COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE SUMMARY

Similar documents
SUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE

SF 6. Gas Handling. DILO. Sustainably tight. Made in Germany

Axpo Power Ltd. 2) GE Grid Solutions

TECHNICAL PAPER PRESENTATION

Environmental and Safety Concerns with SF 6 Gas

Innovation Electrical Industry

Inert Air (N2) Systems Manual

Insulating Gas Management Program

Neil Kane Managing Director EMT UK

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions.

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

Type CAP. CapSwitcher. Capacitor Switching Device kv 38 kv INSTALLATION & INSTRUCTION MANUAL

SF 6 Product Guide. Gas Analysis Instruments and Accessories

Intrinsic safety 101 hazardous locations

Gas density monitor With integrated transmitter Model GDM-100-TI

SF 6. Gas Handling. DILO. Sustainably tight. Made in Germany

Guidelines to the standard IEC60601

23.1 Functions, Basic Configuration, and Interfaces

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC

PRC CO ² -LASER PRESENTATION

CON ACT. Parts and Service News For the Power Transformer and

This test shall be carried out on all vehicles equipped with open type traction batteries.

SERIES 10. Pilot Operated Tank Blanketing Valve, 2" PROTECTOSEAL.

Review of the Hall B Gas System Hardware. George Jacobs

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Finding leaks in Main Cryogenic Heat Exchangers without shutdown

Point level switches for safety systems

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

Procedure of Xenon Transfer

TABLE OF CONTENTS PART 2 - CONFINED SPACES

Maintenance handbook

This multi-functional device allows the determination of up to six quality parameters with only one measurement:

MANUAL DIRECT PURGE OPTION. UNION Instruments GmbH CWD2005 PLUS. General information, safety standards and regulations for direct purge option

Leakage Current Testing Is it right for your application?

Pressure Systems Safety Regulation

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Module 6. Tightness Testing

Mobile Breathing Air Systems

Medical Oxygen Concentrator Systems. Generate gases on site generate savings

Oxygen Generating Systems Ozone Medical Welding Glassblowing Aquaculture Pulp & Paper Wastewater

UTAS EH&S INSTRUCTION No. 036 June 2012 Revision No. 3. Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard)

Power Unit 075. Maintain Substation Circuit Breakers

CO 2. (R744) Service Station Presentation. Contents. Goals Basic functions Specification Recovery R477 Vacuum Charge Safety Other features Prototype

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

Respiratory Protection Self Inspection Checklist

Steam penetration in steam sterilization processes

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

GAS INSULATED SWITCHGEAR

Respiratory Protection Self-Inspection Checklist

RDK-408D2 Cold Head. Technical Manual. SHI-APD Cryogenics Inc Vultee Street Allentown, PA U.S.A. Revision A: September 2005

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

Field Instruction Storage, Handling, Transport and Disposal of Sulphur Hexafluoride (SF6) Gas

Breakdown Performance of Vacuum Circuit Breakers Using Alternative CF 3 I-CO 2 Insulation Gas Mixture

Installation, use and maintenance instructions. Gas burner (5)

Selection of Electrical PPE Tables

Petro-Chemical & Analyzer Sampling Systems

System Pressure Manager Standard & System Pressure Manager Plus

What I have learned about SF 6 gas testing.a Practical explanation

The Experts in Vacuum Solutions

VI.D AIR DISCONNECT SWITCHES

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

Best Practice Guide, Servomex 2700

R E D I C O N T R O L S

ACV-10 Automatic Control Valve

! Warning, refer to accompanying documents.

IDEM Indiana Department of Environmental Management Office of Land Quality P.O. Box 6015 Indianapolis, IN OLQ PH: (317)

PSSI 10 Plant and Apparatus Containing Dielectric Gas

CHAPTER 2: ELECTRICAL SAFETY

AN EXPERIMENTAL AND ANALYTICAL STUDY OF PLASMA CLOSING SWITCHES FILLED WITH ENVIRONMENTALLY FRIENDLY GASES

BPZM-MRD Nitrogen Injection System

DIAPHRAGM VACUUM PUMPS AND COMPRESSORS

ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING

LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES

DIAPHRAGM VACUUM PUMPS AND COMPRESSORS

4 qwer 2/2 3/2 4/2. Intrinsically Safe. Air and Inert Gas Intrinsically Safe Valves Brass, or Stainless Steel Bodies 1/4" to 1" NPT SERIES.

EXPERIENCE WITH A PRE-SERIES SUPERFLUID HELIUM TEST BENCH FOR LHC MAGNETS

Instrumentation & Data Acquisition Systems

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Petro-Chemical & Analyzer Sampling Systems

MIL-STD-883G METHOD

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

DIAPHRAGM VACUUM PUMPS AND COMPRESSORS

Inspection Recommendations

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

High-performance submersible pressure transmitter For level measurement Model LH-10

Supplementary Operator s Manual 42/24-14 EN Rev. 3

6900 Maintenance Instruction System Flush

Lockout/Tagout Training Overview. Safety Fest 2013

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

Lubricating Oils Hydraulic Oils Turbine Oils Cutting and Cooling Mineral Oils Compressor Oils Synthetic Fluids Insulating Oils Quenching Oils

Entry to these spaces must be rigorously controlled to prevent serious injury or death.

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Transcription:

COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE R. L. Middleton, P. Eng. Manitoba Hydro, Winnipeg, Canada SUMMARY Very low temperatures stress a circuit breaker in a complex manner. Mixed-gas circuit breakers were developed for use at temperatures as low as -50 o C. These breakers utilize a gas mixture of SF 6 and CF 4 or SF 6 and N 2 to prevent condensation of the SF 6 gas and have been type tested at -50 o C to ensure travel characteristics, operating times, and gas tightness are acceptably affected. Today s mixed-gas circuit breakers offer excellent cold-weather performance and provide the reliability needed for most utility users systems. 1. INTRODUCTION Manitoba Hydro is a Canadian electric utility located in the province of Manitoba. It is the fourthlargest electric utility in Canada, with a generating capacity of 5100 MW. The bulk of this energy is produced by hydro-electric generating stations located on the Nelson River in northern Manitoba. The power is moved from the north on a high-voltage direct current (HDVC) transmission line. Converter stations at either end convert electricity from alternating current to direct current and send the power to the southern part of the province at 500 kv. From here, power is distributed all over the province. Nominal voltage levels on the Manitoba Hydro interconnected transmission system are 115, 138, 230 and 500 kv. The northern collector system consists of isolated 138 kv and 230 kv systems connected to the northern high-voltage direct current facilities. Sub-transmission and distribution voltage levels are 66, 33, 24.94, and 12.47 kv. Manitoba Hydro uses mixed-gas circuit breakers primarily at the transmission and subtransmission voltage levels. The table below shows the quantity of mixed-gas circuit breakers presently on our system. SYSTEM VOLTAGE SF 6 /N 2 SF 6 /CF 4 500 kv - 2 230 kv 5 62 138 kv - 7 115 kv 2 46 66 kv 19 16 Totals 26 133 1

Figure 1: Single Line Diagram We have been purchasing mixed-gas circuit breakers since 1988. These initial circuit breakers were purchased with a 0.5 MPa mixture (0.31SF 6 + 0.2N 2 ) at 20 o C. In 1990, a new gas mixture of SF 6 and CF 4 became available. This new mixture offered some very important advantages over the SF 6 and N 2 mixture. A circuit breaker filled with the SF 6 /CF 4 mixture is, in most cases, able to retain its full interrupting capability at -50 o C with only very small values of grading capacitance. In some cases, depending on the interrupter chamber design, manufacturers have been able to eliminate the grading capacitors all together. Manitoba Hydro made the decision to standardize on this new gas mixture. The SF 6 /CF 4 breaker operates with a slightly higher pressure of 0.7 MPa (0.37SF 6 + 0.34CF 4 ) at 20 o C. To date, these circuit breakers have performed flawlessly with no reported cold-weather-related problems (i.e., low-pressure alarms, gas leaks). 2. TECHNICAL CONSIDERATIONS 2.1 General The role of the high-voltage circuit breaker is to perform routine and emergency connection and disconnection (i.e., switching) of network elements such as transmission lines and transformers. The disconnection process (i.e., opening or tripping ) generally involves complex phenomena, not only in the case of emergency tripping following short circuits in which interruption of high currents is required, but also during routine switching. Consequently, circuit breaker technology is relatively sophisticated and is still undergoing changes. 2

Picture 1: 500 kv SF 6 /CF 4 Live Tank Circuit Breaker at Manitoba Hydro s Dorsey Substation Over the years, the performance of high-voltage outdoor circuit breakers during cold-weather conditions has been a matter of concern to Manitoba Hydro. As different types and designs were developed, new low temperature problems surfaced. To improve performance and reliability during adverse weather conditions, Manitoba Hydro specifies that circuit breakers must be able to operate down to ambient temperatures of -50 o C without the use of heaters. To meet this requirement, manufacturers must: a) Provide a gas mixture to avoid the temporary condensation of the SF 6 gas at low temperatures. b) Test the mechanical operation of the circuit breaker at -50 o C according to the lowtemperature cycle test defined in IEC 56 (this test requires all heaters to be switched off for 2 hours at -50 o C and the circuit breaker operated). 2.2 Mixed Gas At low ambient temperatures, below -30 o C or -40 o C (depending on filling pressure), there is a risk of SF 6 condensation, which can cause some reduction of breaking capacity. To avoid this, circuit breakers can be filled with a gas mixture of SF 6 and N 2 or SF 6 and CF 4. Mixed gas filling with SF 6 and N 2 deteriorates the thermal and dielectric breaking capacity. The deteriorated dielectric characteristics can be compensated for with a slightly higher operating pressure. High thermal stresses are imposed on the circuit breaker if it has to interrupt a short-line fault. The short-line fault is a fault that occurs on the line several hundred metres from the station and causes a rapidly rising voltage to develop across the circuit breaker contacts directly after current zero. Because of the reduced thermal performance of the SF 6 /N 2 mixture, the circuit breaker must be de-rated one step (i.e., 40 ka to 31.5 ka) to protect against thermal failure of the circuit breaker. If de-rating is unacceptable, then grading capacitors must be connected 3

across the circuit breaker contacts to limit the rate-of-rise of the recovery voltage. In some applications, however, the large values of grading capacitance that are required to avoid derating are unacceptable because they can lead to other problems (ferro-resonance) not directly associated with the circuit breaker. Mixed gas filling with SF 6 and CF 4 results in practically unchanged thermal and dielectric breaking characteristics. This is because the thermal interrupting capability and flow velocity of CF 4 are similar to SF 6. An SF 6 /CF 4 -filled circuit breaker often retains its breaking capacity down to the lowest ambient temperatures. It is usually not necessary to repeat all the type tests for the mixed-gas version if the circuit breaker has already been tested as a pure SF 6 version. The following type tests are typically repeated to confirm the switching capability of the circuit breaker with the gas mixture: 1) Cold performance test for capacitive and small inductive current switching cases 2) Terminal fault tests 3) Short line fault test Tests performed at 20 o C are also valid for -50 o C. Theoretically, there is no difference in switching capability at very low temperatures as long as the liquefaction point of the gas is not reached. 2.3 Low-Temperature Cycle Test Very low temperatures stress a circuit breaker in a complex manner. To qualify a circuit breaker for use at temperatures as low as -50 o C, it is essential that a circuit breaker be mechanically tested at the lowest operating temperature to ensure travel characteristics, operating times, and gas tightness are not unacceptably affected or compromised. Manitoba Hydro requires the lowtemperature cycle type test be performed successfully in accordance with IEC 56, Clause 6.101.3.3 (see Figure 2). 2.4 Gas Leakage Rate Today s gas-filled circuit breakers have very small leakage rates (<0.5% per year at 20 o C). Sealing at low temperatures must be very carefully and precisely engineered; proper materials must be used for gaskets to ensure seals reseal effectively following deformation associated with operation of the circuit breaker. The IEC standard allows a low temperature leakage rate three times the rate at normal temperatures. This rate takes into account that -50 o C will occur only during very limited times over the year. 2.5 Circuit Breaker Types There are two main categories of circuit breakers: one in which the enclosure for the extinguishing medium (SF 6 ) and the contacts is metallic and grounded, and the other in which the chamber containing the extinguishing medium and contacts is insulated from the ground. The former is commonly referred to as a dead tank design and the latter as a live tank design (see Figure 3). In the past, only live tank designs were supplied with a gas mixture. Dead tank designs relied on the use of tank heaters to keep the SF 6 gas above its liquefaction temperature and to prevent 4

seals from leaking. Today some manufacturers can offer a mixed-gas dead tank design up to a rating of 145 kv, 40 ka. As evidenced from bids received during recent years, few suppliers are prepared to bid on a specification that prohibits the use of heaters at low temperatures. Developing a low temperature circuit breaker requires a very significant investment; manufacturers of high-voltage circuit breakers have been unwilling to make this investment because of the very small market share that low-temperature circuit breakers represent worldwide. Competition on recent Manitoba Hydro bids has, therefore, been confined to three suppliers. To increase the level of competition, some utilities will relax their low-temperature requirements at the lower voltage levels, specify less stringent low temperature specifications depending on location, or accept the use of tank heaters at low ambient temperatures. Figure 2: IEC 56 Low-Temperature Cycle Test 5

Figure 3: Circuit Breaker Tank Designs Manitoba Hydro chose not to go this route. Cold weather is a reality in Western Canada and Manitoba, in particular. Low temperatures have frequently approached -50 o C. The Manitoba Hydro system serves many remote or isolated locations. Consequently, it is very important that circuit breakers operate when needed. Today s low-temperature tested mixed-gas circuit breakers offer improved cold-weather performance, especially over the older air blast designs, and provide the reliability needed for our system. 3. SF 6 /CF 4 /N 2 GAS HANDLING Manitoba Hydro presently owns and utilizes three gas handling carts. These carts are manufactured by DILO Company, Inc., and are capable of handling SF 6, CF 4 and N 2 in either the gaseous or liquid form. A diaphragm compressor allows a storage vessel or gas containment compartment to be evacuated to an absolute pressure of 50 mbar. All gas scavenged through use of the diaphragm compressor is accumulated in an empty gas bottle, located on the cart. A vacuum pump, which expels to the atmosphere, is capable of evacuating a gas compartment to an absolute pressure of 2 mbar. The vacuum pump would be activated after the diaphragm compressor has reduced the gas volume to a pressure of 50 mbar. This minimizes the amount of SF 6 exhausted to the atmosphere. Usually, the only time the vacuum pump is utilized is for the drying of the cart or the gas compartment of equipment that is to be refilled with SF 6. Picture 2: DILO Gas Cart Picture 3: Gas Collection Bottles 6

Picture 3: Gas Cart Instrumentation The gas carts we utilize incorporate an in-line filtering unit. One component of the unit is a dry filter cartridge that is capable of absorbing moisture from the gas passed through it. The moisture (H 2 0) content of gas passed through the filter does not exceed 10 ppm mass. The filter unit incorporates a dust filter to cleanse unwanted gaseous particles from the gas such as SF 4, S0 2 F 2, HF, S0 2, and WF 6. The filter also collects solid particles, created as the SF 6 gas decomposes after exposure to an electric arc. These particles include W0 3 and CuF 2. To date, the filter element has not needed to be changed. When it is necessary to change the filter element and all similarly contaminated handling materials, they will be neutralized with soda ash and water, as detailed in a written procedure, prior to disposal. We encourage all our field service personnel to utilize these carts when handling all SF 6 gas to ensure the quality of the gas is maintained and the environment is protected from unnecessary gas release. We do not knowingly release or encourage the release of SF 6 gas into the atmosphere. Whenever gas is extracted from a particular piece of equipment, the reclaimed gas is stored in an empty bottle, which is standard equipment on the gas cart. Normally, all gas stored in this empty bottle is returned to the equipment it was removed from. If it is not, the empty bottle is purged when the gas cart is returned to its storage location. The purged gas is collected and stored until a sufficient quantity is accumulated. The reclaimed gas is then sent to an outside agency for proper disposal. We presently utilize more than 170 circuit breakers, 35 circuit switchers, and 1 station bus system that contain SF 6 gas. Most of our stock gas storage is done at the Waverley Service Centre, although some work centers maintain their own stock. This local storage is discouraged, but the issue has not been pushed. There are records kept with regard to the quantities of the 7

various gases stored at Waverley, but no official records are kept on gas stored in the individual work centers. Also, there are no records kept regarding the quantity of SF 6 gas found in the various pieces of equipment presently in-service. No records are kept that would track the quantity of gas that is either leaking or has leaked from equipment nor the amount that is added to a given piece of equipment over the equipment s life cycle. The setup of a recording system to address these issues is one of our priorities. We feel that we should be monitoring and tracking this information both as due diligence and in preparation for the (probable) upcoming legislation. 4. CONCLUSIONS Manitoba Hydro pioneered the use of mixed-gas circuit breakers in North America and was the first utility to install them on their system. The population of mixed-gas circuit breakers on the Manitoba Hydro system continues to grow. These circuit breakers have performed flawlessly and have provided the cold-weather performance and reliability needed by Manitoba Hydro. 5. REFERENCES (1) Middleton, R., Koschik, V., Hogg, P., Kulkarni, P., and Heiermeier, H. "Development work for the application of 245 kv circuit breakers using a SF 6 /CF 4 gas mixture on the Manitoba Hydro System." Paper presented at Canadian Electrical Association Spring Conference. Toronto, Canada., March 1996. (2) Dale, S.J., and Niemeyer, L. "Current Design of Gas Insulated Equipment." Paper presented at the U.S. Environmental Protection Agency's Conference on Electrical and Transmission Systems, Sulfur Hexafluoride and Atmospheric Effects of Greenhouse Gas Emission. Washington, D.C., August 9-10, 1995. (3) Landry, M., and Jeanjean, R. "Dielectric Withstand and Breaking Capacity of SF 6 Circuit Breakers at Low Temperatures." IEEE WM 121-7, 1987. (4) International Electrotechnical Commission. "High Voltage Alternating Current Circuit Breakers." IEC 56, Fourth Edition, 1987. 6. BIOGRAPHY Bob Middleton received his B.S. in electrical engineering from the University of Manitoba and is a registered professional engineer in the province of Manitoba. He joined Manitoba Hydro in 1972 and has held various positions in generation and transmission engineering. Between the years 1979 and 1986, he worked as a consultant in Vancouver and Winnipeg. Upon his return to Manitoba Hydro in 1986, he re-joined the Apparatus Engineering Group, where he currently holds the title of Apparatus and Quality Control Engineer. Bob Middleton is a member of CSA Technical Committees 123 and 128, Canadian subcommittees on IEC TC 33 and IEC TC 38/WG 26 and the Canadian Electrical Association (CEA). 8