COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

Similar documents
COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

DT400/436 Tee Connector Installation Instructions

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

S Surge Arresters

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Norrsken Family Booklet

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Effective May 2017 Supersedes August 2005 (S )

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

S Loadbreak Apparatus Connectors WARNING: WARNING:

Inspection Recommendations

This document to be used with Hurley traditional Davits

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

OPERATOR'S MANUAL GRASS CATCHER GC-4D

FLANGED TWO-PIECE BALL VALVES

Accu-Tab Systems 1000 Series by Axiall Corporation

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

OPERATOR S MANUAL. Fabric Grass Catcher PART NO PRINTED 1/2011 PRINTED IN USA

Owner s Manual High Density Sports Storage Partial End Closure Accessory 32-inch Partial End Closure 48-inch Partial End Closure

Permanent Roof Anchors

Personal Fall Arrest System. User s. Manual. Part Number January 2014 (Replaces July 2013)

Mini Pod Press. #78H-M2 Mini Pod Press Manual-R1

2000 lb manual winch

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

OPERATOR S MANUAL Expand-it Brushcutter Attachment UT15702A

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

RGC-IR Remote Gas Calibrator for IR400

COMPACT METAL bender 99826

FLANGED TWO-PIECE BALL VALVES

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

Accu-Tab Systems 2000 P Series by Axiall Corporation

User s Guide Temperature Sensor Converter TSC-599

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

Instruction Manual. PE Pipe Squeeze-off Tool Model TR650

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools.

4-in-1 Professional Inflator Kit

OPERATOR S MANUAL SPREADER. CSS, VNQ [For Combine Harvester AW82V] Original instructions

BS Series Basket Strainer

GAS FUEL VALVE FORM AGV5 OM 8-03

MAVERICK FOOSBALL TABLE

OPERATOR'S MANUAL. MODEL GC-F4 Fabric Grass Catcher P/N 9055 GRASS CATCHER GC-F4. PART Rev.2 SC301G

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

INSTALLATION INSTRUCTIONS A-Arm Guards, Rear Part Number: Application: Kawasaki Brute Force 750 4x4i

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

MODEL CALIBRATION GAS DELIVERY SYSTEM

Yoke Block Instruction Manual

VL 2K LIFT D-L WINCH INSTRUCTIONS (Applies to P/Ns , , , , , )

ATD /8 x 50 Retractable Air Hose Reel Owner s Manual

Triple Tine Mechanical Grapple

Pressure Relief Valve Instruction Manual

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

60 Drum Style Spike Aerator

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: HD26248

Single-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

Cocoa Patio Pond with Lit Spillway

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

General Information. NTA607HD Lift Assist Adjustments. Tools Required. Work Location. Notations and Conventions U B F D R B F L

Transcription:

Surge Arresters MN235006EN Effective August 2016 Supersedes June 2014 (S235-35-1) COOPER POWER SERIES UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... ii SAFETY FOR LIFE... iv SAFETY INFORMATION... iv Safety instructions...iv PRODUCT INFORMATION.... 1 Introduction...1 Acceptance and initial inspection...1 Handling and storage...1 Quality standards................................................................................1 INSTALLATION PROCEDURE.... 2 Installation instructions...2 Field testing...3 Removing an arrester from a circuit...3 ACCESSORIES.... 4 Wildlife protection...4 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.2 iv

CAUTION This arrester should be installed only by personnel familiar with good safety practice and the handling of high-voltage electrical equipment. These instructions are not intended to supersede or replace existing safety and operating procedures. Where applicable, the requirements of national and/or local codes and insurance underwriters must be fulfilled. Always handle surge arrester packed or unpacked very carefully. Do not drop, jar, or handle an arrester roughly. Dropping, jarring, and/or rough handling may damage the arrester internally and/or externally, making it incapable of adequately protecting the apparatus or circuit on which it is to be installed or it may shorten the service life of the arrester significantly. WARNING Never install a damaged arrester. A damaged arrester may misoperate violently, causing severe personal injury and property damage. CAUTION Do not install an arrester if the type, voltage, and MCOV data are not exactly the same on the nameplate and the carton label because the arrester may be incapable of adequately protecting the apparatus or circuit on which it is to be installed. Make all electrical connections ground and line so that no mechanical stress is applied to the surge arrester. Mechanical stress may damage the arrester in such a manner that its service life is shortened significantly. IMPORTANT This Cooper Power series product as designed and packaged by Eaton has been classified by the US DOT as not regulated as an explosive. Product information Introduction Eaton s Cooper Power series UltraSIL polymer-housed distribution-class MOV arresters provide overvoltage protection to overhead and underground distribution systems. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, please contact your Eaton representative. Acceptance and initial inspection Each arrester is completely assembled, inspected and tested at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt of an arrester, inspect the connector thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. Handling and storage If the arrester is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the arrester so as to minimize the possibility of physical damage. Quality standards ISO 9001 Certified Quality Management System 1

GROUND TERMINAL STUD LINE TERMINAL STUD Figure 1. UltraSIL housed distribution class MOV arrester LINE TERMINAL 2. Select a mounting location as close as possible to the apparatus that the arrester is to protect. Make the line lead and ground lead as short as possible. 3. De-energize the electrical system. 4. Connect the ground lead to the arrester ground terminal stud. Torque the hex nut to 20 ft-lbs. maximum. NNote: Make the arrester ground connection as short and direct as possible to a solid, effective, permanent, low-resistance ground. If the arrester has a ground lead disconnector, the ground lead must be flexible enough to allow the disconnector to operate properly. 5. Connect the line lead to the arrester line terminal stud. Torque the hex nut to 20 ft-lbs. maximum. If using the eyebolt connector, torque the clamping nut to maximum 20 ft-lbs. NNote: The standard arrester terminals accommodate conductor sizes from AWG No. 6 solid through AWG 2/0 stranded. 6. Re-energize the electrical system. HEX NUT* LOCK WASHER ARRESTER HANGER FLAT WASHER GROUND STRAP NEMA HANGER BRACKET Figure 2. Transformer mounted fully assembled (bulk packed) arrester BOLT Installation procedure Installation instructions NNote: In the event that safety and operating procedures do not exist for installing this arrester to, or removing it from a circuit, we suggest the following: 1. Install all mounting hardware on the arrester. Torque the hanger bracket hex nut between 20 and 25 ft-lbs. See Figure 3 for NEMA brackets and Figure 4 for transformer brackets. Figure 3. Installation of arrester to NEMA hanger bracket *Torque requirement of hex nut is 20-25 ft-lbs. 2

ARRESTER HANGER HEX NUT* LOCK WASHER FLAT WASHER Field testing All UltraSIL housed arresters have passed a complete series of production tests prior to shipment; therefore, no field testing is necessary. CAUTION Before performing any test on an arrester, contact your Eaton s Cooper Power series product sales engineer. Some test procedures may damage the arrester externally and/or internally, making it incapable of protecting the apparatus or the circuit on which it is installed, or shortening its service life significantly. BOLT TRANSFORMER MOUNTING BRACKET Figure 4. Installation of arrester to transformer mounting bracket *Torque requirement of hex nut is 20-25 ft-lbs. WARNING Always consider an arrester to be energized until both the line and the ground leads have been disconnected from the circuit. Removing an arrester from a circuit 1. De-energize the electrical system. 2. Disconnect the arrester line lead(s) from the circuit. NNote: A small amount of static charge may be retained in an arrester when it is removed from an energized circuit. 3. Discharge the arrester by attaching the line terminal to a temporary ground. 4. Mark the temporary ground to make sure it is removed before the arrester is reinstalled. 5. Disconnect the arrester ground lead(s) from the circuit. 6. Re-energize the electrical system. 3

Accessories Wildlife protection 0.80" VALVE OPENING VALVE OPENING 2.22" Push down firmly on top of stud to install 1.03" 152 2.50" SIDE VIEW VALVE OPENING TOP VIEW Figure 5. Universal wildlife protector (catalog number AV346X1C); all dimensions in inches The universal wildlife protector has two self-adjusting valve style openings which vary from 0 to 0.75" in diameter, thus allowing for a large variety of conductor/insulation sizes while providing optimum wildlife protection. Figure 6. Line terminal wildlife guard (catalog number AV698X1C); all dimensions in inches Push protector down firmly onto top stud to install 4

Push onto stud firmly to install Figure 7. Ground terminal wildlife guard (catalog number AV731X1C); all dimensions in inches) NNote: Left shows attachment of ground terminal wildlife guard; right images shows ground terminal wildlife guard completely installed. 5

T his page is intentionally left blank. 6

T his page is intentionally left blank. 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN235006EN August 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.