COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Similar documents
Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

S Surge Arresters

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

Effective May 2017 Supersedes August 2005 (S )

2000 lb manual winch

USER MANUAL. DM65 Manual Flush/Tilt Combo Mount

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

Remington 700. Disclaimer Limited Warranty Satisfaction Guarantee Installation Instructions

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

310 SERIES TILT-TO-LOAD ROTATOR. The Specialist In Drum Handling Equipment

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

Repair instructions. Pivot bushing replacement. XL-AS10001RM-en-DE Rev B

This document to be used with Hurley traditional Davits

COMPACT METAL bender 99826

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

Sunset Swings By Health in Motion, LLC

Owner s Manual Tourmaster Storage Cart

Caliber Sled Wheels Assembly Instructions for PN and 13579

Inspection Recommendations

INSTALLATION & OPERATION MANUAL. Dual Duct VAV Terminals. Redefine your comfort zone.

Owner s Manual High Density Sports Storage Partial End Closure Accessory 32-inch Partial End Closure 48-inch Partial End Closure

Index Table. Model 794. Installation, Operating and Maintenance Instructions

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Mini Pod Press. #78H-M2 Mini Pod Press Manual-R1

Triple Tine Mechanical Grapple

Wallmax Professional Aneroid Sphygmomanometer Model 222 User Manual

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

S Loadbreak Apparatus Connectors WARNING: WARNING:

6 digital caliper with case

INSTALLATION INSTRUCTIONS

Hydraulic Punch Drivers

DLx1200, DLx1500, DLx1900, DLx2300 PULLING WINCHES. U.S. Patent Canadian Patent Model #DLx1200

OPERATOR S MANUAL. Striper. Models: SZL/SFZ/SCZ48/52 STRIPER STC/SCZ/STT STRIPER Scag Power Equipment Division of Metalcraft of Mayville, Inc.

Cover EX Installation Instructions

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

MANUAL SEALLESS STEEL STRAPPING TOOL MODEL A

3M Liqui-Cel EXF-10x28 Series Membrane Contactor

Norrsken Family Booklet

3M Liqui-Cel EXF-10x28 Series Membrane Contactor with ANSI or JIS Connections with Integrated End Caps

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

SERIES 2 RAMP OWNER S MANUAL TOOLS REQUIRED: BEFORE YOU BEGIN... Read and understand these instructions before beginning a ramp setup.

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

Copyright Trek Bicycle Corporation 2005 All rights reserved

Steel Spring Driven Reel Instruction Manual

C - SERIES. Height Adjustable Portable Goal Supports. Installation & Owner s Instructions C1000 C2000. Made in the USA

Traditional Basketball Set. Assembly & Installation Instructions

INSTALLATION INSTRUCTIONS

EXTERNALLY ROUTED DROPPER POST owner S MANUAL

Installation Instructions JATCO Environmental Protection Tank Model J-5000CX

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

OPERATOR S MANUAL. Striper. Models: SZL, SFZ, SFZP, SPZ, SCZ48/52 STRIPER STC, STCII, SCZ61/72, STT, STTII STRIPER

TL-12 FLUSH TANK. Manual Ref. # MN-??? Polyurethane Machinery Corp. REVISION 1.0

OWNER'S MANUAL. Copyright 2003 GAMMA - All Rights Reserved

Cocoa Patio Pond with Lit Spillway

MAVERICK FOOSBALL TABLE

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

Tru Trak Sulky Proline Mid Size Mower Attachment

3M Liqui-Cel EXF-4x13 and 4x28 Series Membrane Contactors

602 STRINGING MACHINE OWNER'S MANUAL

600 / 600FC OWNER'S MANUAL

ATD /8 x 50 Retractable Air Hose Reel Owner s Manual

Front derailleur. Dealer's Manual SORA FD-R3000 FD-R3030 CLARIS FD-R2000 FD-R2030. ROAD MTB Trekking. City Touring/ Comfort Bike DM-RBFD001-01

Transcription:

Reclosers MN280047EN Effective May 2016 Supersedes S280-80-16 December 2003 Operation Counter Replacement Instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Additional information...1 Quality standards................................................................................1 COUNTER INSTALLATION... 1 COUNTER ADJUSTMENT.... 1 Confirm counting...1 Adjustment...1 ii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iii

Operation Counter Product information Introduction Current production models of Eaton s Cooper Power series distribution switchgear incorporate a modern four-digit operations counter. This counter also can be employed as a replacement for counters on older switchgear units. In most instances, this improved counter can be installed without modifying the switchgear. Adaptation instructions, when required, are listed in Table 1. Hazardous voltage. De-energize the switchgear before installing this kit. Follow all locally approved safety practices and procedures when working around high voltage lines and equipment. Failure to comply can result in contact with high voltage, which will cause death or severe personal injury. T232.3 CAUTION Follow all locally approved safety practices when lifting and mounting the equipment. Use the tapped lifting provisions provided. Lift the load smoothly and do not allow the load to shift. Improper lifting can result in equipment damage. G126.0 Refer to the appropriate maintenance manual for the stepby-step procedures to remove the recloser from service. The entire installation process should be conducted in a clean environment, such as a repair shop. 1. Bypass, trip, and de-energize the recloser. 2. Carefully transport the unit to a suitable service facility. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before connecting or operating this equipment. Additional information These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact Eaton s Cooper Power series product representative. Quality standards ISO 9001 Certified Quality Management System Counter installation 1. Locate the counter inside the sleet hood. 2. Remove the existing counter by using a screwdriver to remove the two screws that hold the counter in place. 3. Secure the replacement counter inside the sleet hood, using the two self-tapping screws provided. 4. Check the counter operation after installing the replacement counter. Refer to the section Counter Adjustment below to determine if any linkage adjustment is necessary. Counter adjustment The two most important considerations are: The counter must register each opening operation. The counter operating arm must not reach its stop point within the travel range of the driving linkage. This is particularly critical on recloser Types E, H, L, PV4H, V4H, V6H, VXE, 3H, 4E, 4H, and 6H. Confirm counting Close and trip the switchgear manually and observe that the counter has registered the operation. If the trip operation did not register, confirm that the driving lever (the lever that pushes or pulls the counter arm) is in place and that its movement is causing rotation of the counter arm. Adjustment When the switchgear is manually or electrically closed, a driving lever, linkage, or spring causes the counter arm to pivot, preparing the ratchet to count. Near the end of this arming stroke, a click can be heard in the counter. As the arm returns to its starting point, the digit wheel(s) move(s) to register the count. Near the end of the return stroke, another click can be heard, which indicates completion of the count. If counts do not register, it may be necessary to make a small adjustment to the driving lever or the counter arm. The driving lever must cause (or allow) the counter arm to travel completely through the first click to set the ratchet. Likewise, on the return stroke, the counter arm must travel through the second click to fully pivot the number wheel. On E, H, L, PV4H, V4H, V6H, VXE, 3H, 4E, 4H, and 6H reclosers, at the extremes of its rotation, the counter arm hits a stop and will travel no further. It is essential that the recloser contacts close before the counter arm hits the stop. Perform these steps to verify correct operation: 1. Pull down on the recloser operating handle to open the recloser contacts. The handle is yellow in most cases. 1

Operation Counter 2. Slowly push the operating handle upward and listen for these two sounds: First, the ratchet-set click in the counter. Second, a somewhat louder click of the recloser contacts closing. 3. Adjustment is correct if the counter click occurs before the click of the contacts closing, and the counter arm is not against its stop. 4. If adjustment is needed, do the following: A. Make note of the installed position of the counter, and remove it from the sleet hood. B. Loosen the bolt that clamps the counter arm to the counter shaft, and adjust the counter arm. If the counter stop is encountered too soon, rotate the arm upward (as if into the sleet hood) a small amount. If the counter is failing to register, rotate the arm downward (as if into the sleet hood) a small amount. C. Retighten the bolt and reinstall the counter. D. Check operation of the counter by slowly raising the yellow operating handle to close the recloser contacts. Before the contacts close, the ratchet should drop into the next position indexing the counter. Hold the operating handle at the point where the recloser contacts just close. The counter arm should be able to travel another 3/32 in. (± 1/32 in.) before it reaches the counter stop. 64 mm (2 1 / 2 ") Outer Edge of Sleet Hood 37 mm (1 15 / 32 ") 17 mm ( 11 /16") 11 mm (1 7 / 16 ") Top 4 mm (0.156") Dia. Holes (2) Bottom of Sleet Hood Figure 1. Templates for KA708E and KA708L kits IMPORTANT If the counter lever hits the counter stop before the recloser contacts close, the mechanism may become blocked and the recloser could fail to close. E. Repeat steps A - D as needed until the counter is adjusted correctly. 2

Operation Counter Table 1. Replacement counters and procedures Switchgear Type Serial No. Range Counter Cat. No. Installation Procedure CI, CS, KF, KFE All KA28CO6S Direct replacement. CM CM2340 and above KA28CO10S Direct replacement. CVE, CXE, CZE All KA28CO7S Direct replacement. D, DV All KA28CO5S Direct replacement. E E16570 and below KA708E On reclosers equipped with a shunt mechanism, mount the new counter to the diagonal bracket, beneath the sleet hood, to which the old counter is attached. On others, remove the bracket and attach the counter at the bracket mounting holes. If necessary, drill two new 0.156-in. diameter holes using the template; refer to Figure 1. Place the template as indicated on the outside surface of the sleet hood, on the end opposite the nameplates. E E16571 and above KA28CO3S Direct replacement. E E52007 and above KA28CO1S Direct replacement. F, ME, MLE, MVE All KA28CO8S Direct replacement. GV, GW, GWC, VCR, VLR, VR, VRV All KA28CO3S Direct replacement. H H100973 and below KA704H Replace the old counter with the new counter and bracket assembly, attaching the bracket with the 3/8-in. long self-tapping screw provided. H H100974 to H175859 KA701H Replace the counter directly, and install the new sleet hood cover having dished portion, as furnished in the counter kit. H H175860 and above KA28CO1S Direct replacement. 3H 3H585 and below KP44H Direct replacement. 3H 3H586 to 3H10059 KA701H3 Install replacement counter following instructions in Service Information S280-10-16, furnished in the counter kit. 3H 3H10060 and above KA28CO4S Direct replacement. 4H 4H13354 and below KA701H Replace the counter directly, and install the new sleet hood cover having dished portion, as furnished in the counter kit. 4H 4H13355 and above KA28CO1S Direct replacement. 6H 6H2651 and below KA701H3 Install replacement counter following instructions in Service Information S280-10-16, furnished in the counter kit. 6H 6H2652 and above KA28CO4S Direct replacement. V4H, 4E All KA28CO1S Direct replacement. V6H All KA28CO4S Direct replacement. L L37202 and below KA708L Remove diagonal bracket to which old counter was attached, and mount new counter at the bracket mounting holes. If necessary, drill two new 0.156-in. holes using the template, Figure 1. Place template as indicated on the outside surface of the sleet hood, on the end opposite the nameplates. L L37203 and above KA28CO14S Direct replacement. LV All KA28147VWS Direct replacement. PV4H All KA28CO11S Direct replacement. PWE, PWH, PWVE, PWVH All KA28CO9S R R3732 and below KA865R R R3733 and above KA28CO2S Direct replacement. RV, RX, VW, VWV, W, WV All KA28CO2S Direct replacement. SW, SWE, SWVE, VWS All KA146VWS Direct replacement. TSC All KA146TSC Direct replacement. VSMT, VSO All KA28CO9S Direct replacement. VXE All KA28CO14S Direct replacement. Adjust the counter arm parallel to the counter mounting surface. Aim the counter arm away from the numerals. Remove the sleet hood cover to exchange counters. When replacing the sleet hood cover, install the L-shaped spacer (included in the counter kit) between the sleet hood and cover. Fasten with the 5/8-in. long screws provided. 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN280047EN May 2016 KA20480276 REV03 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.