V146 Series 2-Way Pressure-Actuated Water-Regulating Valves

Similar documents
V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

V43 Pressure Actuated Water Regulating Valve

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

Series V48. 3-Way Pressure Actuated Modulating Valves. Product Bulletin. Features. Pressure balanced design. Free movement of all parts

Series V47 Temperature Actuated Modulating Valves

V246 Series 2-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q= Cv S

DS06D,G Dial Set Pressure Regulating Valve

TECHNICAL DATA. Q = C v P S

D05 Pressure Regulating Valves

TECHNICAL DATA. Q = C v P S

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

TECHNICAL DATA. Q = C v P S

MEGR-1627 Instruction Manual

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

TECHNICAL DATA. Q = C v P S

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

TECHNICAL DATA. Q = C v P S

D05T Compact Design Pressure Regulating Valves

DS05C,D,G Dial Set Pressure Regulating Valves

P499 Heavy Duty Pressure Transducer

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

TECHNICAL DATA OBSOLETE

VB-7263 Series. Application. Features. Applicable Literature

G96 Series BASOTROL Dual Operator Valve

GM-7000 Series CE Approved Gas Control Valve

Model: 43T. Bermad Pressure Relief Valve

VB-7273 Series. Application. Features. Applicable Literature

G92 Series BASOTROL Automatic Pilot Gas Valve

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

VBS-9263 Series. Application. Features. Applicable Literature

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Bermad Pressure Reducing. Model: 42T

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Dual Solenoid Gas Valve Installation

Model GPR Primary Pressure Regulating Valve. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

CROT-6 CROT-10 CRO-4. for Compressor Overload Protection

TECHNICAL DATA CAUTION

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

BGC258 Series BASOTROL Gas Valve

A28 Series Two-Stage Temperature Controls with NEMA 1 Enclosure

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

OPERATING AND MAINTENANCE MANUAL

GM Series Dual-Block Multi-Function Gas Control Valves

Pressure Sensing Valve - Model 4023

TECHNICAL DATA. Page 1 of 12

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Model 7989T Steel Pipe Squeezer Sch. 40 & Sch. 80. Operations Manual

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

H15 Series BASO 100% Shutoff, Automatic Pilot Valve

A t. VB-7323 Series. Application. Features. Applicable Literature. l/2 to 2 Screwed NPT SIEBE

P14 Series Pressure Actuated Mechanical Sequencer

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

C 10 Pressure Reducing Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve

Pressure Regulator B-95

CASH VALVE TYPE KP BACK PRESSURE VALVES

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Water valve Type WVO. Data sheet MAKING MODERN LIVING POSSIBLE

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

BGA158 Series CE Approved Class B Shutoff Gas Valve

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Model Series 62 Constant Differential Relay

VB Series. Application. Features. Applicable Literature. 1/2 to l-1/4 Union End NPT Stem Up Open, Two-Way Valves General Ins tructions

Engineering Data Sheet

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

TECHNICAL DATA CAUTION

776 Cryogenic Safety Valve

KOBOLD KSM FLOWMETER. User Instructions

Anti-flood device Model B-1

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

Simple Set. Pressure Independent Control Valves 2 Way 1/2-2

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

2.0 INSTALLATION & SERVICE

Application Worksheet

1 Exam Prep. Tabs and Highlights

Back Pressure Regulator

PENBERTHY SUBMERSIBLE AUTOMATIC SUMP DRAINER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

SPECIFICATIONS. Approximate Weight: 10 oz. Surface Finish: Ra micro inch or less MATERIALS OF CONSTRUCTION

1805 Series Relief Valves

1305 Series Pressure Reducing Regulators

Transcription:

roduct/technical Bulletin V146 Issue Date November 20, 2002 V146 Series 2-Way ressure-actuated Water-Regulating s The V146 Series 2-Way ressure-actuated Water-Regulating s regulate water flow and control refrigerant head pressure in systems with water-cooled condensers. The V146 valves are ideal for applications with system water pressures of up to 350 psig (2413 ka), such as high-rise buildings. Use V146 valves with standard non-corrosive refrigerants. V146 valves have a monel (nickel-copper alloy) seat and disc holder. Figure 1: V146 Features and Benefits No Close-Fitting or Sliding arts in Water assages High-ressure Design ressure-balanced Design Corrosion-Resistant Material for Internal arts Accessible Range Spring Take-Apart Construction rovides control in less-than-ideal water conditions Allows use in systems with up to 350 psig (2413 ka) water pressure Resists changes to setpoint caused by gradual or sudden water pressure changes romotes long valve life Allows easy manual flushing Allows access to valve interior without removing valve from refrigeration system or pumping down the system 2002 Johnson Controls, Inc. 1 Code No. LIT-121709 www.johnsoncontrols.com

Application IMORTANT: The V146 Series 2-Way ressure-actuated Water-Regulating s are intended to control water flow under normal equipment operating conditions. Where failure or malfunction of a V146 valve could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the V146 valve must be incorporated into and maintained as part of the control system. V146 valves regulate flow in systems with water pressures up to 350 psig (2413 ka). The opening point is adjustable within in a refrigerant pressure range of 70-260 psig (483-1793 ka). See Setup and Adjustments. V146 valves are available in 3/4-in. and 1-in. sizes. Use V146 valves with standard non-corrosive refrigerants. Internal valve parts that are exposed to water are constructed of monel (nickel-copper alloy) and brass to resist corrosion. Finding the Size Required Each application is unique and requires specific engineering data to properly size and design a system to fulfill the appropriate requirements. Typically, a valve is replaced with another valve of the same size in a properly sized and engineered system. Contact Johnson Controls/enn Refrigeration Application Engineering at 1-800-275-5676 to obtain specific engineering data. To make a rough field estimate of the size of valve for an application, find the valve size by locating a point on a flow chart (see Figure 4) that satisfies these requirements: Maximum Water Flow Take the Maximum water flow (Flow) required by the condenser from information provided by the manufacturer. If the manufacturer s information is unavailable, use the following information to make a rough approximation of maximum water flow in gallons per minute (gpm): System Capacity (Tons of Refrigeration) Outlet Water Temperature (Temp. Outlet ) Inlet Water Temperature (Temp. Inlet ) If the outlet temperature is unknown, assume it to be 10F (5.5C ) above the inlet temperature. Refrigerant Head ressure Rise Approximate the Refrigerant Head ressure Rise Above Opening oint ( H ) with the following information: Refrigerant Condensing ressure ( COND ) is the manufacturer s recommended condensing pressure. Closing ressure ( VC ) is equal to the refrigerant pressure at the highest ambient temperature the refrigeration equipment experiences in the Off cycle. Use a ressure-temperature Chart to find this pressure. Maximum Available Water ressure Drop The maximum available water pressure drop through the valve is the water pressure actually available to force water through the valve. Minimum Inlet ressure is the water pressure from city water mains, pumps, or other sources. ressure Drop Through Condenser is the difference in water pressure between the condenser inlet and the condenser outlet. Obtain this information from the condenser manufacturer. ressure Drop Through All Associated iping is an estimated or calculated value. Loss 2 2 Condenser = - COND 1 2 Cooling Tower 1 V146 ump Loss 1 Loss 1 Loss 2 IN = + +... LOSS Figure 2: Maximum Available Water ressure Drop 2 V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin

Equations Maximum Water Flow Flow = Tons of Refrigeration x 30 (Temp. Outlet - Temp. Inlet ) Refrigerant Head ressure Rise H = -( + 7 psi ) COND VC Maximum Available Water ressure Drop AVAIL IN = - - COND LOSS Metric Conversions Use these equations to convert between U.S. and S.I. units. 1 dm 3 /s = 3.6 m 3 /h = 15.8 U.S. gal. /min. = 13.2 U.K. gal. /min. 1 bar = 100 ka = 0.1 Ma 1.02 kp/cm 2 = 1.02 atm at 14.5 psig Sizing Example Maximum Water Flow According to the manufacturer s information, the maximum required water flow for the system is 35 gpm. Maximum water flow is 35 gpm. Refrigerant Head ressure Rise The system uses refrigerant R-22. Maximum ambient temperature during the Off cycle is estimated at 95 F, which gives a refrigerant pressure of 180 psig. ( VC = 180) The manufacturer s recommended condensing temperature is 110 F, so the Condensing ressure is 226 psig. ( COND = 226) H = COND ( VC + 7 psig) = 226 - (180 + 7) = 39 psi Note: Refrigerant Head ressure Rise is 39 psi. Maximum Available Water ressure Drop City water pressure (minimum inlet pressure) is 40 psig. ( IN = 40 psig) The manufacturer s table gives a pressure drop through the condenser and the accompanying piping and valves at 15 psi. ( COND = 15 psi) Water pressure drop through the installed piping is approximately 5 psi. ( LOSS = 5 psi) AVAIL = IN - COND - LOSS = 40-15 - 5 = 20 psi Maximum Available Water ressure Drop is 20 psi. Using a flow of 35 gpm, a head pressure rise of 39 psi, and a pressure drop across the valve of 20 psi, the 1 in. valve meets these criteria. See the 1 in. V146 valve flow chart. V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin 3

V146 Flowcharts Note: The maximum differential water pressure across a valve is 60 psig (414 ka). Flow (gpm) 45 40 35 30 25 20 15 10 5 ressure Drop Through (psi) 0 10 15 20 25 30 35 40 45 50 55 60 Refrigerant Head ressure Rise (psi) Flow (gpm) 80 75 70 65 60 55 50 45 40 35 30 Figure 3: 3/4 in. V146 25 20 15 10 5 0 10 15 20 25 30 35 40 45 50 55 60 Refrigerant Head ressure Rise (psi) 60 50 40 30 20 10 ressure Drop Through (psi) 60 50 40 30 20 10 Operation The V146 valve controls refrigerant head pressure by sensing the condensing pressure and adjusting water flow to meet cooling demand as the condenser requirements change. Installation IMORTANT: If these valves are installed on equipment that contains hazardous or regulated materials, such as refrigerants or lubricants, observe all regulations governing the handling and containment of those materials. IMORTANT: Apply a non-hardening, pliable sealant (Loctite 567 or equivalent) to the face of the copper tailpiece to compensate for slight piping misalignments and surface imperfections on union ends. IMORTANT: After installing the valve, evacuate bellows and pressure connection lines, in accordance with EA and other regulations, to remove air, moisture and other contaminants. Figure 4: 1 in. V146 4 V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin

Dimensions See Table 1, Figure 5 and Figure 6 for dimensions of V146 valves. A B A B D C D C ort 1 ort 2 E ort 1 ort 2 E ressure connection and capillary as specified Figure 6: V146 Dimensions for 3/4 in. s ressure connection and capillary as specified Figure 5: V146 Dimensions for 1 in. s Table 1: Dimensions, inches (millimeters) roduct Code Nominal Size A B C D E V146EK-1C 3/4 in. 3-3/8 (86) 2-3/16 (55) 7-3/16 (183) 4-3/16 (106) 3 (76) V146AL-1C 1 in. 4-3/4 (121) 2-15/16 (75) 10 (254) 5-15/16 (151) 4-1/16 (103) Table 2: Dimensions, Shipping Weight roduct Code Nominal Size Shipping Weight V146EK-1C 3/4 in. 4.3 lb (2.0 kg) V146AL-1C 1 in. 9.3 lb (4.0 kg) Range Spring Spring Guide Top Retainer Range Adjustment Screw Insert screwdrivers underneath the valve spring guide. Manually Flushing the Manually flush the valve and fluid piping before and after installing, repairing, or replacing a valve to remove filings, chips, or other foreign matter. Insert screwdrivers under both sides of the valve spring guide and lift upward to flush the valve. (See Figure 7 and Figure 8.) Manual flushing does not affect valve adjustment. Figure 7: Manual Flushing for 1 in. s V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin 5

Range Spring Spring Guide Top Retainer Range Adjustment Screw Insert screwdrivers underneath the valve spring guide. Figure 8: Manual Flushing for 3/4 in. s Mounting Install the valve vertically with the range adjustment screw on the top and the bellows and pressure connection line on the bottom to allow drainage of oil and refrigerant away from valve bellows. Do not mount the valve in any position other than vertical unless specified by the manufacturer of the equipment on which the valve is installed. Follow the manufacturer's installation instructions. Location Considerations Install the valve on the inlet side of the condenser. If it is necessary to keep the condenser flooded with water, install the valve on the outlet side of the condenser. If the system is located in an area with high ambient temperatures, refrigerant head pressures may remain high enough during off cycles to prevent the valve from closing completely. In such instances, raise the opening point of the valve just enough to cause the valve to stop flow to the condenser during compressor standby periods. ressure Connections! WARNING: Risk of ersonal Injury. Contents of liquid lines could be under pressure. Avoid possible personal injury by shutting off the liquid supply and relieving the pressure before servicing the valve. Connect the refrigerant-side flare connector to the appropriate high-side pressure tap point. If additional capillary tubing is necessary, use 1/4-in. copper tubing. Follow the guidelines below when making pressure connections: Use ressure Tap oints Located on the Top Side of the Refrigerant Lines. This reduces the possibility of oil, liquids, or sediment accumulating in the pressure connection line or valve bellows, which could cause valve malfunction. Avoid Sharp Bends in the Capillary Tubes. Sharp bends can weaken or kink capillary tubes, which may result in refrigerant leaks or restrictions. Allow for Slack in the Capillary Tubes to Dampen Vibration. Mechanical vibration can weaken or damage the capillary tubes. Avoid Contact Between the Capillary Tubing and Sharp or Abrasive Objects. Vibration or rubbing of sharp or abrasive objects in contact with capillary tubes can cause leaks. Coil and Secure Excess Capillary Tubing Away from Contact with Sharp or Abrasive Objects or Surfaces Carefully loop any excess capillary tube into smooth, circular coils (minimum 2 in. [5 cm] diameter). Securely fasten the coiled capillary tube. Do Not Overtighten Flare Nuts on ressure Connection Line Fittings. Overtightening flare connections may damage the threads on the flare nuts or flare connectors and result in refrigerant leaks. Do not exceed 9 lb ft (12 N m) of torque when tightening brass flare connections. Avoid Severe ressure ulsation at ressure Tap oints. Install pressure connection lines to pressure tap points away from the compressor discharge, to minimize the effects of pressure pulsation from reciprocating compressors. 6 V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin

Table 3: Refrigerant ressure Specifications roduct Code Nominal Size Maximum Refrigerant ressure at Bellows V146EK-1C 3/4 in. 370 psig (2551 ka) V146AL-1C 1 in. 320 psig (2206 ka) Opening oint Adjustment Range Factory-Set Opening oint 70-260 psig (483-1793 ka) 165 psig (1138 ka) Setup and Adjustments The V146 valves are factory adjusted for the settings shown in Table 3. The opening point pressure is the refrigerant pressure (at the valve s bellows) necessary to just lift the valve disc off the valve seat and allow water to flow through the valve body. Turning the range adjustment screw changes the opening point pressure. Use a standard service valve wrench or screwdriver to adjust the opening point pressure. Turn the range adjustment screw counterclockwise to raise the opening point pressure. Turn the range adjustment screw clockwise to lower the opening point pressure. Repair and Replacement Replacement of the sensing element, internal parts, and the rubber diaphragm can be made. For a replacement valve or replacement parts kit, contact the nearest Johnson Controls/ENN distributor. For replacement kit part numbers, refer to Table 4. For replacement kit instructions and details, refer to the following bulletins: V146 Series s Repair and Replacement Kits Installation Instructions (art No. 24-7664-2071) V146 and V148 Series s Sensing Element Replacement Kits Installation Instructions (art No. 24-7664-2101) Use a refrigerant pressure gauge to adjust the opening point pressure. Operate the system at normal load conditions and adjust the valve s opening point to the desired pressure. See Table 3 for refrigerant pressure specifications. Table 4: Repair and Replacement Kits roduct Code Nominal Size Seat Repair Kit roduct Code Diaphragm Replacement Kit roduct Code Sensing Element Replacement Kit roduct Code V146EK-1C 3/4 in. STT146075-600R DM14A075-600R SE14A075-603R V146AL-1C 1 in. STT146100-600R DM14A100-600R SE14A100-603R V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin 7

Ordering Information Table 5: Ordering Information roduct Code Nominal Size Inlet and Outlet orts ressure Connection Style* Shipping Weight V146EK-1C 3/4 in. Union (Sweat) 46 4.3 lb (2.0 kg) V146AL-1C 1 in. 9.3 lb (4.0 kg) * See Figure 9. Style 46 Technical Specifications roduct Refrigerant ressure Range Water Supply Material Copper Capillary with 1/4-in. SAE Female Flare Connector (Includes Stem Depressor.) Figure 9: ressure Connection Styles V146 Series 2-Way ressure-actuated Water-Regulating s See Table 3. 350 psig (2413 ka) Maximum, 40 F (4 C) Minimum, 170 F (77 C) Maximum Body Disc Stud, Stem Disc Cup, Seat Disc Sensing Element Diaphragm 3/4 in. - Cast Brass 1 in. - Cast Iron with Corrosion-Resistant Finish Brass Monel (Nickel-Copper Alloy) Buna-N Brass and hosphor Bronze Bellow in Brass Cup Nylon-Reinforced Buna-N Dimensions (H x W x D) See Figure 5, Figure 6 and Table 1. Shipping Weight See Table 2. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult Johnson Controls/ENN Refrigeration Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group 507 E. Michigan Street.O. Box 423 Milwaukee, WI 53201 ublished in U.S.A. www.johnsoncontrols.com 8 V146 Series 2-Way ressure-actuated Water-Regulating s roduct/technical Bulletin