Liquid level measurement using hydrostatic pressure and buoyancy

Similar documents
Level MEASUREMENT 1/2016

Liquid Level Measurement

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

Instrumentation & Data Acquisition Systems

The Discussion of this exercise covers the following points:

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Radar, Ultrasonic and RF Level Transmitters

γ water = 62.4 lb/ft 3 = 9800 N/m 3

Best Practices in Measuring Tank Level

HEATEC TEC-NOTE. Setting Siemens Pressure Transmitter. Used on Heatec Vertical Asphalt Tanks. Publication No , Revised

Rosemount 3159 Nuclear Qualified Remote Diaphragm Seal

Bubble Tube Installations

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

Measurement And Control Appreciation

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Pressure measurement Applying remote seal, isolation diaphragms between process fluids and transmitters

In the liquid phase, molecules can flow freely from position to position by sliding over one another. A liquid takes the shape of its container.

Successful completion of the course leads to the award of the Technical Training Solutions Certificate of Competence 510: Instrumentation.

Improving distillation tower operation

The Discussion of this exercise covers the following points:

In the liquid phase, molecules can flow freely from position. another. A liquid takes the shape of its container. 19.

PHYSICS - CLUTCH CH 17: FLUID MECHANICS.

Gerald D. Anderson. Education Technical Specialist

Introduction to Pressure Measurement

How to specify a product. Process Sensors and Mechanical Instruments

CONTROL and INSTRUMENTATION

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

PALO VERDE NUCLEAR GENERATING STATION

Process Control Loops

PROCESS MONITORING AND CONTROL

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Additional Information

Application Worksheet

Pressure Measurement Single-range transmitters for general applications

SPD Pressure Sensor Families

Air Eliminators and Combination Air Eliminators Strainers

200A Series ELECTRONIC LEVEL TRANSMITTER

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

To connect the words of Archimedes Principle to the actual behavior of submerged objects.

SFC. SKYLINE FLOW CONTROLS INC. The Leader of Accurate and Reliable Flow Measurement DESCRIPTION & APPLICATIONS: ADVANTAGES:

AP Physics B Ch 10 Fluids. MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

TOPIC: KNOWLEDGE: K1.01 [2.5/2.7] An atmospheric pressure of 15.0 psia is equivalent to... A psig. B psig. C psig.

BAPI Pressure Line of Products - FAQs

Cover Page for Lab Report Group Portion. Pump Performance

Hydrostatic & Submersible. Level instruments. for the Australian market

Rig Math. Page 1.

IT STARTS AT THE SOURCE - RE-CALIBRATING YOUR PLANT METERS

PHY131H1S - Class 23. Today: Fluids Pressure Pascal s Law Gauge Pressure Buoyancy, Archimedes Principle. A little pre-class reading quiz

Fluid Statics. AP Physics 2

Sizing Pulsation Dampeners Is Critical to Effectiveness

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

. In an elevator accelerating upward (A) both the elevator accelerating upward (B) the first is equations are valid

Torque Tube TB300 Digital Transmitters

Pressure Measurement

Instructions for SMV 3000 Multivariable Configuration (MC) Data Sheets

Chapter 15 Fluid. Density

InstrumentationTools.com

AP Lab 11.3 Archimedes Principle

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

3 1 PRESSURE. This is illustrated in Fig. 3 3.

PREVIEW COPY. Level Measurement. Table of Contents. Principles of Level Measurement...3. Electrical Instruments Pressure Head Instruments...

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

Density and Archimedes Principle 11-cor

A review of best practices for Selection, Installation, Operation and Maintenance of Gas meters for Flare Applications used for Managing facility

Kinetic-Molecular Theory

HUMOR 20 HUMOR 20. High-precision Humidity Calibrator. Water T, p1

3. A fluid is forced through a pipe of changing cross section as shown. In which section would the pressure of the fluid be a minimum?

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

AMS 6916 Board mount pressure sensor with ratiometric analog output

Notes Chapter 3. Buoyancy

The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions

COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL

From and

Quiz name: Chapter 13 Test Review - Fluids

LAB 13: FLUIDS OBJECTIVES

T EK-SUB 4800C 19 mm Submersible Level Transmitter

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION


Irrigation &Hydraulics Department lb / ft to kg/lit.

Diagnosing EVAP systems By: Bernie Thompson

SDX Submersible Depth Transmitter User Manual

LEVEL MEASUREMENT TECHNOLOGIES In The Process Control Industry

PHYS 101 Previous Exam Problems

Engineering: Measurement Technology Pressure/Level (SCQF level 6)

SDX Submersible Depth Transmitter User Manual

Modeling Case Study: Surge Tanks, Valves, Level sensors, and modeling

Simulating Microgravity with Buoyancy A Space School Lesson Plan

Air Operated Hydraulic Pumping Systems to 50,000 psi

HUMOR 20. High Accuracy Humidity Calibrator. Water T, p1 HUMOR 20 V1.0

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Chapter 9 Fluids CHAPTER CONTENTS

TEK-THERMAL 1700B. Thermal Mass Flowmeter. FLOW. Technology Solutions

Old-Exam.Questions-Ch-14 T072 T071

Ratio Regulator Zero Governor. FRG/6 Series

SERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER

ASME and PED Requirements for Drum Level Instrumentation. Presented by: Amir Hedayatnia Clark-Reliance Corp.

PHYS:1200 LECTURE 13 FLUIDS (2)

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)

LAB 13: FLUIDS OBJECTIVES

Transcription:

iquid level measurement using hydrostatic pressure and buoyancy This worksheet and all related files are licensed under the Creative Commons Attribution icense, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/, or send a letter to Creative Commons, 559 Nathan Abbott Way, Stanford, California 94305, USA. The terms and conditions of this license allow for free copying, distribution, and/or modification of all licensed works by the general public. 1

Question 1 Questions A vessel containing a weak acid/water mixture has a calibrated level range of 0 to 10 feet, measured by a pressure transmitter at the bottom. Suppose that the specific gravity of the normal mixture is 1.12 (112% heavier than pure water, giving 1.12 inches of water column pressure for every inch of vertical height), and that the liquid level happens to be at 6 feet. Now, suppose some pure acid is added to the vessel, increasing the actual liquid level and increasing the liquid density at the same time. The new liquid level is 7 feet high and the specific gravity has increased to 1.35. Assuming the transmitter has been calibrated for the original specific gravity of 1.12, what will its output signal correspond to in feet of liquid level? In other words, if this transmitter s output signal were driving a level indicator device for an operator to read, how many feet of level would the indicator device register? Identify an alternative method for liquid level measurement that would not be affected by changes in liquid density. file i00245 Question 2 An open vessel contains water at 60 o F. A pressure transmitter located at the bottom of the vessel measures the hydrostatic pressure ( head ) generated by the water and outputs a signal corresponding to level. Suppose that the temperature of this vessel were to increase over time to 110 o F due to exposure to very hot outside air (the vessel is located in Death Valley, California during the summer). Knowing that an increase in water temperature will result in a decrease in density, what will happen to the level transmitter s output as the vessel heats up? Will the transmitter output increase, decrease, or stay the same? Why?? Assume that no water enters or exits the vessel during the period of heating from 60 o F to 110 o F. file i00246 2

Question 3 A vessel holding some process liquid needs to have its level monitored. The range of level in this vessel is 0 to 20 feet, and the process liquid has a specific gravity of 1.0 (like water). Someone decides to attach a pressure transmitter to the bottom of the vessel to infer level from hydrostatic pressure like this: 20 feet Process liquid S.G. = 1.0 Pressure transmitter ater, a top is added to this vessel to keep rain from entering in. Unfortunately, though, this process liquid tends to emit vapor which will be trapped by the closed vessel and create a pressure inside of it. A small vent is added to the top of the vessel to permit the vapor to escape, but it is a small vent, not big enough to ensure a total absence of vapor pressure buildup at all times: (small) vent pressure 20 feet Process liquid S.G. = 1.0 Pressure transmitter What problem in level measurement will result from there being an occasional vapor pressure buildup inside this vessel? ow may this problem be corrected so that the liquid level will be accurately measured at all times? file i00248 3

Question 4 The principle of buoyancy may be used to create a level transmitter instrument, generating an output signal proportional to the change in weight of a displacer rod suspended in a liquid: Cap Vessel Process liquid Block valves displacer Weightmeasuring mechanism Displacer "cage" Drain valve Often, the displacer is housed inside its own cage for easy removal from the process, as shown above, or it may be inserted directly into the process vessel like this: Weightmeasuring mechanism Vessel displacer Process liquid If the vessel is open and the liquid inside is turbulent due to mixing or other agitation, a stilling well serves the same purpose as a cage: 4

Weight-measuring mechanism Vessel Process liquid Stilling well displacer To calibrate such an instrument, it must be isolated from the process liquid. Sometimes this means simply closing block valves and draining the cage. Other times it means removing the displacer mechanism from the vessel entirely. But once the displacer is hanging dry, there is the problem of simulating a 100% condition for calibration purposes. Describe a way to make the displacer think it is fully submerged in process liquid when it in fact is hanging freely in the air. Explain how you would be able to precisely and accurately simulate this condition, as well as any given condition of partial displacer submersion for that matter. file i00276 5

Question 5 The following storage vessel holds water. The hydrostatic-pressure level transmitter is located 5 feet below the bottom of the vessel, and the desired level measurement range is 8 feet to 12 feet: URV = 12 ft RV = 8 ft 4 ft 8 ft Water 5 feet transmitter Assuming a pneumatic transmitter with an output range of 3 PSI to 15 PSI, and a calibration accuracy of +/- 1% of span, complete the following calibration table for the transmitter: Process Percent of pressure Output signal Output signal Output signal level (ft) span (%) sensed ( W.C) ideal (PSI) min. (PSI) max. (PSI) 0 10 25 50 75 90 100 file i00257 6

Question 6 Determine the RV and URV settings for the water seal drum lever transmitter (T-21), assuming the RV point is at the lower nozzle and the URV point is at the upper nozzle (the two nozzles being 3 feet 8 inches apart from each other), and that the remote seal fill fluid has a specific gravity of 0.934: Flare tip PG 36 P flare gas header Dwg. 10143 ST ST A PG 35 S 19 19 ST PG 37 A A 22 23 Knockout drum G 20 IR 24 WirelessART C 21 I 21 T 21 Water seal drum S 22 G 25 T 24 Y 24 S 23 NC NC FO C 24 TT 27 RTD TT 26 FO TV 26 Process water Dwg. 13241 OWS V 24 ST PG 12 V 21 FC WirelessART TIR 27 TC 26 Steam T trap PG 10 30 PSI steam Dwg. 13249 NC OWS ST P condensate Dwg. 13249 file i02820 7

Question 7 Calculate the hydrostatic pressure generated at the bottom of this vessel (in units of PSI) when it is completely filled with water: Flow Overflow 11 ft (water) Pressure =??? Now calculate the hydrostatic pressure at the bottom of this vessel (in units of PSI) when it is completely filled with gasoline (density = 42 lb/ft 3 ): Flow Overflow 11 ft (gasoline) Pressure =??? 8

What do you think the pressure will be at the bottom of the vessel if it is exactly half-full of gasoline and half-full of water, with a gasoline-water interface at the 5.5 foot mark? Explain your reasoning. Flow Overflow 11 ft (gasoline) (water) Pressure =??? file i00308 Question 8 Calculate the differential pressure sensed by the level transmitter at three different water levels in this boiler steam-drum level measurement system: 0%, 50%, and 100%. Condensate pot 100% level Steam 10" 30" 0% level Water 9" Output 4-20 ma Assume a density for (hot) boiler drum water of 36 lb/ft 3, a density for steam in the drum of 7 lb/ft 3, and a density for (warm) water in the wet leg of 61.8 lb/ft 3. If the pressure at the low () side of the transmitter is greater than the pressure at the high () side, be sure to express the differential pressure quantity as a negative number. Credit will be given for correctly calculating each of the differential pressures: (6 points) Transmitter P at 0% water level = (6 points) Transmitter P at 50% water level = (6 points) Transmitter P at 100% water level = file i00516 W.C. W.C. W.C. 9

Question 9 A displacer-type density transmitter registers a displacer weight of 6.3 pounds with the cage completely full of sample liquid. The displacer has a dry weight of 14 pounds, a density of 120 lb/ft 3, and is cylindrical in shape. Calculate the density of the liquid in units of pounds per cubic foot. file i00283 Question 10 Determine a basic 5-point (0%, 25%, 50%, 75%, and 100%) calibration table for the displacer level transmitter in this scenario: 100% Measurement span = 40 in Water Block valves displacer 100% Measurement span = 40 in 0% 0% The cylindrical displacer weighs 15 pounds (dry) and has a diameter of 2 inches. The process liquid is water. The 0% process liquid level (RV) is even with the bottom of the displacer. Assume an electronic transmitter mechanism with an output range of 4 to 20 ma. file i00508 Process Percent of Buoyant Output signal level (in) span (%) force (lb) ideal (ma) 0 25 50 75 100 10

Question 11 Determine a basic 5-point (0%, 25%, 50%, 75%, and 100%) calibration table for the displacer level transmitter in this scenario: 100% Measurement span = 20 in Water Block valves displacer 100% Measurement span = 20 in 0% 0% The cylindrical displacer weighs 9 pounds (dry) and has a diameter of 2 inches. The process liquid is water. The 0% process liquid level (RV) is even with the bottom of the displacer. Assume an electronic transmitter mechanism with an output range of 4 to 20 ma. file i00509 Process Percent of Buoyant Output signal level (in) span (%) force (lb) ideal (ma) 0 25 50 75 100 11

Question 12 When installing a hydrostatic level transmitter on a working process, one must determine the proper lower- and upper-range values (RV and URV) for the transmitter in order to properly register 0% at the RV liquid level and 100% at the URV liquid level. If all fluid densities and physical dimensions are known in advance, this is a simple matter of a few mathematical calculations. owever, sometimes it is difficult to know all the physical dimensions in advance, especially the elevation or suppression. Consider this example, assuming clean water as the process liquid and a static pressure of 0 PSIG inside the (vented) process vessel: (vent) 38.5 inches URV Sightglass 17.3 inches RV T 1 Overview 2 PV 47.900 3 AO 11.664 4 RV 0.000 5 URV 100.00 ART communicator in2o ma in2o in2o This transmitter has already been calibrated at the instrument shop to accurately register applied pressure, but its range values have not been customized to the installation. Using a tape measure, we find a vertical distance of 38.5 inches between the RV and URV points marked on the sightglass, and we also see the current liquid level is 17.3 inches above the marked RV point. Using a ART communicator to interrogate this smart transmitter, we see that the registered pressure at this process condition is 47.9 inches of water column ( WC), which is greater than 17.3 inches registered by the sightglass due to the transmitter s suppression (physical location beneath the RV point, creating a hydrostatic pressure simply due to process water inside the impulse tube). Based on this information alone, calculate the appropriate RV and URV settings to program into the smart transmitter, so that it will output 4 ma when the process water level is at the RV height and 20 ma when the water level is at the URV height: RV = WC URV = WC file i02870 12

Answer 1 Answers If the liquid level in the vessel rises to 7 feet, the transmitter should (ideally) output a final signal corresponding to 7 feet of level. owever, since the transmitter in question is a hydrostatic pressure type, and the liquid density has increased as well, it will not register accurately anymore. The old specific gravity was 1.12, and the new specific gravity is 1.35. The error in span will be the ratio of the new specific gravity to the old, or 1.35/1.12 = 1.2054. In other words, the new acid/water mixture is 1.2054 times denser than it is supposed to be, according to how the transmitter was calibrated. Thus, the transmitter output will correspond to a liquid level of 7 feet times the error factor of 1.2054, or 8.4375 feet. A good way to solve this problem is to apply the problem-solving technique of simplification. Imagine the two specific gravities being much simpler numbers: 1 and 2 instead of 1.12 and 1.35, respectively. It should be obvious now that a doubling of specific gravity will result in a doubling of level indication (i.e. the transmitter will register twice as much liquid level as there actually is inside the vessel). It should also be obvious that the error factor is 2:1, which is precisely the ratio of new:old specific gravity. Alternatively, liquid level could be measured with a float, a capacitive sensor, ultrasonic or radar gauge, or some other instrument functioning on the detection of the liquid/vapor interface. 13

Answer 2 The transmitter output will stay the same. If you thought that the transmitter output would decrease due to the water becoming less dense, I recommend you explore the concept of density a little deeper with the following thought experiment: Imagine the vessel filled half-way with liquid. Imagine that liquid heating up and expanding until it is only half as dense as it was at the beginning of the experiment. Calculate the new hydrostatic pressure with the expanded, less-dense liquid. In a way, this is a trick question. As any given mass of water heats up, its volume will increase. This is what makes it less dense than before: increased volume with the same mass (weight). Knowing how to calculate hydrostatic pressure from height and specific gravity, you might have approached this problem by assuming the water column height would have stayed the same while its density decreased, resulting in a lesser hydrostatic pressure and decreased transmitter output. owever, this answer is incorrect. If the water volume expands as a result of a temperature increase, the level inside the vessel must rise, because it will require a higher vessel level to contain a greater volume of water. The level will rise by the same percentage that the density decreases, resulting in a cancellation of level increase with density decrease. As a result, the hydrostatic pressure at any point in the vessel remains constant. If you have difficulty picturing this effect, consider an exaggerated example to make things simpler. Suppose that a vessel has been filled to a height of 10 feet with cold liquid: 10 feet cold Pressure transmitter Now, imagine that same vessel being heated until the liquid expands to exactly twice its former volume: 14

10 feet hot (twice original volume) 10 feet Pressure transmitter Source of heat The liquid level must double to accommodate twice the volume in the same vessel, assuming a vessel of constant diameter, and its density will be cut in half (twice the volume with the same mass). Consequently, the two factors of liquid level change and liquid density change cancel each other out to give the exact same hydrostatic pressure as before. In other words, the transmitter will register the same liquid level as it did when the liquid was cold, and will output the exact same signal, even though the actual vessel level is quite a bit more than it was when cold. Pretty tricky, huh? 15

Answer 3 Any vapor pressure will be sensed by the transmitter and interpreted as increased liquid level! Two solutions to this problem: (1) Use two transmitters (one at top of vessel, one at bottom) and electronically subtract their output signals. (2) Connect the ow side of the one P transmitter to the top of the vessel to naturally compensate for vapor pressure. Since the transmitter infers level from the amount of pressure sensed at the bottom of the vessel, any vapor pressure buildup inside the vessel will be falsely interpreted as additional liquid level, since the transmitter senses the sum total of hydrostatic pressure plus any vapor pressure trapped inside the vessel. For example, if the process liquid level were at 10 feet (50% of range), the hydrostatic pressure generated by the liquid column would be 120 inches W.C., assuming a specific gravity of 1.0, equal to water. If, however, the vessel contained a vapor pressure equal to 15 inches W.C., this pressure would add with the 120 inches W.C. of pressure generated by liquid head to create 135 inches W.C. of total pressure sensed by the transmitter. As a result, the transmitter would think it was detecting a liquid level of 11.25 feet (135 inches high) instead of the true level of 10 feet (120 inches high). Essentially, any vapor pressure in the vessel results in a zero shift of the transmitter s indication. In many applications, the gas pressure inside a vessel far exceeds the hydrostatic pressure generated by the column of liquid inside of it, so this problem can be a very serious one in level measurement. We need to fully understand the nature of the problem and how to solve it in order to successfully measure liquid level in many industrial applications. The solution to this dilemma is to measure the difference in pressure between the top and bottom of the vessel. We could do this by using two pressure transmitters, one at the top and one at the bottom, and detect hydrostatic pressure by subtracting the top transmitter s measurement from the bottom transmitter s measurement. A computer may be used to perform the mathematical subtraction of signals: (small) vent Pressure transmitter pressure A-B B Output 20 feet Process liquid S.G. = 1.0 Pressure transmitter A Another, more elegant method, incorporates a differential pressure transmitter with pipe connections to both ends of the vessel. This solution performs the subtraction mechanically, by directly exposing the transmitter s sensing element to the difference of two applied pressures: 16

(small) vent pressure Pipe or tubing 20 feet Process liquid S.G. = 1.0 Differential pressure transmitter Output Pipe or tubing Because the differential pressure transmitter solution requires only one sensing instrument rather than two, and results in better accuracy because we are only dealing with the inaccuracies of a single instrument rather than the compounded inaccuracies of two instruments (three, if you include the subtraction unit), the differential, or d/p solution is the one more widely used. In this particular level measurement application, a differential pressure instrument would have the exact same calibration points (lower and upper range-values) as a normal pressure transmitter connected to an open vessel. 17

Answer 4 One way to simulate a full condition is to use a hand scale: "Dry" calibration Pull up on string until scale registers the desired force Scale Vessel Process liquid valves closed displacer Weightmeasuring mechanism iquid drained out of cage valve open Answer 5 Process Percent of pressure Output signal Output signal Output signal level (ft) span (%) sensed ( W.C) ideal (PSI) min. (PSI) max. (PSI) 8 0 156 3 2.88 3.12 8.4 10 160.8 4.2 4.08 4.32 9 25 168 6 5.88 6.12 10 50 180 9 8.88 9.12 11 75 192 12 11.88 12.12 11.6 90 199.2 13.8 13.68 13.92 12 100 204 15 14.88 15.12 18

Answer 6 The elevation for this transmitter (i.e. the total differential pressure applied by the height of fill fluid on both sides) is equal to the total height difference between the remote seal diaphragms multiplied by the specific gravity of the fill fluid: P elevation = (44 in)(0.934) = 41.1 WC In the RV condition, this is the only pressure seen by the transmitter. Therefore, 41.1 WC is the appropriate RV setting for this transmitter. If we assume that the port of this DP transmitter connects to the lower nozzle, the RV will be -44.1 WC. If we assume the port connects to the upper nozzle, the RV will be +41.4 WC. In the URV condition, we have the exact same amount of elevation (the fill fluid inside the capillary tubes) but on the lower nozzle we have the hydrostatic pressure of 44 vertical inches of water (i.e. the water inside the seal drum). Thus, in the URV condition the transmitter sees a differential pressure of: P differential = 44 WC 41.1 WC = 2.9 WC If we assume the port of this DP transmitter connects to the lower nozzle, the URV will be +2.9 WC. If we assume the port of this DP transmitter connects to the upper nozzle, the URV will be -2.9 WC. URV = -2.9 "WC URV = +2.9 "WC RV = +41.1 "WC T 21 RV = -41.4 "WC T 21 Answer 7 ydrostatic pressure when completely full of water = 4.769 PSI ydrostatic pressure when completely full of gasoline = 3.208 PSI ydrostatic pressure when water-gasoline interface is at the 50% level = 3.988 PSI Answer 8 (6 points) Transmitter P at 0% water level = -38.832 W.C. (6 points) Transmitter P at 50% water level = -31.864 W.C. (6 points) Transmitter P at 100% water level = -24.896 W.C. Answer 9 The liquid has a density of 66 pounds per cubic foot. 19

Answer 10 Process Percent of Buoyant Output signal level (in) span (%) force (lb) ideal (ma) 0 0 0 4 10 25 1.135 8 20 50 2.270 12 30 75 3.405 16 40 100 4.540 20 Answer 11 Process Percent of Buoyant Output signal level (in) span (%) force (lb) ideal (ma) 0 0 0 4 5 25 0.567 8 10 50 1.135 12 15 75 1.702 16 20 100 2.270 20 Answer 12 If the transmitter registers an actual applied pressure of 47.9 WC when the process water level is known to be 17.3 inches above the RV, it means the transmitter must be mounted 30.6 inches below that RV height: 47.9 WC 17.3 WC = 30.6 WC This 30.6 inch suppression then becomes the transmitter s lower-range value, so that it will output 4 ma (0% signal) when the process water level is at the RV height and the only pressure sensed by the transmitter is the hydrostatic pressure produced by water inside the 30.6 vertical inches of impulse tube. The necessary upper-range value is simply this RV added to the known span of 38.5 inches: 30.6 WC + 38.5 WC = 69.1 WC RV = 30.6 WC URV = 69.1 WC 20