Pressure Independent Control Valve (PICV) Fig DN15-32

Similar documents
PRESSURE INDEPENDENT CONTROL VALVE (PICV)

CONSTANT FLOW REGULATOR (CFR)

THERMOSTATIC MIXING VALVES

2-port seat valves PN25 with externally threaded connections

Pressure independent control valve (PICV) FLOWMATIC

Two-port valves, male threaded, PN25

Engineering Data Sheet

Issue 1. Air Valves OUR GENIUS IS FITTINGS.

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

3776B FLANGED PRESSURE INDEPENDENT CONTROL VALVE (P.I.C.V.) PN 16 TECHNICAL DATA SHEET. Main features:

Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN

2-port and 3-port valves PN 16

Overview of types. T5-R B2/R B2 en v Subject to changes 1 / 4. k vs (Sequence 2)

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions

TBV-CM. Combined control & balancing valves for small terminal units For modulating control

differential pressure regulating valve - threaded

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

TA-FUSION-P. Combined control & balancing valves Pressure independent combined balancing and control valves with independent EQM characteristics

Harmony. Pressure Independent Balancing and Control Valve

3-port seat valves with externally threaded connection, PN 16

Simple Set. Pressure Independent Control Valves 2 Way 1/2-2

CLASS TLP Pressure Reducing Valve

Pressure Independent Control Series

GM Series Dual-Block Multi-Function Gas Control Valves

Products no longer available

2-Port Seat Valves with Flange, PN 16

2-Port Seat Valves with Flange, PN 16

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

TBV-CM. Combined control & balancing valves for small terminal units For modulating control NPT threads

2-port and 3-port seat valves, PN16

Three-port valves. Special versions with special stem sealing gland for: High temperature hot water C Thermo oils

Automatic balancing valves

Rp [ ] Sv min. [ ] C215QP-B 15 1/ C215QP-D 15 1/ C220QP-F 20 3/ [ ]

Overview of types. Technical data

Self-help Temperature Adjustment

Ballorex Dynamic Description. Versions. Benefits. Balancing

Technical data sheet. Type overview. Technical data. Safety notes. T5-R2.. Open-close en v Subject to changes 1 / 3

TA-FUSION-P. NPT threads / ANSI flanges

Overview of types. Technical data. Safety notes

CALEFFI. Ball zone valves. series /03 GB

Two-port seat valves

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

Cim 787 Variable orifice balancing valve

HERZ-Motorised flow controler

DS MZ, MZF, MJF THREE-PORT SEAT VALVES

Pressure independent balancing and control valve AB-QM DN

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

Differential Pressure Control Valve. Passim

TA-COMPACT-P. Combined control & balancing valves for small terminal units Pressure independent balancing and control valve (PIBCV)

Automatic balancing valves ASV

Pressure Independent Control Valves

Seated valves VRB 3, VRG 3

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

C 10 Pressure Reducing Valve

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

QPL... Pressure Switches. Siemens Building Technologies HVAC Products

VRB00 Series CLASS B SERVO REGULATED COMBINATION VALVES

BCVi43 Blowdown Control Valve

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

Type overview. R B2 en-gb subject to changes 1

VR46.5V(A)/VR86.5V(A) SERIES

Products no longer available

KTM 50 (DN ) Installation, maintenance and operating instructions

Dual Solenoid Gas Valve Installation

TA-Modulator. Combined control & balancing valves for small terminal units Pressure independent balancing and control valve for modulating control

2-Port and 3-Port Seat Valves with Female Thread, PN16

Twin & Triple Control Concealed Thermostatic Shower Valve

Differential Pressure Control Valve (DPCV)

k valve ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF installation guide aylesbury For valve sizes (DN):

STAD. Balancing valves DN (MD60, MD61, MD62)

Contents. 1. General information BROEN BALLOMAX Steel Ball Valves Approvals Quality Management...2

KKT Training Series: ECO Series, Preventative Maintenance

KAX VALVE ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF INSTALLATION GUIDE AYLESBURY FOR VALVE SIZES (DN):

Deluge Optimo Shower valve and kit 10032CP

130400A 1/2 NPT Female A 3/4 NPT Female A 1 NPT Female A 1 1/4 NPT Female A 1 1/2 NPT Female A 2 NPT Female

ATS430 turbidity sensor Retractable insertion assembly

Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G

Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G

Bermad Pressure Reducing. Model: 42T

GM-7000 Series CE Approved Gas Control Valve

2/2-Way Solenoid Control Valve

VK8515M(R) MODULATING GAS CONTROL APPLICATION DESCRIPTION SPECIFICATIONS INSTRUCTION SHEET. Electrical data

STAD. Balancing valves DN 15-50

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

STAD-D. Balancing valves Balancing valve for domestic water systems, DN Balancing valves

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Operator: Save these instructions for future use!

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Manual Actuated Boiler Blowdown Valves

BGA158 Series CE Approved Class A Shutoff Gas Valve

PRAHER PLC-MP AQUASTAR MANAUL 2009

Pressure Dump Valve Service Kit for Series 3000 Units

Air Differentail Pressure Switch

PCTV/PCMTV/PCTVS15-25

Pettinaroli Pressure Independent Control Valves. EvoPICV

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2

Model: 43T. Bermad Pressure Relief Valve

Transcription:

Installation and Operating Instructions Pressure Independent Control Valve (PICV) Fig. 1932 - DN15-32 GENERAL NOTES The Hattersley Fig.1932 PICV; can be used in variable volume heating and chilled water systems provides modulating control for terminal units when installed with a modulating actuator offers flow rate pre-setting has an equal percentage control characteristic at all pre-set flow rates has built in Differential Pressure Control has an operating temperature: -10 to 100 C has a maxiumum working DP = 3.5 bar has a maximum operating pressure: 16 bar has built in pressure test points to verify operational differential pressures These instructions apply to the Fig.1932 when installed as a standalone valve or when supplied as part of the Hattersley Hook-Up range. LIMITS OF USE These valves have been categorised in accordance with the Pressure Equipment Directive PED. The fluid to be transported is limited to Group 2 liquids i.e. non-hazardous. On no account must these valves be used on any Group 1 liquids, Group 1 gases or Group 2 gases.

INSTALLATION These instructions are issued as guidelines only and do not cover all installed conditions. If unsure please contact our Technical Helpline before installation. Hattersley products are designed for installation and use within suitably designed systems reflecting CIBSE, BSRIA and HVAC guidelines. Particular care should be taking with regards to; accessibility to valve for setting/adjustment tube cutting jointing bracketing/supports orientation: whilst the PICV can operate correctly in different orientations, there are recommendations regarding the orientation of actuators - see diagram on page 5 would normally be installed on return pipework, i.e. after the equipment it is controlling, but can be installed in flow if required ensure direction of flow is correct - indicated by cast arrow on body Fig.1932 operates between a minimum and maximum pressure drop across the valve - see commissioning PICV s are not designed as isolation valves. Dedicated isolation valves should be installed to isolate against system pressure, i.e. for maintenance etc., when disconnecting/draining pipework systems should be installed with strainers to protect the PICV and other installed items FLUSHING Control valves, like the PICV, are sized to give good control over the system water, therefore, have been designed with small convoluted flow path. These water ways may not allow adequate water velocities for flushing of the coil, even when fully open. Therefore, in line with BSRIA recommendations, it is recommended that a flushing point be located between the coil and the PICV. This allows the coil to be flushed without the water passing through the PICV. 02

Installation and Operating Instructions SET POSITION The PICV set position can be established by: 1. Calculation 2. Use of look up table on page 4 1. ESTABLISH SET POSITION BY CALCULATION Identify installed valve from ID Plate on bottom of valve From the chart below, establish maximum flow rate (P10 Flow) Divide required flow rate by fully open flow rate x 100 to establish % open setting: e.g. flow rate at 100% = 0.28 l/s required flow rate = 0.168 l/s (0.168 / 0.28)*100 = 60% 2. Use of look up table on page 4 Identify installed valve from ID Plate on bottom of valve Check flow rate required Read across chart: Valve = DN20 Required flow rate = 0.168 l/sec Set position = 6 To set the valve, use the setting key provided to close the valve (position 0), then re-open the valve by turning the setting key anti-clockwise until position 6 is reached. Remove the setting key. The valve is now ready for actuator to be fitted. COMMISSIONING The Fig.1932 controls the flow rate depending on its set position, therefore, removing the need to measure the flow rate. The Fig.1932 maintains a constant differential pressure across its internal seat, any excess pressure being removed by the internal differential pressure controller. To ensure that sufficient pressure is available for the differential pressure controller to control the flow rate correctly, a differential pressure reading should be taken using the test points provided. When taking differential pressure readings, it is important that the system is running at full load, i.e. with all PICVs open. This ensures that differential pressure readings are carried out in the most unfavourable conditions, guaranteeing optimum performance in normal running conditions. To ensure that all PICVs are working at the required differential pressure, it is necessary to check the least favoured / index PICV. By verifying the least favoured PICV is set to the required differential pressure, all other PICVs must have a higher differential pressure. However, we would also recommend that a selection of other PICVs are tested along the circuit to verify this. 03

DIFFERENTIAL PRESSURE REQUIREMENTS Each valve size (DN15LF-DN32) at each % setting option requires a specific (Differential Pressure) to ensure the PICV is within its working range; DN15 LF DN15 STD FLOW DN20 DN25 DN32 POS Typical FLOW POS Typical FLOW POS Typical FLOW POS Typical FLOW POS Typical FLOW 2 14 0.008 2 12 0.040 2 12 0.056 2 10 0.096 2 30 0.18 3 14 0.017 3 12 0.060 3 12 0.084 3 10 0.144 3 30 0.28 4 14 0.026 4 12 0.080 4 12 0.112 4 10 0.192 4 30 0.37 5 14 0.035 5 12 0.100 5 12 0.140 5 10 0.240 5 30 0.47 6 14 0.044 6 12 0.120 6 12 0.168 6 10 0.288 6 30 0.56 7 14 0.053 7 12 0.140 7 12 0.196 7 10 0.336 7 30 0.66 8 14 0.062 8 12 0.160 8 12 0.224 8 10 0.384 8 30 0.75 9 14 0.071 9 12 0.180 9 12 0.252 9 10 0.432 9 30 0.85 10 14 0.080 10 12 0.200 10 12 0.280 10 10 0.480 10 30 0.94 For flow rates in between settings, extrapolation of position can be used. The pump speed should be set to ensure that the required differential pressure is always available. By setting the differential pressure across the least favoured PICV to the value stated in the above table, it ensures that minimum pump energy is used, therefore, reducing system running costs and CO 2 emissions. To set pump speed to achieve this; whilst measuring ΔP, increase pump speed until a constant ΔP is achieved, however please note that the typical ΔP value, as shown in the table above, can differ but in itself is not important. The optimum setting is achieved when there is sufficient, but not excessive, pump pressure available. Flow rate verification should be carried out using separate Flow Measurement Devices (FMD) where fitted. In line with CIBSE & BSRIA recommendations, we recommend that as a minimum requirement, FMDs are installed in all branches. Where flow rate verification is required at terminals, FMDs may also have been installed at each terminal. Terminal flow rates can also be confirmed by measuring branch flow rates and closing individual terminal PICVs one at a time and measuring the reduction in flow at the branch. Care should be taken to ensure that reduced flow rates are still within the measuring range of the branch FMD, i.e. that the measured signal doesn t drop below 1kPa. 04

Installation and Operating Instructions ACTUATOR OPTIONS The Fig.1932 PICV is designed to work with ACT1932M modulating actuators, ACT1932TH three-point actuators and ACT991TH thermal actuators. (ACT1932TH for sizes DN15-DN25 only). For Installation, operating and maintenance guidance on the ACT991TP (Three Point) please see separate IOM shipped with the actuator. Hattersley cannot be held responsible for the control function if alternative actuators are used. ACT1932M (MODULATING) ACTUATOR: To fit the actuator, remove protective cap from the valve, and follow the installation instructions supplied with the actuator. The connecting thread on the valve and actuator is M30 x 1.5. Overall Dimensions Mounting Options Temperature Limits The LED at the front of the actuator signals actuator position: Off Green Blinking = Moving to position Solid Green = Position reached Red Blinking = Power on calibration Solid Red = Power failure no signal Actuator operation indicator Wiring Diagram 05

ON 1 2 3 4 5 6 CONNECTING TO VALVE Before fitting to valve: Ensure that spindle is fully retracted (1) Carefully align actuator and valve connection threads (2) Turn actuator connection nut clockwise to secure to valve (3) Hand tighten only (4) Do not over-tighten. ACTUATOR SETTING UP Customer only needs to remove lid if changing settings from default below. 1 Ensure that power supply is disconnected 2 Gently loosen actuator cover from main body 3 Remove cover, and keep in safe place ON OFF 1 2 3 4 5 6 ON OFF 1 2 3 4 5 6 0...10VDC 0...20mA DA LIN VDC 0...5VDC 1: CONTROL SIGNAL 2: RANGE 3: 5...10VDC RA Eq% * ma 2...10VDC 4...20mA 4: ACTION 5: CURVE 6: SIGNAL TYPE ELECTRO-MECHANICAL ACTUATOR: ACT1932M 24VAC/DC, 50/60Hz, 2.5VA 140N Min. - 8s/mm - IP43 0-10V Input Signal *Default setting 06

Installation and Operating Instructions 5 Aign to top cover 6 Refit to cover securely 7 Power supply can now be connected. THERMAL ACTUATOR: ACT1932TH (NORMALLY CLOSED) Thermal actuators are designed for ON/OFF control. Thermal actuators are small, light, and therefore a good choice for confined spaces. Thermal actuators are rated to IP54 and can be installed in any orientation. To fit the actuator, remove protective cap from the valve, and follow the installation instructions supplied with the actuator. The connecting thread on the valve and actuator is M30 x 1.5. FITTING THE ACTUATOR: The valve and actuator have matching threads. The actuator comes supplied with an adaptor ring, so no additional one is required. Simply screw the adaptor ring onto the valve and fit the thermal head onto it. Rotate the lower ring until you hear two clicks. The rotation of the lower ring of the actuator onto the valve sets the valve to its normally closed position. 07

WIRING INSTRUCTIONS When servicing make sure that: the electric supply to the actuator is switched off to avoid possible damage to the equipment, personal injury or shock make sure that the line power supply is in accordance with the power supply specified on the actuator all wiring should conform to local codes and must be carried out by authorized personally only do not touch or attempt to connect or disconnect wired when electric power is on do not open or attempt to repair, contact the Technical department.- BLUE BROWN BLACK GREY N L Mounting of the cable Wiring diagram Auxiliary switch wiring diagram Supply voltage for the Hattersley ACT1932TH actuator is 24V AC/DC and the actuator is Normally Closed. To visit our Video Library go to: www.youtube.com/user/cranebsu PO BOX 719, IPSWICH, IP1 9DU HOME SALES: +44 (0) 1744 458670 EXPORT SALES: +44 (0)1744 458671 TECHNICAL HELPLINE: 0845 604 1790 FAX: +44 (0)1744 26912 EMAIL: uksales@hattersley.com EMAIL: exportsales@hattersley.com FM00311 ISO 9001 Designed and manufactured under quality management systems in accordance with BS EN ISO 9001-2008 Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing. Hattersley assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the information within the publication and reserves the right to change without notice. H_PICV_0115 IOM_ 004B01932D799_v4 www.cranebsu.com