Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Similar documents
Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

Linear Compressor Discharge Manifold Design For High Thermal Efficiency

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Application of Computational Fluid Dynamics to Compressor Efficiency Improvement

Scroll Compressor Operating Envelope Considerations

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors

Development of Large Capacity CO2 Scroll Compressor

Test on a Twin-Screw Compressor

Efficiency Improvement of Rotary Compressor by Improving the Discharge path through Simulation

LGWP & HC Refrigerants Solubility Tests Performed in Running Scroll Compressor

CFD Analysis and Experiment Study of the Rotary Two-Stage Inverter Compressor with Vapor Injection

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Investigation of Suction Process of Scroll Compressors

Hermetic Compressor Manifold Analysis With the Use of the Finite Element Method

Performance and Operating Characteristics of a Novel Rotating Spool Compressor

Performance Analysis of Centrifugal Compressor under Multiple Working Conditions Based on Time-weighted Average

Research of Variable Volume and Gas Injection DC Inverter Air Conditioning Compressor

Predicting the Suction Gas Superheating in Reciprocating Compressors

Improvement of the Volumetric and Isentropic Efficiency Due to Modifications of the Suction Chamber

Scroll Compressor Performance With Oil Injection/Separation

Ball Beating Lubrication in Refrigetation Compressors

Comparative Analysis of Two Types of Positive Displacement Compressors for Air Conditioning Applications

Operation of Compressors Through Use of Load Stands

Development of a New Mechanism Compressor Named "Helical

Characterization and Performance Testing of Two- Stage Reciprocating Compressors using a Hot-Gas Load Stand with Carbon Dioxide

Using PV Diagram Synchronized With the Valve Functioning to Increase the Efficiency on the Reciprocating Hermetic Compressors

Numerical Simulation for the Internal Flow Analysis of the Linear Compressor with Improved Muffler

Development of Scroll Compressors for R410A

ENGINEERING FLUID MECHANICS

Domain Decomposition Method for 3-Dimensional Simulation of the Piston Cylinder Section of a Hermetic Reciprocating Compressor

A Twin Screw Combined Compressor And Expander For CO2 Refrigeration Systems

Tutorial. BOSfluids. Relief valve

Updated Performance and Operating Characteristics of a Novel Rotating Spool Compressor

Impact Fatigue on Suction Valve Reed: New Experimental Approach

Noise Characteristics Of A Check Valve Installed In R22 And R410A Scroll Compressors

Incorporating 3D Suction or Discharge Plenum Geometry into a 1D Compressor Simulation Program to Calculate Compressor Pulsations

Modeling and Testing of an Automobile AC Scroll Compressor, Part II: Model Validation

Development of a High Pressure, Oil Free, Rolling Piston Compressor

Capacity Modulation of Linear Compressor for Household Refrigerator

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

Tip Seal Behavior in Scroll Compressors

Design Optimization for the Discharge System of the Rotary Compressor Using Alternative Refrigerant R410a

Heat Transfer Research on a Special Cryogenic Heat Exchanger-a Neutron Moderator Cell (NMC)

Evaluation of a Prototype Rotating Spool Compressor in Liquid Flooded Operation

Correlation Between the Fluid Structure Interaction Method and Experimental Analysis of Bending Stress of a Variable Capacity Compressor Suction Valve

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Performance Analysis of a Twin Rotary Compressor

Linear Compressor Suction Valve Optimization

Real Gas Performance Analysis of a Scroll or Rotary Compressor Using Exergy Techniques

Variable Volume-Ratio and Capacity Control in Twin-Screw Compressors

University of Cincinnati

CFD Simulation of the Flow Through Reciprocating Compressor Self-Acting Valves

CFD Flow Analysis of a Refrigerant inside Adiabatic Capillary Tube

Vibration-Free Joule-Thomson Cryocoolers for Distributed Microcooling

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Digital Computer Simulation of a Reciprocating Compressor-A Simplified Analysis

Small Variable Speed Hermetic Reciprocating Compressors for Domestic Refrigerators

CYCLE ANALYSIS OF LINEAR COMPRESSORS USING THREE- DIMENSIONAL CFD

Axial and Radial Force Control for CO2 Scroll Expander

University of Cincinnati

Centrifugal Compressor Performance Deviations with Various Refrigerants, Impeller Sizes and Shaft Speeds

ASSIGNMENT 2 CHE 3473

Simulator For Performance Prediction Of Reciprocating Compressor Considering Various Losses

Pressure Indication of Twin Screw Compressor

ASSIGNMENT 2 CHE 3473

SELECTION CRITERIA FOR SAFETY VALVE

Effect of Coiled Capillary Tube Pitch on Vapour Compression Refrigeration System Performance

Chapter 4, Problem 30.

HW-1: Due by 5:00 pm EDT on Wednesday 13 June 2018 to GradeScope.

POLISH MARITIME RESEARCH 4(80) 2013 Vol 20; pp /pomr

Experimental Verification of Integrated Pressure Suppression Systems in Fusion Reactors at In-Vessel Loss-of -Coolant Events

Self-Adjusting Back Pressure Mechanism for Scroll Compressors

Valve Losses in Reciprocating Compressors

Soft-optimization test of R-410A alternative refrigerant R-32 in a split condensing unit - Phase II

ME 200 Thermodynamics I Spring 2010 (Last) (First) Thermo Number: CIRCLE YOUR LECTURE BELOW

1.2 Example 1: A simple hydraulic system

Investigation to Improve Efficiency of Transcritical R744 Two-Stage Vapor Compression Systems

Theoretical Study of Design and Operating Parameters on the Reciprocating Compressor Performance

Transient Analyses In Relief Systems

Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

MODELING AND SIMULATION OF VALVE COEFFICIENTS AND CAVITATION CHARACTERISTICS IN A BALL VALVE

Internal Leakage Effects in Sliding Vane, Rotary Compressors

A Numerical Study of the Performance of a Heat Exchanger for a Miniature Joule-Thomson Refrigerator

TESTING AND ANALYZING ON P-V DIAGRAM OF CO 2 ROLLING PISTON EXPANDER

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

Earlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System.

Quiz #1 Thermodynamics Spring, 2018 Closed Book, Open Appendices, Closed Notes, CLOSED CALCULATORS

Enter your parameter set number (1-27)

Impact of Refrigerant Fluid Properties on the Compressor Selection

Using P-T Analysis As A Service Tool

A NEW PROCESS FOR IMPROVED LIQUEFACTION EFFICIENCY

A virtual EXV mass flow sensor for applications with two-phase flow inlet conditions

Analytic and Experimental Techniques for Evaluating Compressor Performance Losses

System Conditions Harmful to Compressors Their Diagnosis and Prevention

Lubrication of Screw Compressor Bearings in the Presence of Refrigerants

GLOSSARY OF TERMS. Adiabatic Compression Compression process when all heat of compression is retained in the gas being compressed.

Modeling of Gas Leakage through Compressor Valves

Seminar 65 Compression Challenges for Low GWP Refrigerants

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Sophie Colmek sophie.colmek@tecumseh.com Laurent Goderneaux Follow this and additional works at: http://docs.lib.purdue.edu/iracc Colmek, Sophie and Goderneaux, Laurent, "Gas Vapor Injection on Refrigerant Cycle Using Piston Technology" (2012). International Refrigeration and Air Conditioning Conference. Paper 1220. http://docs.lib.purdue.edu/iracc/1220 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2228 Page 1 Gas vapor Injection on refrigerant cycle using piston technology Sophie COLMEK 1, Laurent GODERNEAUX 2 1 Tecumseh Europe, Design & Research department, 38090 Vaux Milieu, Isère, France Phone: +33(0)4 74 82 20 71 Fax: +33(0)4 74 82 24 89 Mail: sophie.colmek@tecumseh.com 2 Tecumseh Europe, Laboratory department, 38290 La Verpillière, Isère, France Phone: +33(0)4 74 82 21 81 Fax: +33(0)4 74 82 24 89 Mail: laurent.goderneaux@tecumseh.com ABSTRACT Gas vapor injection on refrigerant cycle is always used with Scroll, Rotary or others compressors technology to improve efficiency of the system at low and high ambient temperatures. Probably this kind of compressor is more adapted than the piston technology owing to their mechanical system. In this paper, we present the challenge of vapor injection realized on piston technology compressor range non for improving the cooling capacity of the system but to maintain the compressor temperature in conformity without damage the capacity. Indeed, the principal action of gas injection is to refresh the mechanical system according to the ambient temperature for improving the capacity of the system. In this case of study, the compressor is enclosure on a room without opening at the ambient, thus the temperature of the compressor exceed 130 C, which is the limit temperature of compressor functioning. To reduce the compressor temperature on this refrigerant cycle a gas injection is done from output of condenser to the input of the compressor thanks to the capillary tubes. Therefore, the quantity of gas injection must be sufficient to reduce the temperature, and not damage the capacity of the system. In addition, the piston technology compressor is more sensitive than the others compressors technologies because the compressor valve behavior could be damaged by the liquid phase of the refrigerant. That why the capillary tubes and the density of gas are defined by simulation and the results have been comforted by test. Thus, thanks to gas injection, we can reduce the temperature of the compressor on the refrigerant system with only a capillary tube. 1. INTRODUCTION Today, the acoustic level of product is more important point for customer. A lots of solutions could be proposed for improve the acoustic level of the product and one of these solutions is to isolate the main noises sources. On the refrigerant application the two main noises sources are: the compressor, which represents approximately 50% of global noise, and the ventilation noise. Thus, to reduce the noise level, we propose to isolate the compressors room into the condensing unit without ambient opening in order to reduce the acoustic leakage. This solution could reduce 4dBA (average) of global noise on the refrigerant application. Therefore, closing the compressor at the ambient reduce the convective exchange and increase the temperature of the compressor upper than 130 C, which is

2228 Page 2 the limit temperature of compressor damage. That why, we are focused on a refrigerant injection technique, not to increase the capacity but to maintain temperature. The first part of the present paper is devoted to describe the simulation model done in order to estimate the compressor behavior with different mass flow injection. The simulation model is done thanks to a one dimension multi physics tool. The injection of the refrigerant is done from the outlet of the condenser to the input of the compressor like a capillary tube with 3% maximum reduction of the cooling capacity of condensing unit. 3 3 4 Condenseur Evaporator 1 2 1 Pressure Liquide phase 4 3 3% 3 1 Two phase 1 1 2 Gas phase Enthalpy Figure 1: Schematic representation of injection system and P-h diagram representation The injection simulation model can be able to define the compressor temperature evolution according to the mass flow injection with the thermal convection exchange on the compressor room temperature. The results obtain by the simulation model, will be confirm by laboratory test result on the second part of the paper. Through this paper we will try to present not a liquid or gas injection technique, but a two phase flow refrigerant injection by using a capillary tube. 2. Simulation model of refrigerant injection The definition of the simulation model of the refrigerant injection requires the knowledge of thermal behavior of compressor on the condensing unit s room with or without opening at the ambient. Thus, the model is composed of two main parts which are: the thermal model of compressor and the condenser, only for extract the flow quantity to inject at the inlet of thermal model of compressor. Ventilation room Connection with ventilation room Injection tube 1st noise source 2nd noise source Compressor room Connection with ambient Figure 2: Condensing Unit used for refrigerant injection On this system, the two openings are composed by the ventilation room and the ambient opening which can create thermal convection into the compressor room and refresh the temperature functioning of compressor. The closure one of this opening could not maintain good thermal exchange, consequently the temperature increase on the compressor room and exceed 130 C into the compressor.

2228 Page 3 Thus the idea is to refresh the hot part of the system by the cold part easily without use a flash tank, an internal heat exchange or other system, but only by a capillary tube defined by the useful flow quantity needed to refresh the compressor. That why, the simulation model is focused on the thermal flow model of the compressor. 2.1 The thermal model of compressor The compressor model is composed of thermal exchange element and a flow part in order to evaluate the temperature of the flow through the compressor according to the ambient exchange condition thanks to the one dimension multi physic tool. Suction part Discharge part Inlet flow condition at the compressor Compression Figure 3: Thermal simulation model of compressor Thanks to the simulation tools, it is easily to define rapidly the temperature at the different internal point on the compressor according to the ambient condition and the several operating point of compressor. All parameters, like contact surface, mass, pressure of flow, the convective and conduction coefficient are defined for each part of the compressor. The thermal parts of the compressor are principally composed by convective and conduction thermal equation (Fourier laws ) like following equations: Convection : Conduction : Φ Φ convection conduction = K. S. T = ( K. S ) e. T ( 1) ( 2) Thus, with only the pressure and temperature values of the flow at the inlet of the compressor model, and the characteristics of the compressor like: Capacity Volumetric efficiency Isentropic efficiency Mechanical efficiency It is possible to know the thermal behavior of compressor according to the ambient temperature and the operating point of the compressor. The quantity of mass flow injection can be defined after to know the difference of temperature increasing between the system with or without opening at the ambient.

2228 Page 4 The simulation of the thermal behavior of compressor is done on the following test condition: Flow boundaries conditions at inlet of the compressor Suction pressure: 2.5Bar Discharge pressure: 23 Bar Operating condition : -25 C/ 50 C Compressor characteristics Capacity: 74 cc Volumetric efficiency: 0.7 Isentropic efficiency : 0.9 Mechanical efficiency: 0.75 Ambient condition Temperature of standard compressor room: 60 C Temperature with compressor room closing: 90 C The simulation result is given by the following plots between the opening and closing configuration of the compressors room into the condensing unit platform for operating condition at -25 C/ 50 C -2% +23 C Plot 1: Mass flow through the compressor Plot 2: Housing temperature of the compressor +10 C +12 C Plot 3: Discharge temperature on the compressor Plot 4: Flow temperature on compressor housing At this operating condition, the closing configurations damage the compressor capacity by decreasing 2% of the mass flow in comparison with the opening configuration. The discharge temperature is upper than 130 C. Therefore the efficiency of the refrigerant cycle decreases according to the compressor mass flow. Thus, it is necessary to

2228 Page 5 inject cold refrigerant for this Low Back Pressure* (LBP) application in order to reduce the temperature at the compressor and increases the mass flow. This reduction, of the mass flow through the compressor could be explain by the superheat of the compressor rooms into the condensing unit, and induce the diminution of the density flow which impact the mass flow. According to this first simulation on the thermal behavior of the compressor, it seems to be necessary to inject lower than 2% of the mass flow from the outlet of condenser to the input at the compressor. 2.2 The refrigerant injection on the thermal model of compressor The injection technique of refrigerant can be classified into two types: liquid refrigerant and vapor refrigerant. In these two types of injection techniques it is necessary to have a flash tank or an internal heat exchange for compressor injection. In our case of study, it is not possible to use these kinds of materials owing to the surface restriction into the compressor room of the condensing unit. In addition, the more benefit type of refrigerant injection to refresh is the liquid injection. However, the piston compressor technology is more sensitive of the slugging phenomenon on the valve. Thus, the idea is to do an injection not by only gas but in two phase flow thanks to a capillary tube. Indeed, if the refrigerant extraction for injection is done at the saturation point on outlet of the condenser thanks a capillary tube it is possible to obtain a two phase flow refrigerant. In addition, a capillary tube does not need more surfaces and could install easily through on the condensing unit system. After, to define the technicality of the injection system adopted, it is possible to modify the thermal model simulation of the compressor in adding only the enthalpy and the ratio of mass flow injection at compressor inlet. Figure 4: Injection model and thermodynamics properties According to the first simulation, on the thermal behavior characterization of the compressor, we notice that the closing room, damage the mass flow through the compressor at 2% in comparison with the opening configuration. Thus, the simulation of the injection model is done on the following tests conditions: Flow boundaries condition at inlet of the compressor ( see thermal model of compressor) Compressor characteristics ( see thermal model of compressor) Ambient condition( see thermal model of compressor) Mass flow injection Enthalpy: 276 kj/kg Mass flow injection n 1: 0.00015 kg/s ( 1% according to the standard), with ambient temperature at 90 C Mass flow injection n 2: 0.0004 kg/s ( 2% according to the standard), with ambient temperature at 90 C The simulation result of refrigerant injection is given by the following plots between the different quantities of mass flow injections according to the closing configuration and -25 C/ 50 C operating condition

2228 Page 6 Plot 5: Mass flow through the compressor Plot 6: Housing temperature of the compressor Plot 7: discharge temperature on the compressor Plot 8: Flow temperature on compressor housing The simulation of two phase flow refrigerant injection has been done according to 1% and 2% of mass flow in order to estimate the thermal behavior of compressor according to the injection quantity define by the thermal simulation of compressor. The result of the simulation bring out that for each percentages of injection, it is possible to reduce the discharge temperature of 3 C. In this case of study, and according to the simulation results, the useful mass flow injection for this LBP application seems to be 2%. Indeed, with 2% of injection, the mass flows through the compressor seem to be alike to the opening configuration, and the temperature of compressor decrease approximately of 10 C. In spite of the sufficient injection of mass flow, the temperature of housing and the flow temperature on the compressor, is not alike to the opening configuration, these differences could be explained by the static temperature condition put at the ambience on the simulation model. Thus, this static ambient temperature leads to reheat the housing temperature and compressor inlet flow. Therefore, the simulation model can not give the reality of the thermal behavior but can estimate keys parameter before the test. Indeed, the thermal model of compressor is based on hypothesis like the ambient temperature of the compressor room, which can change according to thermal mass on the ambience room. That why, the housing temperature of compressor simulation model present 6 C of different with the opening configuration in spite of 2% of injection. After the simulation result, laboratory test will be presented at the following part of the paper.

2228 Page 7 3. VALIDATION BY LABORATORY TEST The validation of thermal behavior on compressor according to the quantity mass flow injection defined from simulation model is done by the laboratory tests on the condensing unit application. The test is useful to validate the injection with capillary tube. Indeed, knowing that the liquid phase of refrigerant is bad for piston technology, but more benefit than gas injection, we decided to test the injection of two phase of the refrigerant. The goal of refrigerant injection is to increase the density in order to improve the thermal behavior. Therefore, in this case of study, the injection can be applied only for LBP application owing to lower density and higher temperature. 3.1 Tests results and platform definition The injection is done thanks to the mass flow on the refrigerant circuit, in other word there is no adding flow on the circuit. That why, it is not possible to extract more than 3 or 4% of the mass flow in order to not damage the cooling capacity on the refrigerant circuit. In order to not damage the compressor, the tests start not by a capillary tube but by a valve system linking the outlet of condenser to the inlet of compressor. Thus, the valve opening can be use to define the characteristic of capillary tube. Indeed, it is necessary to validate the 2% of mass flow injection extract by the simulation before using capillary tube defines by simulation results. The definition of capillary is done according to the singularity pressure losses by the valve system and the linear pressure losses according to the following equation: 1 2 Psin gularity = ζ ρ v 2 2 1 l v Plinearity = λ 2 d if consider same velocity : l capilarity ζ = ρ d λ ( 3) ( 4) ( 5) cooling capacity Discharge temperature Cooling capacity ( W) 5000.00 4500.00 4000.00 3500.00 3000.00 2500.00 2000.00 1500.00 1000.00 500.00 0.00-40.00-35.00-30.00-25.00-20.00-15.00-10.00-5.00 0.00 evaporating temperature ( C) Qpf_closing configuration Qpf_closing configuration + injcetion Qpf _ opening configuration Discharge temperature 150.00 145.00 140.00 135.00 130.00 125.00 120.00 115.00 110.00-45.00-40.00-35.00-30.00-25.00-20.00-15.00-10.00-5.00 0.00 evaporating temperature ( C) Qpf_closing configuration Qpf_closing configuration + injection Qpf_ opening configuration Plot 9: Cooling capacity and discharge temperature evolution The test is done for all LBP evaporating temperature range from -35 C to -5 C. The opening valve has been adjusted one time, then it was replacing by the capillary tube corresponding of the equivalent of the singularity pressure losses. The ratio of cooling capacity between the opening and closing configuration is 1.2% by test.

2228 Page 8 The comparison between test and simulation results is done on the ratio of mass flow injected on the compressor. The test result can conclude the thermal model of compressor which defined 2% of mass flow while the test brings out 1.2%. The others temperatures, like discharge and housing were compared with the simulation results, and as predicted on the simulation results, there is only the housing temperature present differences. 4. CONCLUSIONS Operating compressors at high compression ratios or high ambient temperature can result in excessively high discharge temperature, which can chemically degrade refrigerant oil and lead to mechanical and motor failure. Therefore, employing refrigerant injection is a good option for high pressure ratio compressor, or a high ambient temperature. The goal of the refrigerant injection is to improve the density of refrigerant on the compressor in order to reduce the compressor thermal behavior. Two phase flow injection by capillary tube can be possible but only on the LBP application owing to the low mass flow. Indeed for higher mass flow, it will be necessary to have a controller to inject the just necessity to refresh in order to not damage the capacity. NOMENCLATURE K heat coefficient (W.m -2.K) P Pressure losses (MPa) S total surface of exchange (m 2 ) d diameter (m) e distance (m) ς coefficient of pressure losses (-) θ heat flux (W) λ coefficient of pressure losses (-) ρ density (kg/m3) v velocity (m/s) l length (m) REFERENCES Fanchon JJ, 2001, Guide de mécanique, Chapitre 36, Statique des fluides, Nathan, Paris :p. 473-503 Meunier. F, Rivet. P, Terrier. MF, 2005, Thermodynamique et transferts thermiques, Chapitre 1,Froid Industriel, Dunod, Paris :p. 3-42.