Vane Flow Switches Colima FLU Series

Similar documents
TP1 and TP2 Temporary Cone Shaped Strainers

TSS21 Sealed Thermostatic Steam Tracer Trap

DF1 and DF2 Diffusers

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

Dri-Line Mk3 Monnier Compressed Air Drain Trap

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

PV4 and PV6 Piston Valves

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

CP10 Sensor Installation and Maintenance Instructions

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

Colima TOR Magnetic Level Switches

MF2M Monnier Miniature Compressed Air Filter

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

FV Flash Vessel Installation and Maintenance Instructions

DCV6 Disc Check Valve

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

Manual Actuated Boiler Blowdown Valves

ML3M Monnier Miniature Compressed Air Lubricator

CVS10 Sanitary Check Valves

AVM7 Stainless Steel Thermostatic Air Vent

APT14, APT14HC and APT14SHC Spares 2

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

AVC32 Carbon Steel Air Vent for Steam Systems

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

CA44, CA44S, CA46 and CA46S Air and Gas Traps

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

Spirax Compact FREME Flash Recovery Energy Management Equipment

SRV66 Sanitary Pressure Reducing Valve

Airodyn, BRair and BRoil Compressed Air Drain Traps

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

CS10-1 Stainless Steel Clean Steam Separator

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

TW Temperature Control Valve

S and SF Inverted Bucket Steam Traps

BCV31 DN40 - Blowdown Control Valve

PC10HP Pipeline Connector (ASME 600)

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

Colima Visco and Colima Viscorol Magnetic Level Indicators Installation and Maintenance Instructions

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

MFP14-PPU (Vented) Automatic Packaged Pump Units

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

SRV2S Pressure Reducing Valve

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

BPT13 Balanced Pressure Thermostatic Steam Traps

BRV71 and BRV73 Pressure Reducing Valves

CA10S, CA14 and CA14S Air and Gas Traps

M111 Spiraflo Transducer

BCV31 DN20 - Blowdown Control Valve

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

RJ check valves Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

QuickHeat TM Packaged Heat Exchanger Solutions

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

SCA Series Inverted Bucket Steam Traps

Thermocirc Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

BCVi43 Blowdown Control Valve

BDV60 Blowdown Vessel Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

Transcription:

3.797.5275.200 CH Issue 2-2016 Vane Flow Switches Colima FLU Series Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation and Maintenance 4. Spare parts E X P E R T I S E S O L U T I O N S S U S T A I N A B I L I T Y Copyright 2013

1. General safety information Safe operation of these products can only be guaranteed if they are properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. The products comply with the requirements of the European Pressure Equipment Directive: 2014/68/EU (PED) falling within category 'SEP'. It should be noted that products within this category are required by the Directive not to carry the mark. Products intended for use in the Naval and Marine sectors are RINA, and M.M.I (Italian navy) approved. i) The products have been specifically designed for use on steam, compressed air and inert industrial gases which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 2 3.797.5275.200

1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns and consider whether protective clothing (inlcuding safety glasses) is required. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 3.797.5275.200 3

1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 350 C. Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Safety information (Specific to the product) For any safety requirements relating to particular components and / or materials used in the product construction, please refer to installation and maintenance instructions below. 1.16 Disposal This product is recyclable. No ecological hazard is anticipated with the disposal of this product providing due care is taken. 1.17 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 3.797.5275.200

2. General product information 2.1 Description Magnetically activated vane type flow switches for monitoring gas or liquid flow rates are present in most industrial applications. The flow switches can be equipped with electrical contacts, SPDT or DPDT micro switches along with different protective housings and with optional two-colour visual indicator to suit most environmental and safety conditions. 2.1.1 Applications - Protects pumps, motors and other equipment against low or no flow - Controls sequential operation of pumps - Automatically starts auxiliary pumps and engines - Stops liquid cooled engines, machines and processing when coolant flow is interrupted - Shuts down burner when air flow through heating coil fails 2.1.2 Operating principle Two oscillating magnets on the same axis, one integral with the vane and one integral with the electrical equipment, repel each other reciprocally through a non-magnetic material flange. The flange separates the housing, containing the electrical equipment, from the vane that is inserted in the pipe. The vane in absence of flow is maintained in its resting position by balance weight and repulsion between the two magnets that face each other with the same polarity. When the flow pushes the vane, the integral vane magnet moves and the magnetic field pushes the integral switch magnet. The switching of the electrical contact is quick and reliable. 2.1.3 Mounting The Flu flow switches can be installed horizontally, directly into a pipe, or in a dedicated chamber connected between two pipes. Several type of flanges are available upon customer request. 3.797.5275.200 5

2.2 Materials No. Part Material 1 Housing ALU + Rilsan 2 Cover ALU + Rilsan 3 Indicator Plexiglass 4 Microswicth Omron Z-15GW4-B 5 Screw AISI 304 6 Magnet Sm Co 7 Flange AISI 304 8 Magnet Sm Co 9 Counter weight AISI 304 10 Vane AISI 304 2 3 1 4 5 6 7 8 10 9 6 3.797.5275.200

2.3 Design conditions TMA PMA Maximum allowable temperature Maximum allowable pressure Steel Steel -20 C to + 150 C with cooling extension -20 C to + 350 C Colima's flange < 16 bar g flange sized according to rating < 100 bar g 2.4 Models FLU A Gas flow switch, with IP 67 aluminum housing. Can not be fitted directly on the pipes but before the the cooling battery. FLU O Liquid flow switch, with IP 67 aluminum housing and two-colour visual indicator (optional). 3.797.5275.200 7

3. Installation and Maintenance Note: Before actioning any installation or maintenance work observe the 'Safety information' in Section 1. Refering to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation. Check: materials, pressure and temperature to ensure compatibility of the product with the required application. Also make sure that the ambient temperature in proximity of the device is between the values reported on the label (-20-40 C). Remove protective covers from all connections and the protective film from the name-plate. 3.1 Assembly The Colima FLU magnetic flow switches are delivered packed. 3.1.1 Fit the flow switch into the tank paying attention to avoid any damage at vane. Any damage can interfere with the correct operation of the unit. 3.1.2 Place the supplied gasket between the flanges. 3.1.3 Fix the flanges with bolts. Firmly secure the fixing by tightening the flange bolts. 3.1.4 In case of threaded connection, tighten the instrument and place it in the direction indicated by the arrow on the housing base. Caution: Always ensure that correct earthing of the equipment is carried out. Specific points are set inside and outside the housing. Caution: These products should only be used for what they are designed for. Anything outside of the stipulated application range may be subject to unforeseen and dangerous circumstances and full responsibility will be with the installer. 3.2 Electrical equipment and housings for Colima FLU series flow switches The electrical equipment for the FLU series level switches comprises a support and a contact. The oscillating element includes a magnet whose south pole points towards the flange that separates the electrical equipment from the liquid or gas contained in the pipe. According to the pressure on the vane provided by the liquid or gas flow in the pipe, the vane works by pivoting a sealed cartridge containing a magnet, with south polarity on the end towards the flange. As the two magnets on the two oscillating devices repel each other, they are never in line on the same axis. Consequently, the status of the electrical equipment switches from the normally open (NO) to normally closed (NC) position or vice versa. 8 3.797.5275.200

Requisiti dei contatti elettrici Standard SPDT Contact Standard microswitches are recommended for general purpose Contact resistance: 15 mohm Max (Initial value) Mechanical life: >106 Electrical life: >105 V ~ A = Load 250 15 0,25 Resistive 15 0,03 Inductive 125 15 0,5 Resistive 15 0,05 Inductive 30 NA 6 Resistive NA 5 Inductive SPDT execution COM (Common) DPDT execution (two simultaneous SPDT contacts) COM (Common) NC (Normally Closed) NO (Normally Open) NO (Normally Open) NC (Normally Closed) 3.797.5275.200 9

3.3 Disassembly Before disassembly of the flow switch disconnect or isolate any electricity supply or circuit and depressurize the pipe. Warning: do not disassemble the level switch before the pipe has been emptied. 3.3.1 Open the housing. 3.3.2 Disconnect the electric circuit cables. Close the housing. 3.3.3 Unscrew the connection bolts. 3.3.4 Extract the instrument from its slot paying attention to avoid any damage to the vane. Periodical inspections are necessary to guarantee complete efficiency of the unit. A regular maintenance programme starting from its initial installation is recommended. The suggested precautions are important to obtain the best operating conditions of the level control. The instrument does not require preventive maintenance, however it is recommended that from time-to-time a check of the liquid fluidity is actioned to avoid any suspensions or deposits that can influence wetted parts. 4. Spare parts The available spare parts are detailed below. No other parts are supplied as spares. Available spares Contacts To replace the contact: 1. Open the housing and remove the visual indicator (if present). 2. Disconnect cables from the electrical circuit, taking note of their position on the microswitch. 3. Unscrew the screws (1) and remove the block with the switch. 4. Unscrew the screws (2) and remove the switch from the bracket. 5. Place the new switch onto the bracket and secure it by tightening the screws (2). 6. Place the block with the switch and secure it by tightening the screws (1). 7. Reconnect the electrical cables and close the housing after repositioning the visual indicator (if present). 2 1 10 3.797.5275.200

How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and serial number of the unit which is indicated on the name-plate: Example: N 1 off Contact for flow switch for Spirax Sarco Colima FLU series having DN50 flanged ASME 150 RF connections - Serial number 123456. 3.797.5275.200 11

SERVICE For technical support, please contact our local Sales Engineer or our Head Office directly: Spirax Sarco S.r.l. - Technical Assistance Via per Cinisello, 18-20834 Nova Milanese (MB) - Italy Tel.: (+39) 0362 4917 257 - (+39) 0362 4917 211 - Fax: (+39) 0362 4917 315 E-mail: support@it.spiraxsarco.com LOSS OF GUARANTEE Total or partial disregard of above instructions involves loss of any rights to guarantee. Spirax-Sarco S.r.l. - Via per Cinisello, 18-20834 Nova Milanese (MB) - Tel.: 0362 49 17.1 - Fax: 0362 49 17 307 3.797.5275.200 CH Issue 2-2016.09