Testing Procedures & Trouble Shooting Guide Reduced Pressure Zone Assembly (1/2, 3/4", 1, 1 1/4, 1 1/2" & 2 )

Similar documents
Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

S & M Water Consultants

WW-720. Pressure Reducing Control Valve

WW-720. Pressure Reducing Control Valve

WW-730. Pressure Sustaining/Relief Control Valve

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Pressure Reducing Control Valve w/ Hydraulic Check Feature

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

Installation Troubleshooting Maintenance Instructions Installation / Start-up

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

MEGR-1627 Instruction Manual

553 Series.

Series 867. Reduced Pressure Zone Assemblies " 3" (65 80mm)** INDEX. Testing INSTALLATION INSTRUCTIONS WARNING NOTICE NOTICE !

OPERATING AND MAINTENANCE MANUAL

Model 420-HY Pressure Regulating Hydrant Valve

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Bermad Pressure Reducing. Model: 42T

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

INSTALLATION OPERATION MAINTENANCE

SINGER MODEL 106/206-RPS-L&H

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Model 1800 PFM Series Regulator For Constant Outlet Pressure Precise Fixed Factor Measurement From 0.5 to 30 PSIG

ZW209 & ZW209BP LEAD-FREE*

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Model: 43T. Bermad Pressure Relief Valve

Lesson 6: Flow Control Valves

Easy Nest Kits. Installation Suggestions

Serie ECO 3T. Threaded end back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection E U R O P E

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Pressure Reducing Valve for Steam Type 2333 A

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

CLASS TLP Pressure Reducing Valve

Pressure Dump Valve Service Kit for Series 3000 Units

INSTALLATION INSTRUCTIONS

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Discharge Relief Valve Operation & Maint.

HPIC D Hydrostatic Test Pump PRODUCT INFORMATION AND OPERATING INSTRUCTIONS

FUNDAMENTALS OF PRESSURE REGULATORS ROBERT BENNETT MANAGER OF TRAINING ELSTER AMERICAN METER

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

SYSTEM REGULATING VALVES PRESSURE RELIEF VALVE - SRV BRASS & S/STEEL ADJUSTABLE

627 Series Pressure Reducing Regulators

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

Model Series 62 Constant Differential Relay

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

CAST IRON VALVES FLOAT VALVE

Model GPR Primary Pressure Regulating Valve. Instruction Manual

CASH VALVE TYPE KP BACK PRESSURE VALVES

Installation and operating instructions KEMPER Backflow Preventer BA Figure 361

REDUCED PRESSURE ZONE DEVICES SERIES PRODUCT CODES OPERATION HIGH HAZARD RATING. 15mm - 50mm FEATURES APPLICATION DESCRIPTION

Installation, Operation and Maintenance Manual for Back Pressure Regulator

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

Installation Instructions

Copyright, 2005 GPM Hydraulic Consulting, Inc.

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

Halsey Taylor Owners Manual STOP!

TECHNICAL DATA. than the water inlet pressure to the concentrate

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

K Page 1 of 48 Air Intake - Pg. 17

Anti-flood device Model B-1

Model 1800 PFM Series Regulator. Technical Bulletin

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity)

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

BACK PRESSURE / SUSTAINING

CM MBC & CM MBC PARTS LIST

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

D05 Pressure Regulating Valves

INSTALLATION AND OPERATION MANUAL CHEMICAL BYPASS FEEDER General Instructions Regarding All Models

BACK PRESSURE / SUSTAINING

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Direct Operated Precision Regulator Modular Style. Standard Specifications

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

C 10 Pressure Reducing Valve

Operating Instructions Model and Hydrostatic Test Pump

Model Secure-Gard Pilot Operated Vent Valve SECTION II. Remove all packing material inside and outside of the valve prior to installation.

HIGH RATE BASKET STRAINER

RS(H)20, 25 USER MANUAL

Pressure Dump Valve Service Kit for Series 2300 Units

Model 141-A Regulators

MEGR-1912 Instruction Manual

TECHNICAL INSTRUCTIONS

DynaPak Gas Sampler S Y S T E M S U P P O R T M A N U A L DP-2000

Hydraulic Punch Drivers

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

DIVE RESCUE INTERNATIONAL, INC. Divator MKII Parts Price List

pressure reducing valves

Serie ECO 3F. Flanged back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

SINGER SOLUTIONS: A VISUAL GUIDE TO TROUBLESHOOTING YOUR VALVES

DynaPak 2000L System Support Manual Version

FILTER BYPASS CONTROL

Installation Instructions

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Installation Instructions

MT-239-E ENGLISH PRESSURE REGULATOR STAFLUX MINI TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

STATEMENTS OF FACT BENCH BG-4 CONTEST. 1. A positive pressure leak could be caused by a leakage in or at device components.

Transcription:

Testing Procedures & Trouble Shooting Guide Reduced Pressure Zone Assembly (1/2, 3/4", 1, 1 1/4, 1 1/2" & 2 ) First Check Valve Test 1) Bleed all test cocks. First open test cock 4, make sure it is slightly open and water is flowing. Then open TC3, then TC2, then TC1 until they are completely bled. Close all TC s in the reverse order. 4) Open TC3 fully, then open the low side needle valve and let the water run out. 6) Attach a bypass hose from the high side bleed needle valve to TC4. Open TC4.

7) Open the low side bleed needle valve. Allow the pressure to build and close the low side needle valve. When the reading settles, this is the pressure differential across CV1, record the value. Relief Valve Test 1) Bleed all test cocks. First open test cock 4, make sure it is slightly open and water is flowing. Then open TC3, then TC2, then TC1 until they are completely bled. Close all TC s in the reverse order. 4) Open TC3 fully, then open the low side needle valve and let the water run out. 6) Open the high side needle valve and bleed the high side hose. 7) Close SOV2. 8) Close the high side needle valve. Once the test kit has pressurized, slowly close the low side needle valve. 9) If test kit pressure drops and the relief valve opens, CV1 is leaking. If the Test kit pressure holds, proceed to step 10. 10) Attach a bypass hose from the low side bleed needle valve to the high side bleed needle valve. 11) Open the high side needle valve one turn, then slowly open the low side needle valve onequarter turn. Record the pressure when the water begins to discharge from the relief valve. Second Check Valve Test 1) Bleed all test cocks. First open test cock 4, make sure it is slightly open and water is flowing. Then open TC3, then TC2, then TC1 until they are completely bled. Close all TC s in the reverse order.

4) Open TC3 fully, then open the low side needle valve and let the water run out. 6) Open the high side needle valve and bleed the high side hose. 7) Close SOV2. 8) Attach a bypass hose from the high side bleed needle valve to TC4. Open TC4. 9) Open the low side bleed needle valve. Allow the pressure to build beyond the recorded differential for CV1 and close the low side needle valve. 10) Open the high side bleed needle valve. If the pressure holds, CV2 is sealed properly.

BEECO FRIENDLY REDUCED PRESSURE ZONE (½ 2 ) Test Cock Lid Lid O-Ring First Check Valve Plastic Spacer Second Check Valve Ball Valve Cast Bronze Body Relief Valve BEECO CHECK VALVE (½ 2 ) Relief Check Valve Check Valve Body Spring Check Valve Disc Retainer Cap Disc Screw Check Valve O-Ring Check Valve Base

BEECO RELIEF VALVE (½ 2 ) Seat O-Ring Seat Sub-Assembly Spring Screw Disc Stem Diaphragm Trouble Shooting Guide Piston Piston O-Ring Problem No flow Low flow Leaking Check Valves Constant drip or drain from vent Relief valve fails to open during test Intermittent drip or "dump" from vent Probable Causes Device installed backwards. Upstream or downstream gate valves not open. Clogged strainer or clogged device. Low supply pressure. Pressure drop through the device. Device's gate valves not opened completely. Debris on seat area or seal Damaged seat area Damaged seal If occurs when no call for water only, indicates fouled first check valve. If under flow, indicates that either relief valve mechanism is malfunctioning or first check is fouled. Can be verified by test. Blockage in relief valve supply tubing or internal passage. Physical blockage of relief valve. Device is in a flow condition due to leaking downstream gate valve. Relief valve mechanism is malfunctioning. Fluctuating supply pressure.