Influence of Persons' Movements on Ventilation Effectiveness Brohus, Henrik; Hyldig, Mikkel; Kamper, Simon; Vachek, Ulla Maria

Similar documents
Cross Infection in Hospital Wards with Downward Ventilation - Different Locations of Return Openings without and with Partitions between Beds

Aalborg Universitet. Published in: EERB-BEPH Publication date: Document Version Publisher's PDF, also known as Version of record

Aalborg Universitet. Published in: Proceedings of Offshore Wind 2007 Conference & Exhibition. Publication date: 2007

Single-sided Natural Ventilation Driven by a Combination of Wind Pressure and Temperature Difference Larsen, Tine Steen; Heiselberg, Per Kvols

Stability of Cubipod Armoured Roundheads in Short Crested Waves Burcharth, Hans Falk; Andersen, Thomas Lykke; Medina, Josep R.

Sea state estimation from an advancing ship - The wave buoy analogy Presentation at Skibsteknisk Selskab

Effect of airflow direction on human perception of draught

Aalborg Universitet. Published in: Proceedings of Indoor Air Publication date: 2008

Measurement of Air Flow Rate in a Naturally Ventilated Double Skin Facade Larsen, Olena Kalyanova; Jensen, Rasmus Lund; Heiselberg, Per Kvols

Experimental Study of Wind-Opposed Buoyancy-Driven Natural Ventilation Andersen, A.; Bjerre, M.; Chen, Z. D.; Heiselberg, Per Kvols; Li, Y.

CFD Modeling of Thermal Manikin Heat Loss in a Comfort Evaluation Benchmark Test

Aalborg Universitet. Ice Control with Brine on Highways Bolet, Lars. Publication date: 2008

Thermal properties of Fiber ropes

Measuring offshore winds from onshore one lidar or two?

THE AIRCRAFT SEAT AS INDOOR AIR QUALITY AND TEMPERATURE CONTROL SYSTEM

Yawing and performance of an offshore wind farm

Complex terrain wind resource estimation with the wind-atlas method: Prediction errors using linearized and nonlinear CFD micro-scale models

NUMERICAL INVESTIGATION OF THE FLOW BEHAVIOUR IN A MODERN TRAFFIC TUNNEL IN CASE OF FIRE INCIDENT

Spinner Anemometry Pedersen, T.F.; Sørensen, Niels; Madsen, H.A.; Møller, R.; Courtney, M.; Enevoldsen, P.; Egedal, P.

Drivers of cycling demand and cycling futures in the Danish context.

Study on wind turbine arrangement for offshore wind farms

THE EXAMINATION OF COMFORT AND CROSS INFECTION IN A DISPLACEMENT VENTILATED ROOM

Laser remote sensing for wind energy

Aspects of Using CFD for Wind Comfort Modeling Around Tall Buildings Rasmussen, Michael Robdrup; Andersen, Lars Vabbersgaard

The European Green Capital Award. Its Role, Evaluation Criteria and Policy Implications

Laboratory studies on the effect of ozonation on THM formation in swimming pool water

Steady State Comparisons HAWC2 v12.5 vs HAWCStab2 v2.14: Integrated and distributed aerodynamic performance

Occupant body movement and seat occupancy rate for design of desk microenvironment

Comparison of NWP wind speeds and directions to measured wind speeds and directions

Extrapolation of Extreme Response for Wind Turbines based on FieldMeasurements

Thermal Conditions in a Simulated Office Environment with Convective and Radiant Cooling Systems

The effect of boot shaft flexibility on ankle, knee and hip coupling during mogul skiing Kersting, Uwe G.; McAlpine, Paul; Kurpiers, Nico

Vertical Distribution of Wave Overtopping for Design of Multi Level Overtopping Based Wave Energy Converters Kofoed, Jens Peter

Validation of a Neutral Pressure Isolation Room

Wind Resource Assessment Østerild National Test Centre for Large Wind Turbines

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. Publication date: Document Version Accepted author manuscript, peer reviewed version

Development of virtual 3D human manikin with integrated breathing functionality

Aalborg Universitet. Estimation of wave conditions at Liseleje location Bogarino, Bruno; Brorsen, Michael. Publication date: 2007

Post-mortem study on structural failure of a wind farm impacted by super typhoon Usagi

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

Validation of Measurements from a ZephIR Lidar

Modelling atmospheric stability with CFD: The importance of tall profiles

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

Astudy of the air quality in the breathing zone in a room with displacement ventilation

Radioactivity in the Risø District July-December 2010

Wind Flow Validation Summary

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012

Radioactivity in the Risø District July - December 2009

Spectral analysis of wind turbulence measured by a Doppler Lidar for velocity fine structure and coherence studies

NOVEL BED INTEGRATED VENTILATION METHOD FOR HOSPITAL PATIENT ROOMS. Technical University of Denmark, Kgs. Lyngby, Denmark. Poland.

AIRFLOW AND TEMPERATURE FIELD CALCULATIONS FOR WINTER SPORTS FACILITIES

Cycling and urban form Evidence from the Danish National Transportation Survey

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

Aerodim TM The new aerodynamic silencer reduces sound by half

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

LONGITUDINAL AIR VELOCITY CONTROL IN A ROAD TUNNEL DURING A FIRE EVENT

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM

Validation of long-range scanning lidars deployed around the Høvsøre Test Station

Free Surface Flow Simulation with ACUSIM in the Water Industry

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1

FUBA RULEBOOK VERSION

ESTIMATION OF THE DESIGN WIND SPEED BASED ON

Sample Applications of the Second Generation Intact Stability Criteria Robustness and Consistency Analysis

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

Ermenek Dam and HEPP: Spillway Test & 3D Numeric-Hydraulic Analysis of Jet Collision

Flow and Mixing in the Liquid between Bubbles

A CFD ANALYSIS OF VENTILATION SYSTEM OF LAVATORY IN OFFICE BUILDING , Higashi-mita, Tama-ku, Kawasaki, Japan

Effects of seam and surface texture on tennis balls aerodynamics

Sea Slot Cone Generator Overtopping Performance in 3D Conditions Margheritini, Lucia; Vicinanza, Diego; Frigaard, Peter Bak

Bio-Effluents Tracing in Ventilated Aircraft Cabins

An experimental study of internal wave generation through evanescent regions

Wind pressure coefficient determination for greenhouses built in a reclaimed land using CFD technique

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

What is air track? 1 Introduction

AIRFLOW GENERATION IN A TUNNEL USING A SACCARDO VENTILATION SYSTEM AGAINST THE BUOYANCY EFFECT PRODUCED BY A FIRE

Vindatlas i Ægypten. Mortensen, Niels Gylling; Badger, Jake; Hansen, Jens Carsten. Publication date: Document Version Peer reviewed version

Results of Field Measurements and CONTAM Simulation. Building Science

Transport attitudes, residential preferences, and urban form effects on cycling and car use.

How to Select and Specify Mixers for Potable Water Storage Tanks

Flow Visualisation Studies - I

TACTICAL FOOTBALL GAME RULEBOOK fubatacticalfootballgame. Game design by Hannu Uusitalo

AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

Computer Simulation Helps Improve Vertical Column Induced Gas Flotation (IGF) System

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

AN EVALUATION OF ENCAPSULATED OIL FLOODED SCREW COMPRESSOR SYSTEMS. Nikola Stosic, Ahmed Kovacevic, ian K Smith and Elvedin Mujic

North Sea offshore Grid development: Combined optimization of grid and generation investments towards 2050

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series

Lecture 7. More on BL wind profiles and turbulent eddy structures. In this lecture

WP2 Fire test for toxicity of fire effluents

Natural Ventilation Applications in Hot-humid Climate: A Preliminary Design for the College of Design at NTUST

Fire safety of staircases in multi-storey buildings The results of measurements in Buildings and Simulations

WIND CONDITIONS MODELING FOR SMALL WIND TURBINES

Torrild - WindSIM Case study

Aalborg Universitet Radon barrier: Method of testing airtightness General rights Take down policy

SEMI-SPAN TESTING IN WIND TUNNELS

Design and manufacturing of a morphing flap for wind turbine blades

Meteorology & Air Pollution. Dr. Wesam Al Madhoun

Ventilation Effects on Compartment Fire Characterization

Design, Building and Teaching with a Hydrostatic and Buoyancy Apparatus

Transcription:

Aalborg Universitet Influence of Persons' Movements on Ventilation Effectiveness rohus, Henrik; Hyldig, Mikkel; Kamper, Simon; Vachek, Ulla Maria Published in: Proceedings of Indoor Air 2008 Publication date: 2008 Document Version Publisher's PDF, also known as Version of record Link to publication from Aalborg University Citation for published version (APA): rohus, H., Hyldig, M., Kamper, S., & Vachek, U. M. (2008). Influence of Persons' Movements on Ventilation Effectiveness. In Proceedings of Indoor Air 2008: The 11th International Conference on Indoor Air Quality and Climate, Copenhagen, Denmark, 17-22 August, 2008 Technical University of Denmark (DTU). General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.? Users may download and print one copy of any publication from the public portal for the purpose of private study or research.? You may not further distribute the material or use it for any profit-making activity or commercial gain? You may freely distribute the URL identifying the publication in the public portal? Take down policy If you believe that this document breaches copyright please contact us at vbn@aub.aau.dk providing details, and we will remove access to the work immediately and investigate your claim. Downloaded from vbn.aau.dk on: May 01, 2017

Influence of persons movements on ventilation effectiveness Henrik rohus *, Mikkel L. Hyldig, Simon Kamper and Ulla M. Vachek Aalborg University, Denmark * Corresponding email: hb@civil.aau.dk SUMMARY Most often the ventilation effectiveness of a ventilated room is determined without considering the influence of persons movements. Even though the main reason for supplying the ventilation may be to create a healthy and productive environment for the occupants, their own influence on the ventilation is usually disregarded. This paper presents results from a systematic investigation of the movements influence on the ventilation effectiveness using human subjects combined with tracer gas measurements. Several typical movements are defined and carefully repeated to determine the influence of different kinds of movement compared with the case of no movements. It is found that mixing ventilation is considerably more robust compared with displacement ventilation. At the same time it is found that displacement ventilation on average is more effective than mixing ventilation when movements prevail, even though the movements reduce the effectiveness. Furthermore, it is found that the influence of the different movements vary substantially. KEYWORDS Persons movements, Ventilation effectiveness, Ventilation, Person s activities, Contaminant distribution INTRODUCTION During the past two decades awareness of concentration gradients in ventilated rooms has increased and the concept of ventilation effectiveness is widely adopted today (Mundt et al., 2004). Thus, it is a well known fact that for instance personal exposure may depend strongly on the local concentration distribution. Assuming fully mixed conditions may result in substantial errors (rohus and Nielsen, 1996; jørn and Nielsen, 2002). Most often, however, the ventilation effectiveness of a ventilated room is determined without considering the influence of persons movements. Even though the main reason for supplying the ventilation may be to create a healthy and productive environment for the occupants, their own influence on the ventilation due to movements is usually disregarded. The obvious reason is the level of complexity connected with inclusion of movements in the calculations combined with a lack of knowledge from full-scale measurements. Available studies considering persons movements report a significant influence and strongly encourage the consideration in the design of air distribution and analysis of contaminant distribution (Hillerbrant and Ljungqvist, 1990; Matsumoto et al., 2004; rohus et al., 2006). This paper presents results from a systematic investigation of the movements influence on the ventilation effectiveness using human subjects combined with tracer gas measurements. A room equipped with selected furniture, heat sources, contaminant sources and a moving person is investigated in case of mixing ventilation and displacement ventilation, respectively. Several typical movements are defined and carefully repeated to determine the influence of different kinds of movement compared with the case of no movements.

METHODS This paper investigates the influence of movements by means of full scale measurements in a ventilated test room using human subjects performing well-defined characteristic movements, see Table 1. oth mixing and displacement ventilation is applied for three different contaminant sources in case of the various movements. Table 1. Investigated parameters Parameter Variation Ventilation principle Mixing ventilation Displacement ventilation Movement No movement (Figure 5) Five movements Contaminant source At the back (person, warm source) (Figure 4) Above Convector 1 (warm source) On Table 1 (passive source) The test room is shown in Figure 1 and the setup is detailed in Table 2. The test room is built inside a larger test facility. Wall 4 Wall 3 Wall 1 Wall 4 Door Figure 1. Photos and sketch of the test room. Table 2. Test room setup Room volume 35.4 m 3 Air change rate 5 h -1 Location of temperature sensor Mixing ventilation: In the exhaust duct Displacement ventilation: 1.2 m above floor inside the test room Temperature set point 21 C Operation of the two convectors Stratification height (concentration) Each of 350 W. Applied in case of displacement ventilation only. The purpose is to generate appropriate concentration and temperature stratification. Approximately 1.3 m (only in case of displacement ventilation) The setup is partly inspired by an operating room which is the reason for the location of the tables and the clothing among others (rohus et al., 2008), see Figure 2. In case of mixing ventilation the ceiling device is the supply opening and air is exhausted close to the floor. When displacement ventilation is applied the system is somewhat opposed with a displacement inlet device mounted at the floor and air exhausted through the ceiling device, see Figure 3. The two convectors are applied only in case of displacement ventilation to generate a proper concentration (and temperature) stratification. One human subject is present all the time standing still or doing the specified movements.

Figure 2. Measurement setup and coordinate system. The circles represent three different contaminant sources (see Figure 4). The crosses represent measurement locations. Figure 3. Left: Mixing ventilation inlet device (and exhaust opening in case of displacement ventilation). Centre: Mixing ventilation exhaust opening. Right: Displacement ventilation inlet device. Figure 4. Three different tracer gas contaminant sources. Left and centre: Source at the back of a person (with and without coat). Upper right: Source on Table 1 (the tracer gas source and the measuring point are not applied at the same time). Lower right: Source above Convector 1.

To investigate the concentration distribution and ventilation effectiveness tracer gas measurements are performed. Three different tracer gas contaminant sources are applied, see Figures 2 and 4, one passive and two warm contaminant sources. The passive contaminant source comprises tracer gas supplied on Table 1 and the two warm sources comprise tracer gas supplied at the back of the person under a coat and supplied above Convector 1, respectively. The passive source may represent spread of contaminant locally in front the person. The source at the back may represent bacteria emission, CO 2 or bio effluents. Finally, the source supplied above the heated convector represents a stratified concentration distribution typical for displacement ventilation. Figure 5. Sketch of five characteristic movements: D = Vertical Downward, U = Vertical Upward, R = Random, H = Horizontal, W = Walking. Full-drawn line means fast/normal movement. roken line means slow movement. The five movements illustrated in Figure 5 include four movements of the arms (feet located at the same place) and one walking movement. They are chosen to constitute typical movements inspired by movements that may be found in an operating room and elsewhere (rohus et al., 2008). On one hand the movements should represent real movements and on the other they should be well-defined and possible to repeat in a systematic and controlled way by the human subject. The speed of the movements is a balance between the speed of the real movements and consideration of the human subject that is going to repeat the movement many times during a measurement series to get enough samples to obtain reliable results. To guide the movements a number of reference points are established in the room together with guiding sound recordings played using the loudspeakers shown in Figure 2. Table 3 provides information on the specific location of the tracer gas sources and the concentration measurement locations.

Table 3. Measurement setup Tracer gas source location 1 Location (see Figure 4) At the back Above Convector 1 On Table 1 Coordinates (x, y, z) in m (1.6, 1.35, 1.935) (1.655, 1.11, 0.8) (1.6, 0.82, 2.65) Tracer gas concentration measurements 2,3 Location Personal Exposure (not when the source is at the back) On Table 1 (only when source is at the back) On Table 2 At a height of 1.8 m Exhaust air, in case of mixing ventilation Exhaust air, in case of displacement ventilation Coordinates (x, y, z) in m (1.6, 1.55, 2.19) (1.6, 0.82, 2.65) (1.0, 0.82, 2.05) (2.25, 1.8, 3.3) (3.2, 0.3, 2.05) (1.6, 2.7, 2.05) 1: Tracer gas: N 2 O 2: Equipment: rüel & Kjær Multipoint Sampler and Dozer type 1303 and rüel & Kjær Multigas Monitor type 1302. 3: For each setup concentration is measured at two locations inside the room as well as in the exhaust air. Each setup comprises 40 concentration measurements at each location to ensure reliable results leading to a total duration of 3.5 hours for each case. Steady-state conditions are maintained except of course for the systematic movements. RESULTS Selected results from the measurements are presented in Table 4 in shape of concentration measurements at four different locations including the personal exposure. Apart from the presented results extensive smoke visualization and various other measurements are performed like concentration and temperature profiles inside the room which are not presented to save space. Table 4. Selected results from tracer gas measurements Ventilation Source 1 Movement 2 Exposure 3,4,5 Table 1 Table 2 H180 Mixing T N 1.65 (0.61) 1.12 (0.25) T U 1.61 (0.83) 1.01 (0.07) T H 1.56 (0.40) 1.20 (0.52) T R 1.24 (0.29) 0.95 (0.03) Displacement T T T N D R N H R N D R 0.89 (0.12) 1.48 (0.31) 1.29 (0.18) 1.03 (0.04) 1.05 (0.03) 1.07 (0.03) 0.26 (0.01) 0.40 (0.08) 0.43 (0.07) 0.99 (0.05) 1.05 (0.07) 1.07 (0.05) 0.38 (0.06) 1.31 (1.22) 0.28 (0.03) 0.31 (0.01) 0.25 (0.02) 0.29 (0.05) C W 0.84 (0.14) 0.47 (0.10) 0.85 (0.10) 1: Tracer gas source (see Table 3): T = On Table 1, = At the ack, C = Above Convector 1 2: Movements (see Figure 5): N = No movement, D = Vertical Downward, U = Vertical Upward, R = Random, H = Horizontal, W = Walking. 3: Measurement locations are found in Table 3. 4: Dimensionless tracer gas concentration: c * P = c P /c R, where c P is the local concentration and c R is the return concentration (i.e. exhaust air). 5: Mean value and standard deviation (in brackets).

All results are presented in terms of dimensionless tracer gas concentration by dividing by the return concentration. The local ventilation effectiveness, and the personal exposure index (rohus and Nielsen, 1996), can be found by taking the inverse of the results. Thus, a dimensionless concentration of 1 corresponds to fully mixed conditions. Furthermore, levels below 1 correspond to ventilation effectiveness above 1. DISCUSSION Influence of movements in case of mixing ventilation Two contaminant sources are applied for the mixing ventilation case, namely the passive source located on Table 1 and the source at the back of the person, respectively. First, the source on Table 1 is considered. Here it is evident that the dimensionless personal exposure is above 1 (i.e. ventilation effectiveness somewhat below 1) both in case of no movements and for the three chosen movements. The corresponding results regarding the concentration on Table 2 indicate a level much closer to 1, however, depending on the kind of movement. It is clear that the contaminant source in front of the person is partly entrained in the convective boundary layer along the person and transported to the breathing zone, a fact which is supported by smoke visualisation. The random movement seems to generate the highest level of local mixing and produces the lowest concentration at both locations. The horizontal movement is found to transport lumps of fluid containing tracer gas from the source area above Table 1 to the measuring location on Table 2. Thus, even though the air change rate is reasonably high (5 h -1 ) the mixing ventilation may be quite sensitive to local passive sources. Second, the heated source (tracer supplied at the back of the person) is examined. The measurements on Table 1 and Table 2 show levels quite close to 1 for all movements indicating that the mixing is effective in this case. Influence of movements in case of displacement ventilation In case of displacement ventilation the difference between the passive and the warm source is pronounced and the influence of movements is highly significant. Compared with mixing ventilation the stratified concentration distribution in the displacement ventilation case reduces the exposure due to entrainment of clean air from the lower cleaner part of the room when the persons is standing still. In case of movements the results look more like the mixing ventilation case due to the local disturbances in front of the person caused by the movements. The concentration on Table 2 is clearly influenced by the movements. When no and random movements occur levels below 0.4 prevail whereas horizontal movements generate a level exceeding 1 which is even worse than the mixing case. When the source is located at the back the concentrations on Table 1 and Table 2 are quite low for no, downward and random movements. Especially in case of no movement very high ventilation effectiveness is found (1/0.26 = 3.8). In this case the displacement principle is much more robust than in case of the abovementioned passive source. The walking movement is investigated using another heated source in shape of tracer gas released above the heated Convector 1 (see Figure 4). In this case the contaminant is

transported to the upper part of the room generating a clearly stratified flow. Here it is seen that the personal exposure equals the concentration approximately at the same height measured at a neutral part of the room without local influence from the walking person. This result corresponds well with the findings of rohus and Nielsen (1996). The concentration on Table 2 is significantly lower, around half the exposure level, which indicates that significant stratification prevails despite the substantial local disturbances caused by the walking movement. Mixing ventilation vs. displacement ventilation When mixing ventilation and displacement ventilation are compared the result is highly dependent on the kind of contaminant source. If the source is warm it is found that the ventilation effectiveness of displacement ventilation is significantly higher (approximately 2 4 times) than mixing ventilation almost irrespective of the movements in the present case. The only movement in the displacement ventilated room that results in mixing-like ventilation effectiveness is walking which is also expected. Here, it should be noted that the stratification height is around 1.3 m, i.e. below breathing zone height. If the stratification height was found above breathing zone height it would presumably result in higher ventilation effectiveness, however, at the expense of substantially increased air flow rate and energy consumption. When the influence of the passive contaminant source is investigated the outcome is quite different. On average the displacement ventilation still provides the lowest exposure as well as Table 2 concentration even though the difference is substantially reduced. However, now the displacement principle is less robust and may in certain cases cause higher local concentrations than in the mixing case. This may be due to the fact that significant stratification may catch and lock amounts of contaminant in a horizontal layer (as found by jørn and Nielsen (2002) among others). This indicates that displacement ventilation may be excellent in offices, where the main pollution sources are warm, whereas it cannot be recommended in hospitals where high local bacteria concentrations may jeopardize the hygiene. Thus, overall it can be stated for the present test case that displacement ventilation has higher ventilation effectiveness that mixing ventilation. However, displacement ventilation is less robust to the influence of movements. CONCLUSIONS It is found that mixing ventilation is considerably more robust compared with displacement ventilation. At the same time it is found that displacement ventilation on average is more effective than mixing ventilation when movements prevail, even though the movements reduce the effectiveness. Furthermore, it is found that the influence of the different movements vary substantially. In general ignorance of the influence of persons movements may lead to significant overestimation of the ventilation effectiveness as well as an overestimation of the robustness of the air distribution system. REFERENCES jørn E. and Nielsen, P.V. 2002. Dispersal of exhaled air and personal exposure in displacement ventilated rooms. Indoor Air, 12, 147-164.

rohus H. and Nielsen, P.V. 1996. Personal exposure in displacement ventilated rooms. Indoor Air, 6, 157-167. rohus H., alling K.D., and Jeppesen, D. 2006. Influence of movements on contaminant transport in an operating room. Indoor Air, 16, 356-372. rohus H., Hyldig M.K., Kamper S., and Vachek U.M. 2008. Influence of disturbances on bacteria level in an operating room. Proceedings of Indoor Air 2008. The 11 th International Conference on Indoor Air Quality and Climate, 17 22 August. Copenhagen, Denmark. Hillerbrant. and Ljungqvist. 1990. Comparison between three air distribution systems for operating rooms. Proceedings of Roomvent 90, Paper 62, 1-13, 13 15 June, Oslo, Norway. Matsumoto H., Matsusaki A., and Ohba. 2004. CFD simulation of air distribution in displacement ventilated room with a moving object. Proceedings of Roomvent 2004, 9 th International Conference on Air Distribution in Rooms. 5 8 September, Coimbra, Portugal. Mundt E. et al. (Ed.) 2004. Ventilation effectiveness. REHVA Guidebook No. 2. REHVA, russels, elgium.