commissioning Procedure Danger...10 Operation Attention...10

Contents continued Maintenance Page Danger...11 BK 45, BK 45U, BK 46...11 Checking steam traps...11 Cleaning / exchanging Thermovit regulator and nozzle insert...11 Cleaning / replacing strainer...12 Tools...13 Tightening torques...13 Spare Parts BK 45, BK 45U, BK 46...13 Spare parts list...13 Decommissioning Danger...14 Attention...14 Disposal...14

Important Notes Usage for the intended purpose Use steam trap only for discharging condensate or air-venting from steam lines. Use the equipment only within the allowable pressure and temperature ratings and only if the chemical and corrosive influences on the equipment are taken into account. Safety note Installation, commissioning, retrofitting and maintenance work must only be performed by qualified staff who through adequate training have achieved a recognised level of competence. Danger The equipment is under pressure and hot during operation. Risk of severe burns and injuries to the whole body. Installation and maintenance work should only be carried out when the system is depressurized (0 bar) and cold (20 C). The equipment must be isolated and vented from both upstream and downstream pressure before installation or maintenance work is performed. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves when servicing the equipment. Attention The name plate specifies the technical features of the equipment. Do not commission or operate any item of equipment that does not bear its specific name plate. The pressure and temperature ratings on the name plate of the equipment must meet the requirementes of the installation. PED (Pressure Equipment Directive) The equipment fulfills the requirements of the Pressure Equipment Directive PED 97/23/EC. For use with fluids of group 2. The equipment is excluded from the scope of the PED according to section 3.3 and must not bear a CE marking. ATEX (Atmosphère Explosible) The equipment does not have ist own potential source of ignition and is therefore not subject to the ATEX Directive 94/9/EC. Applicable in Ex zones 0, 1, 2, 20, 21, 22 (1999/92/EC). The equipment is not Ex marked. 4

Explanatory Notes Scope of supply BK 45: 1 Steam trap BK 45 1 Installation manual BK 45U: 1 Steam trap BK 45U 1 Installation manual BK 46: 1 Steam trap BK 46 1 Installation manual Description Thermostatic/thermodynamic steam trap with corrosion resistant Thermovit regulator (bimetallic plates) able to withstand waterhammer. With internal strainer and integral non-return valve action. Asbestos-free body gasket (graphite/crni). The standard version discharges the condensate with virutally no banking-up, the version U with approx. 30 K undercooling. Function During start-up of the plant the steam trap is completely open. Cold condensate and air are discharged. As the temperature rises, the bimetallic plates deflect, drawing the stage nozzle towards the closed position. Just before the condensate reaches saturated steam temperature the orifice will be shut off tight. The thermodynamic effect of the stage nozzle chamber assists in the closing process. The steam trap provides automatic air-venting at start-up and during operation of the plant and can also be used for thermal air-venting. 5

Technical Data Corrosion resistance If the equipment is used for the intended purpose, its safety is not impaired by corrosion. Name plate / marking The temperature/pressure ratings are indicated on the trap body or on the name plate. For more information see GESTRA technical documents such as data sheets and the Technical Information. The name plate or the trap body indicate the type and design: Name/logo of the manufacturer Type designation Pressure class PN or Class Material number Max. temperature Max. pressure Direction of flow 4 Stamp on trap body, e. g. specifies the quarter and the year of production 09 (example: 4th quarter 2009) Type of regulator U Type designation Nominal size Max. allowable pressure Max. allowable temperature BK 4... DN 15 CLASS 150 PMA 1960 bar TMO 205 C TMA 425 C at 1300 bar PMX 1900 bar MADE BY GESTRA Pressure rating Max. operating temperature at operating pressure... bar Max. differential pressure Fig. 1 6

Component Parts Component parts BK 45, BK 45U, BK 46 1 2 3 Space required for servicing = 70 mm 4 5 4 6 7 8 9 Fig. 2 0 7

Componen Parts continued Key 1 Hexagon-head screw M 10 x 25 2 Name plate 3 Cover 4 Thermovit regulator 5 Bushing (interference fitted, no spare part) 6 Gasket 40 x 48 x 2 7 Enclosure 8 Strainer 9 Gasket A 24 x 29 0 Sealing plug 8

Installation BK 45, BK 45U, BK 46 When installing the steam trap make sure that the flow arrow on the trap body matches the direction of flow of the steam. Preferred installation of the steam trap with the strainer insert hanging downwards to facilitate cleaning. Other installation orientations are possible, please consult the factory with installation details. We recommend not to insulate the steam trap. Danger The equipment is under pressure and hot during operation. Risk of severe burns and injuries to the whole body. Installation and maintenance work should only be carried out when the system is depressurized (0 bar) and cold (20 C). The equipment must be isolated and vented from both upstream and downstream pressure before installation or maintenance work is performed. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves when servicing the equipment. Installation instructions 1. Make sure that the flow arrow on the trap body matches the direction of flow of the steam. 2. Consider space required for servicing the trap. When the trap is installed a minimum withdrawal space for servicing is required for removing trap parts (see Design, Component Parts BK...). 3. Remove plastic plugs. They are only used as transit protection. 4. Clean end connections. 5.1 Install steam trap with releasable end connections (e. g. flanges). 5.2 For equipment with socket-weld ends or butt-weld ends: Apply arc welding processes 111 and 141 according to ISO 4063 (or equivalent standard). Attention Welded trap installation should only be performed by qualified welders (certified according to DIN EN 287 or equivalent). 9

Installation continued Heat treatment of welds A subsequent heat treatment of the welds is not required. Tools Combination spanner A. F. 16 mm, DIN 3113, Form B Combination spanner A. F. 22 mm, DIN 3113, Form B Torque spanner (US: torque wrench) 20-120 Nm, ISO 6789 Commissioning Procedure Make sure that all connections are subjected to a suitable pressure test according to the pertinent rules and regulations. Danger The equipment is under pressure and hot during operation. Risk of severe burns and injuries to the whole body. Installation and maintenance work should only be carried out when the system is depressurized (0 bar) and cold (20 C). The equipment must be isolated and vented from both upstream and downstream pressure before installation or maintenance work is performed. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves when servicing the equipment. Operation Attention Drain steam trap if the installation is shut down and ambient temperatures 0 C (frost) are to be expected. 10

Maintenance Periodic testing and maintenance of the trap is recommended to ensure proper functioning. Continuous monitoring is recommended for critical applications. Danger The equipment is under pressure and hot during operation. Risk of severe burns and injuries to the whole body. Installation and maintenance work should only be carried out when the system is depressurized (0 bar) and cold (20 C). The equipment must be isolated and vented from both upstream and downstream pressure before installation or maintenance work is performed. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves when servicing the equipment. BK 45, BK 45U, BK 46 GESTRA steam traps BK 45, BK 45U and BK 46 do not require any special maintenance. However, If used in new installations which have not been rinsed check and clean the Thermovit regulator after the commissioning procedure. Checking steam traps You can check the GESTRA steam traps BK 45, BK 45U and BK 46 for correct operation using the GESTRA ultrasonic measuring unit VAPOPHONE or TRAPTEST. We recommend that you perform the measurement at the lower part of the cover 3. Should you detect any loss of live steam clean the steam trap or discard and replace the Thermovit regulator (see table List of Spare Parts). Cleaning / exchanging Thermovit regulator and nozzle insert 1. Unscrew body screws 1 and remove cover 3 from body 7. 2. Unscrew and clean Thermovit regulator 4. 3. Discard and replace Thermovit regulator 4 in case of visible signs of wear or damage (see table List of Spare Parts). 4. Clean body and internals. Clean all gasket surfaces. 5. Apply heat-resistant lubricant to all threads, the seating surfaces of the nozzle insert and the cover (use for instance OKS 217) 6. Screw in Thermovit regulator and tighten with the torque indicated in the table Torques required for tightening. 7. Gasket 6 must be discarded and replaced if there are visible signs of damage. Use the same cover 3. Always discard and replace gasket 6 when using a new cover 3 or the cover of another steam trap (see table List of Spare Parts). 8. Put cover onto body. Tighten body screws 1 alternately and in several steps with the torque indicated in the table Torques required for tightening. OKS 217 is a registered trademark of OKS Schmierstoffe GmbH, München, Germany 11

Maintenance Cleaning / replacing strainer 1. Unscrew sealing plug 0 and strainer 8. 2. Clean strainer, sealing plug and gasket surfaces. 3. Discard and replace strainer and sealing plug in case of visible signs of wear or damage (see table List of Spare Parts). 4. Discard and replace gasket 9 if damaged (see table List of Spare Parts ). 5. Apply heat-resistant lubricant to the thread of the sealing plug (e. g.oks 217). 6. Unscrew sealing plug 0 with gasket 9 and strainer 8. Screw in Thermovit regulator and tighten with the torque indicated in the table Torques required for tightening. Tools Combination spanner A. F. 16 mm, DIN 3113, Form B Combination spanner A. F. 22 mm, DIN 3113, Form B Combination spanner A. F. 30 mm, DIN 3113, Form B Torque spanner (US: torque wrench) 20-120 Nm, ISO 6789 Tightening torques Item Designation Torque [Nm] 4 Thermovit regulator 90 1 Body screws 25 0 Sealing plug 75 All torques indicated in the table are based at a room temperature of 20 C. OKS 217 is a registered trademark of OKS Schmierstoffe GmbH, München, Germany 12

Spare Parts BK 45, BK 45U, BK 46 4 6 8 9 0 Fig. 3 Spare parts list Item Designation Stock code BK 45 Stock code BK 45U Stock code BK 46 4 Thermovit regulator 375 234 375235 375464 8 9 0 Strainer set, cpl. 375 113 375 113 375113 6 Gasket*) 40 x 48 x 2, graphite 375 159 375 159 375159 9 Gasket*) A 24 x 29, stainless steel 375 162 375 162 375162 *) Minimum purchasing quantity 50 items. For smaller quantities please contact your local dealer. 13

Decommissioning Danger The equipment is under pressure and hot during operation. Risk of severe burns and injuries to the whole body. Installation and maintenance work should only be carried out when the system is depressurized (0 bar) and cold (20 C). The equipment must be isolated and vented from both upstream and downstream pressure before installation or maintenance work is performed. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves when servicing the equipment. Disposal Attention Drain steam trap if the installation is shut down and ambient temperatures 0 C (frost) are to be expected. For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. 14

For your notes. 15

GESTRA Agencies all over the world: www.gestra.de España GESTRA ESPAÑOLA S.A. Luis Cabrera, 86-88 E-28002 Madrid Tel. 0034 91 / 5 15 20 32 Fax 0034 91 / 4 13 67 47; 5 15 20 36 E-mail: aromero@flowserve.com Great Britain Flowserve GB Limited Abex Road Newbury, Berkshire RG14 5EY Tel. 0044 16 35 / 46 99 90 Fax 0044 16 35 / 3 60 34 E-mail: gestraukinfo@flowserve.com Polska GESTRA Polonia Spolka z.o.o. Ul. Schuberta 104 PL - 80-172 Gdansk Tel. 0048 58 / 3 06 10-02 0048 58 / 3 06 10-10 Fax 0048 58 / 3 06 33 00 E-mail: gestra@gestra.pl Portugal Flowserve Portuguesa, Lda. Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 00351 22 / 6 19 87 70 Fax 00351 22 / 6 10 75 75 E-mail: jtavares@flowserve.com Italia Flowserve S.p.A. Flow Control Division Via Prealpi, 30 l-20032 Cormano (MI) Tel. 0039 02 / 66 32 51 Fax 0039 02 / 66 32 55 60 E-mail: infoitaly@flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel. 001 502 / 267-2205 FaxL 001 502 / 266-5397 E-mail: FCD-Gestra-USA@flowserve.com GESTRA AG P. O. Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Telephone 0049 (0) 421 / 35 03-0 Fax 0049 (0) 421 / 35 03-393 E-Mail gestra.ag@flowserve.com Internet www.gestra.de 810437-06/12-2009cm (808837-00) GESTRA AG Bremen Printed in Germany 16