V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

Similar documents
V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

V146 Series 2-Way Pressure-Actuated Water-Regulating Valves

V43 Pressure Actuated Water Regulating Valve

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure

Series V48. 3-Way Pressure Actuated Modulating Valves. Product Bulletin. Features. Pressure balanced design. Free movement of all parts

Series V47 Temperature Actuated Modulating Valves

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G96 Series BASOTROL Dual Operator Valve

MEGR-1627 Instruction Manual

P499 Heavy Duty Pressure Transducer

GM-7000 Series CE Approved Gas Control Valve

G92 Series BASOTROL Automatic Pilot Gas Valve

Dual Solenoid Gas Valve Installation

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q= Cv S

H15 Series BASO 100% Shutoff, Automatic Pilot Valve

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Page 1 of 12

D05 Pressure Regulating Valves

TECHNICAL DATA. Q = C v P S

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

TECHNICAL DATA. Q = C v P S

P14 Series Pressure Actuated Mechanical Sequencer

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

V246 Series 2-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

BGA158 Series CE Approved Class A Shutoff Gas Valve

DS06D,G Dial Set Pressure Regulating Valve

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

Model Series 62 Constant Differential Relay

TECHNICAL DATA. Q = C v P S

BGC258 Series BASOTROL Gas Valve

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

DS05C,D,G Dial Set Pressure Regulating Valves

TECHNICAL DATA CAUTION

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

Installation, Operation and Maintenance Manual for Back Pressure Regulator

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

BGA158 Series CE Approved Class B Shutoff Gas Valve

Halsey Taylor Owners Manual STOP!

TECHNICAL DATA. Q = C v P S

GM Series Dual-Block Multi-Function Gas Control Valves

CROT-6 CROT-10 CRO-4. for Compressor Overload Protection

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

TECHNICAL DATA OBSOLETE

TECHNICAL DATA CAUTION

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

D05T Compact Design Pressure Regulating Valves

VB-7263 Series. Application. Features. Applicable Literature

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

VOLUMATIC WATER REGULATOR

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

VB-7273 Series. Application. Features. Applicable Literature

29 SERIES - SAFETY VALVE

Pressure Sensing Valve - Model 4023

3/8" Dr. Air Butterfly Impact Wrench

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Introduction. Description. Series P48 Pressure Controls for Steam, Air or (hot) Water. Feature and Benefits

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

Model GPR Primary Pressure Regulating Valve. Instruction Manual

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

Hydraulic Piston Accumulators

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

VBS-9263 Series. Application. Features. Applicable Literature

shutoff valves 900 Series psig Manual Shutoff Valves

Operation Manual Piston Sensed Gas Pressure Regulators

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Medical Gas Control Panel

64 Series Pressure Reducing Regulators

Model 40H Nullmatic Pressure Regulators

INSTRUCTIONS PARTS LIST

OPERATING AND MAINTENANCE MANUAL

1805 Series Relief Valves

A28 Series Two-Stage Temperature Controls with NEMA 1 Enclosure

INSTALLATION / OPERATION / MAINTENANCE INSTRUCTION

Engineering Data Sheet

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

Installation Instructions

INSTALLATION INSTRUCTIONS

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

Bermad Pressure Reducing. Model: 42T

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

BUTTERFLY VALVES Series 800

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

776 Cryogenic Safety Valve

Transcription:

Installation Instructions V46 Issue Date 11//1 V46 Series -Way Pressure-Actuated Water-Regulating Valves With Union Fittings Application IMPORTANT: The V46 Series -Way Pressure-Actuated Water-Regulating Valves are intended to control water flow under normal equipment operating conditions. Where failure or malfunction of the V46 valves could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the V46 valve must be incorporated into and maintained as part of the control system. Dimensions A C D B The V46 direct-acting models open on an increase in pressure. The V46 valves with Union fittings are available in 1/-in. through 1-1/4-in. sizes and may be used with standard non-corrosive refrigerants. Installation Port 1 Port E IMPORTANT: If these valves are installed on equipment that contains hazardous or regulated materials, such as refrigerants or lubricants, the installer and user should observe all regulations governing the handling and containment of those materials. Pressure connection and capillary as specified Figure 1: V46 Valve Dimensions For Models With Union Fittings IMPORTANT: It is recommended to apply a non-hardening, pliable sealant (Loctite 67 or equivalent) to the face of the copper tailpiece to compensate for slight piping misalignments and surface imperfections on union ends. Table 1: V46 Valve Dimensions, inches (millimeters) Code Number Valve A B C D E V46AJ-C 1/ in. 4-9/16 (11) 1-13/16 (47) 6-3/8 (16) 3-3/4 (96) V46EK-C 3/4 in. -3/8 (136) () 6-13/16 (173) 4-3/16 (6) -/8 (67) V46AL-C 1 in. 7-1/16 (179) 9-11/16 (46) -1/16 (11) 3-3/4 (9) V46AM-C 1-1/4 in. 7-3/16 (18) -/8 (67) -1/16 () 6-3/16 (1) 3-1/16 () 1 Johnson Controls, Inc. 1 Part No. 4-7664-1, Rev. A www.johnsoncontrols.com

Manually Flushing the Valve Manually flush the valve and fluid piping before and after installing, repairing, or replacing a valve to remove filings, chips, or other foreign matter. Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush the valve. See Figure. Manual flushing does not affect valve adjustment. Pressure Connections! WARNING: Risk of Personal Injury. Contents of liquid lines could be under pressure. Avoid possible personal injury by shutting off the liquid supply and relieving the pressure before servicing the valve. Range Spring Valve Spring Guide Top Retainer Range Adjustment Screw Insert screwdrivers underneath the valve spring guide. Connect the refrigerant-side flare connector to the appropriate high-side pressure tap point. If additional capillary tubing is necessary, use 1/4-in. copper tubing. Follow the guidelines below when making pressure connections: Use Pressure Tap Points Located on the Top Side of the Refrigerant Lines This reduces the possibility of oil, liquids, or sediment accumulating in the pressure connection line or valve bellows, which could cause valve malfunction. Figure : Manual Flushing Location Considerations Install the valve vertically with the range adjustment screw on the top and the bellows and pressure connection line on the bottom to allow drainage of oil and refrigerant away from valve bellows. Do not mount the valve in any position other than vertical unless specified by the manufacturer of the equipment on which the valve is installed. Follow the manufacturer's installation instructions. Install the valve on the inlet side of the condenser. If it is necessary to keep the condenser flooded with water, the valve may be installed on the outlet side of the condenser. If the system is located in an area with high ambient temperatures, refrigerant head pressures may remain high enough during off cycles to prevent the valve from closing completely. In such instances, the opening point of the valve should be raised just enough to cause the valve to close flow to the condenser during compressor standby periods. IMPORTANT: After installing the valve, evacuate bellows and pressure connection lines, in accordance with EPA and other regulations, to remove air, moisture and other contaminants. Avoid Sharp Bends in the Capillary Tubes Sharp bends can weaken or kink capillary tubes, which may result in refrigerant leaks or restrictions. Allow for Slack in the Capillary Tubes to Dampen Vibration Mechanical vibration can weaken or damage the capillary tubes. Avoid Contact Between the Capillary Tubing and Sharp or Abrasive Objects Vibration or rubbing of sharp or abrasive objects in contact with capillary tubes can cause leaks. Coil and Secure Excess Capillary Tubing Away from Contact with Sharp or Abrasive Objects or Surfaces Carefully loop any excess capillary tube into smooth, circular coils (minimum in. [ cm] diameter). Securely fasten the coiled capillary tube. Do Not Overtighten Flare Nuts on Pressure Connection Line Fittings Overtightening flare connections may damage the threads and result in refrigerant leaks. Do not exceed 9 lb ft (1 N m) of torque when tightening brass flare connections. V46 Series -Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions

Avoid Severe Pressure Pulsation at Pressure Tap Points Install pressure connection lines to pressure tap points away from the compressor discharge, to minimize the affects of pressure pulsation from reciprocating compressors. Table : Specifications for V46 Series Valves with Union Fittings Code Number Valve Maximum Refrigerant Pressure at Bellows Opening Point Adjustment Range Factory-Set Opening Point V46AJ-C 1/ in. 3 psi (6 kpa) 7 to psi (483 to 1793 kpa) 16 psi (1138 kpa) 4 V46EK-C 3/4 in. 37 psi (1 kpa) 46 V46AL-C V46AM-C 1 in. 1-1/4 in. 3 psi (6 kpa) Pressure Connection Style Style 4 Style 46 Copper Capillary with 1/4-in. SAE Female Flare Connector (Includes Valve Stem Depressor) Copper Capillary with 1/4-in. SAE Female Flare Connector (Includes Valve Stem Depressor) Figure 3: Pressure Connection Styles Setup and Adjustments The V46 valves are factory adjusted for the settings shown in Table 3. The opening point pressure is the refrigerant pressure (at the valve s bellows) necessary to just lift the valve disc off of the valve seat and allow water to flow through the valve body. Turning the range adjustment screw changes the opening point pressure. Use a standard service valve wrench or screwdriver to adjust the opening point pressure. Turn the range adjustment screw counter-clockwise to raise the opening point pressure. Turn the range adjustment screw clockwise to lower the opening point pressure. Use a refrigerant pressure gauge to adjust the opening point pressure. Operate the system at normal load conditions and adjust the valve s opening point to the desired pressure. See Table 3 for refrigerant pressure specifications. charts 1 1/-in. V46 - All Range Above Opening Point Figure 4: 1/-in. V46 Valve V46 Series -Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions 3

4 3 1 3/4-in. V46 - All Range Above Opening Point 8 7 Figure : 3/4-in. V46 Valve 1-in. V46 Valve - All Range 1 3 4 Refrigerant Through Valve 8 7 1-1/4-in. V46 - All Range Above Opening Point Figure 7: 1-1/4-in. V46 Valve Repairs and Replacement Replacement of the sensing element, internal parts, and the rubber diaphragm can be made. For a replacement valve or replacement parts kit, contact the nearest Johnson Controls/PENN distributor. For replacement kit part numbers, refer to Table. For replacement kit instructions and details, refer to the following bulletins: V46, V47, 46, and 47 Repair Parts and Service Instructions Repair Parts Bulletin, LIT-1169 V46, V47, V48, and V49 Sensing Element Replacement Technical Bulletin, LIT-117 Figure 6: 1-in. V46 Valve Table 3: Repair and Replacement Kits Valve Code Number Shipping Weight Seat Repair Kit Code Number Sensing Element Replacement Kit Code Number V46AJ-C 1/ in. 3.3 lb (1.kg) STT1A-R SEP91A-R, SEC99AB-48C V46EK-C 3/4 in. 4.3 lb (.kg) STT16A-1R SEP91A-1R, SEC99AB-48C V46AL-C 1 in. 9.3 lb (4.kg) STT17A-9R SEP91A-3R, SEC99AB-48C V46AM-C 1-1/4 in.. lb (4.kg) STT17A-6R SEP91A-3R, SEC99AB-48C 4 V46 Series -Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions

Technical Data Body Material Extension Sleeve, Disc, Stud, Disc Holder Material Valve Seat Material Valve Disc Diaphragm Water Supply Pressure Water Supply Temperature V46 Series -Way Pressure-Actuated Water-Regulating Valves 1/-in. and 3/4-in. s - Cast Brass Bodies, 1-in. and 1-1/4-in. s - Cast Iron Bodies with Rust-Resisting Finish Brass Aluminum Bronze Buna-N Nylon Reinforced Buna-N 1 psig (34 kpa) Maximum 17 F (77 C) Maximum Water See Figures 4-7. Sensing Element Pressure Range See Table 3. Shipping Weight See Table. Brass and Phosphor Bronze Bellows in Brass Cup The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, contact Refrigeration Application Engineering at (8) 7-676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 7 E. Michigan Street P.O. Box 43 Milwaukee, WI 31 Printed in U.S.A. www.johnsoncontrols.com V46 Series -Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions