LOW GAS PRESSURE REGULATOR WITH OR WITHOUT INCORPORATED SAFETY SHUT-OFF DEVICE TYPE: 123 (shut-off device: - for high pressure VP - for high and low pressure VNP) REGULATOR NISKOG PRITISKA BEZ I SA BLOKADNIM MEHANIZMOM TIP: 123 (blokada od: - visokog pritiska VP - visokog i niskog pritiska - VNP) TECHNICAL MANUAL TEHNI^KI KATALOG
INTRODUCTION Pressure regulator type: 123 is direct action device for low pressure, which ensure a constant downstream pressure (p 2 ). The regulator is controlled by a diaphragm and spring. They can be provided with shut-off device for low and high pressure or for high pressure. They can be used with natural gas, LPG, air, nitrogen, etc. UVOD Regulator pritiska tip: 123 predstavlja regulator direktnog dejstva koji obezbeñuje konstantnu vrednost izlaznog pritiska (p 2 ). Regulacija pritiska se vrši pomoću membrane i opruge. Regulator se izvodi i sa sigurnosno prekidnim mehanizmom (odnosno blokadnim mehanizmom) i to za visoki i niski pritisak ili za visoki pritisak. Koristi se za prirodni gas, tečni naftni gas, vazduh, azot, itd. Picture 1. / Slika 1. Type: 123 / Tip:123 Version without safety shut-off device/ Varijanta bez blokadnog mehanizma Picture 2./ Slika 2 Type: 123-BV/ Tip:123-BV Version with safety shut-off device/ Varijanta sa blokadnim mehanizmom MAIN FEATURES - Design pressure (PS): 25 bar - Ambient temperature: -20ºC +60 ºC - Max inlet pressure: 12 bar - Range outlet pressure: 0,01 0,3 bar - Nominal size: DN40, DN50 - Nominal pressure: PN16, PN25, ANSI 150 - Regulating characteristics: OSNOVNE KARAKTERISTIKE - Projektni (PS): 25 bar - Temperatura okoline: -20ºC +60 ºC - Max ulazni pritisak: 12 bar - Opseg izlaznog pritiska: 0,01 0,3 bar - Nazivne dimenzije: DN40, DN50 - Klasa pritiska: PN16,PN25, ANSI 150 - Regulacione karakteristike: DN p 2 AC SG p bl AG DN p 2 RG ZG p bl AG 40 0,01 0,1 10 20 VP 0,03 1,0 2,5 40 0,01 0,1 10 20 VP 0,03 1,0 2,5 50 0,1 0,3 5 10 NP 0,002 0,3 5 50 0,1 0,3 5 10 NP 0,002 0,3 5 Table 1. - Connections according to EN 1092-1, EN 1759-1 - Face to face dimensions according to EN 334 - Available nozzle diametar (mm): see Tables 3 4 - With relief valve: p open = (p 2 +30 mbar ±10%), where are: p open relief valve opening pressure, p 2 outlet pressure Tabela 1. - Prirubnice u skladu sa EN 1092-1, EN 1759-1 - Ugradbene mere u skladu sa EN 334 - Raspoloživi prečnici dizne (mm): videti Tabele 3 4 - Sa odušnim ventilom : p otv = (p 2 +30 mbar ±10%), gde je: p otv pritisak otvaranja odušnog ventila, p 2 izlazni pritisak
REGULATOR OPERATION In the absence of pressure, gas pressure regulators type: 123 and type: 123-BV are in open position. Inlet pressure acting upon diaphragm (1), thus overcoming the spring (2) action, and through diaphragm assembly and lever (3) move the rod (4) with pad unit (5). When outlet pressure increase up to presset value, the nozzle (6) is completely closed by pad unit. Increasing inlet pressure up to value of completely closed nozzle is defined by lock-up pressure (SG). Gas consuption cause outlet pressure decreasing, and cause opening nozzle by moving pad unit. This is main gas regulator function: Maintaing constant outlet pressure which is defined by accuracy class (AC). Set point pressure is established by the adjusting ring (7). In order to increase the outlet pressure, rotate clockwise the adjusting ring, and to decrease the outlet pressure rotate counterclockwise the adjusting ring. OPIS RADA Regulato pritiska tip: 123 i tip: 123-BV su u početnom stanju otvoreni. Puštanjem gasa u instalaciju, pritisak deluje na donju površinu membrane (1) i savlañuje silu opruge (2) i preko membranskog sklopa i poluge (3) gura trn (4) i zatvarač (5). Zatvarač pritvara sedište (6) do potpunog zatvaranja kada vrednost izlaznog pritiska dostigne podešenu vrednost p iz. Porast pritiska do trenutka zatvaranja definisan je zatvornom grupom (ZG). Potrošnja gasa prouzrokuje pad izlaznog pritiska što dovodi do ponovnog otvaranja reglatora i obavljanje njegove osnovne funkcije: održavanje konstantnog izlaznog pritiska gasa u okviru zadatih granica odstupanja definisanih regulacionom grupom (RG). Vrednost izlaznog pritiska se podešava pritezanjem opruge pomoću pritezača opruge (7), sabijanjem opruge vrednost raste i obrnuto. Picture 3. / Slika 3. Gas pressure regulator type: 123-BV / Regulator pritiska gasa tip: 123-BV GT-123-01 2
SHUT-OFF DEVICE OPERATION Gas pressure regulator equiped with shut-off device is called 123-BV. Protecting the instalation and the consumers after regulator against extreme (high and low) pressure is the basic function of shut-off device (protection against only high pressure upon request). Shut-off device for protection against high and low pressure is type: GT.BM.VNP.02.65.P and for high pressure protection is type: GT.BM.VP.02.65.P. Operation shut-off device for protection against low and high pressure type: GT.BM.VNP.02.65.P is explained in folowing text. Outlet pressure intake through the pulse pipe under the diaphragm assembly (1). Pressure increasing move the diaphragm assembly upper, through lever (2) cause moving of pusher (11) which release the ball (3) from the rod (4). The rod under the spring (5) load move the valve disc (6) to close the nozzle. Increasing outlet pressure act uppon diaphragm assembly and overcome the high pressure spring (7) load (VP). Decreasing outlet pressure move the diaphragm assembly down under the low pressure spring (8) load (NP) and through lever move the pusher and release the ball from the rod. Activate pressure is realized by setting springs (7) and (8) by adjusting ring for VP (9) and adjusting ring NP (10). Rotate adjusting ring clockwise for increase pressure or rotate adjusting ring counterclockwise to decrease activating pressure. Shut-off device is manualy reset by pulling handle (12). Shut-off device used only for protection against high pressure (type: GT.BM.VP.02.65.P) is equipied without spring NP (8) and adjusting ring for NP (10). OPIS RADA BLOKADNOG MEHANIZMA Regulator pritiska tip:123-bv se izvodi sa integrisanim blokadnim mehanizmom. Blokadni mehanizam štiti instalaciju i potrošače posle regulatora od previsokog i preniskog pritiska,. Blokadni mehanizam za zaštitu od previsokog i preniskog pritiska je tip: GT.BM.VNP.02.65.P, a za zaštitu od previsokog pritiska je tip: GT.BM.VP.02.65.P. Opis rada blokadnog mehanizma za zaštitu od preniskog i previsokog pritiska tip: GT.BM.VNP.02.65.P opisan je u tekstu ispod. Izlazni pritisak se impulsnim vodom dovodi ispod membranskog sklopa (1) blokadnog mehanizma. Porast pritiska prouzrokuje pomeranje membranskog sklopa na gore koji preko poluge (2) povlači trn (11) čime je osloboñena kuglica (3) a samim tim i osovinica (4) koji pod oprugom (5) gura zatvarač (6) na sedište. Pri porastu izlaznog pritiska membranski sklop savlañuje oprugu VP (7). Pad izlaznog pritiska dovodi do pomeranja membranskog sklopa usled sile opruge NP (8), koji preko poluge povlači osovinicu i oslobaña kuglicu, odnosno otključava bravu blokadnog mehanizma. Podešavanje pritiska aktiviranja obezbeñuje se pomoću pritezača opruge VP (9) i pritezača opruge NP (10). Okretanjem pritezača u smeru kazaljke na satu, povećava se pritisak aktiviranja i obrnuto. Blokada se ručno deaktivira povlačenjem ručnog potiskivača (12). Kod blokadnog mehanizama samo za zaštitu od previsokog pritiska GT.BM.VP.02.65.P, ne ugrañuju se pozicije (8) i (10). Picture 4. / Slika 4. Shut-off device type: GT.BM.VNP.02.65.P / Blokadni mehanizam tip: GT.BM.VNP.02.65,P GT-123-01 3
OVERALL DIMENSION / GABARITNE DIMENZIJE Picture 5. / Slika 5. Dimension / Dimenzije mere DN A B C D E F G H I J [mm] 40 465 350 295 100 290 95 200 170 265 145 50 475 350 295 115 300 105 230 170 265 150 Table 2. / Tabela 2.
FLOW RATES TABLE Stm 3 /h / TABELE PROTOKA Stm 3 /h Folowing flow table referred to natural gas / Tabele protoka se odnose na prirodni gas
For other gases with differnt densities, the flow rate must be multipied by the correction factor: / Za druge gasove, vrednosti iz tabele se množe sa korekcionim faktorom: 0,78 where ρ G is gas density at temperature t = 0 C and pressure p = 1,01325 bar / gde je ρ G gustina tog gasa na temperaturi t = 0 ºC i pritisku p = 1,01325 bar. For usual used gases correction factor is shown in folowing table 8. / Korekcioni faktor za najčešće korišćene gasove dat je u tabeli 8. Gas / Gas Relative density / Gustina [kg/stm 3 ] Correction factor f / Korekc. faktor f Butane / Butan 2,01 0,53 Propane / Propan 1,53 0,62 Air / Vazduh 1 0,77 Nitrogen / Azot 0,97 0,79 Table 5. / Tabela 5. "GasTeh" d.o,o. Kralja Petra I b.b. 22320 Indjija Serbia tel/fax: +381022/561-630 e-mail: office@gasteh.com www.gasteh.com GT-123-01 6