BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

Similar documents
TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

Thermocirc Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

AVM7 Stainless Steel Thermostatic Air Vent

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

AVC32 Carbon Steel Air Vent for Steam Systems

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

DF1 and DF2 Diffusers

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

TSS21 Sealed Thermostatic Steam Tracer Trap

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

PV4 and PV6 Piston Valves

CA44, CA44S, CA46 and CA46S Air and Gas Traps

S and SF Inverted Bucket Steam Traps

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

BPT13 Balanced Pressure Thermostatic Steam Traps

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

CVS10 Sanitary Check Valves

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

CA10S, CA14 and CA14S Air and Gas Traps

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

BDV1 and BDV2 Blowdown / Depressurisation Valves

PC10HP Pipeline Connector (ASME 600)

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

CS10-1 Stainless Steel Clean Steam Separator

DCV6 Disc Check Valve

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

Dri-Line Mk3 Monnier Compressed Air Drain Trap

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

CP10 Sensor Installation and Maintenance Instructions

TP1 and TP2 Temporary Cone Shaped Strainers

SRV2S Pressure Reducing Valve

SRV66 Sanitary Pressure Reducing Valve

PC3_ and PC4_ Pipeline Connectors

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

MFP14-PPU (Vented) Automatic Packaged Pump Units

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

BCV31 DN40 - Blowdown Control Valve

Installation and Maintenance Manual

MF2M Monnier Miniature Compressed Air Filter

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

CA44 and CA44S Carbon Steel Air and Gas Traps Flanged DN15 to DN25

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

BRV71 and BRV73 Pressure Reducing Valves

ML3M Monnier Miniature Compressed Air Lubricator

BCV31 DN20 - Blowdown Control Valve

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

FV Flash Vessel Installation and Maintenance Instructions

APT14, APT14HC and APT14SHC Spares 2

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

TW Temperature Control Valve

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Blowdown vessels Meeting the requirements of HSE PM60

CA14 SG Iron Air and Gas Trap ½" and ¾" (Screwed)

Manual Actuated Boiler Blowdown Valves

BCVi43 Blowdown Control Valve

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

DP17, DP17E, DP17G, DP17R, DP17Y and DP27G Pilot Operated Pressure Reducing Valves

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Spirax Compact FREME Flash Recovery Energy Management Equipment

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

QuickHeat TM Packaged Heat Exchanger Solutions

M111 Spiraflo Transducer

Transcription:

1810050/4 IM-P181-03 ST Issue 4 BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Printed IM-P181-03 in the ST UK Issue 4 Copyright 20021

1 General safety information Safe operation of these units can only be guaranteed if they are properly installed, commissioned and maintained by a qualified person (see Secton 11 of the attached Supplementary Safety Information) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. Isolation Consider whether closing isolating valves will put any other part of the system or personnel at risk. Dangers might include: isolation of vents and protective devices or alarms. Ensure isolation valves are turned off in a gradual way to avoid system shocks. Pressure Before attempting any maintenance consider what is or may have been in the pipeline. Ensure that any pressure is isolated and safely vented to atmospheric pressure before attempting to maintain the product, this is easily achieved by fitting Spirax Sarco depressurisation valves type DV (see separate literature for details). Do not assume that the system is depressurised even when a pressure gauge indicates zero. Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns and consider whether protective clothing (including safety glasses) if required. Disposal These products are recyclable. No ecological hazard is anticipated with the disposal of these products providing due care is taken. 2 IM-P181-03 ST Issue 4

2 General product information 2.1 General description The BTD52L is manufactured from 316L stainless steel specifically for mains drainage applications in clean steam systems. Optional extras An insulating cover is available at extra cost to prevent the trap being unduly influenced by excessive heat loss when subjected to low ambient temperature, wind and rain etc. Note: For additional information see Technical Information Sheet TI-P181-01. 2.2 Sizes and pipe connections ¼", 3 /8", ½" screwed BSP or NPT. ½" O/D x 16 swg (0.065") wall thickness tube end. DN 11850 (Series 1) tube ends 12 mm O/D x 1.0 mm wall thickness (DN10) 18 mm O/D x 1.0 mm wall thickness (DN15) ISO 1127 (Series 1) tube ends 17.2 mm O/D x 1.6 mm wall thickness (DN10) 21.3 mm O/D x 1.6 mm wall thickness (DN15) ½" Sanitary clamp compatible connections (DN15) Fig. 2 ½" Tube ends Fig. 1 Screwed Fig. 3 Sanitary clamp ends IM-P181-03 ST Issue 4 3

2.3 Limiting conditions Body design conditions PN16 PMA - Maximum allowable pressure 16 bar g (232 psi g) TMA - Maximum allowable temperature 450 C (842 F) PMO - Maximum operating pressure 10 bar g (145 psi g) TMO - Maximum operating temperature 450 C (842 F) Designed for a maximum cold hydraulic test pressure of: 24 bar g (348 psi g) Note: Minimum pressure for satisfactory operation is 0.25 bar g (3.6 psi g). 2.4 Operating range Temperature C 450 400 300 200 100 0 0 Steam saturation curve 2 4 6 8 10* 12 14 16 Pressure bar g The product must not be used in this region. * PMO Maximum operating pressure recommended for steam service. PMOB Maximum operating back pressure is 80% of the upsteam pressure. 4 IM-P181-03 ST Issue 4

3 Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation. 3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2 Determine the correct installation situation and the direction of fluid flow. 3.3 Remove protective covers from all connections. 3.4 Always ensure the correct tools, safety procedures and protective equipment are used at all times. 3.5 The trap should be installed in the horizontal plane, preferably preceded by a small drop leg. For freeze proof installation, or where horizontal fitting is not possible. The BTD52L may be installed vertically, but the service life may be affected. 3.6 Suitable isolation valves must be installed to allow for safe maintenance and trap replacement. 3.7 Where the trap discharges into a closed return system, a non-return valve should be fitted downstream to prevent return flow. Remove all packaging and protective covers and ensure all connections ports are clear from obstruction. 3.8 Always open isolation valves slowly until normal operating conditions are achieved - this will avoid system shocks. Check for leaks and correct installation. Note: If the trap is to discharge to atmosphere ensure it is to a safe place. The discharging fluid may be at a temperature of 100 C (212 F) 4 Commissioning After installation or maintenance ensure that the system is fully functional. Carry out tests on any alarms or protective devices. 5 Operation The thermodynamic steam trap will discharge condensate with a blast type action at a few degrees below steam saturation temperature, due care must be given to the site of the discharge. IM-P181-03 ST Issue 4 5

6 Maintenance Note: Before actioning any maintenance programme observe the 'Safety information' in Section 1. 6.1 General maintenance Before undertaking any maintenance on the trap it must be isolated from both the supply line and return line and any pressure allowed to safely normalise to the atmosphere. The trap should then be allowed to cool. When reassembling, ensure that all joint faces are clean. 6.2 How to service: - Note; refer to Figure 4, page 7, for part number location. - Remove the insulating cover (4) if fitted. - Unscrew the cap (2) using a spanner. Do not use Stillsons or a wrench of similar type which may cause distortion of the cap. - If the disc (3) and body seating surfaces (1) are only slightly worn they can be refaced by lapping individually on a flat surface such as the surface plate. A figure of eight motion and a little grinding compound such as Carborundum Co's Compound I.F. gives the best results. If the wear is too great to be rectified by simple lapping, the seating faces on the body must be ground flat and then lapped and the disc replaced with a new one. The total amount of metal removed in this way should not exceed 0.25 mm (0.01"). - When reassembling the disc (3) is normally placed in position with the grooved side in contact with the body seating face. - Screw on the cap (2); no gasket is required but a fine smear of Molybdenum Disulphide grease should be applied to the threads. Tighten the cap (2) to the recommended tightening torque (see Table 1). Warning: When torquing or untorquing the cap (2), some support should be given to the body of the trap to prevent over stressing and/or distortion of the end connections and system pipework. Table 1 Recommended tightening torques Warning: When torquing or untorquing the cap (2), some support should be given to the body of the trap to prevent over stressing and/or distortion of the end connections and system pipework. or Item Part N m (Ibf ft) mm 2 Cap 36 A/F 115-130 (85-96) 6 IM-P181-03 ST Issue 4

7 Spare parts The spare parts available are shown in heavy outline. Parts drawn in broken line are not supplied as spares. Available spares Disc 3 Insulating cover 4 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of trap. Example: 1 - Disc for the Spirax Sarco ½" BSP Spirax Sarco BTD52L thermodynamic steam trap. 4 2 (not an available spare) 3 1 (not an available spare) Fig. 4 IM-P181-03 ST Issue 4 7

8 IM-P181-03 ST Issue 4