GAS SUPPLY APPLICATION GUIDE

Similar documents
GAS SUPPLY DESIGN GUIDE

KC Series Gas Components and Supply Design Guide

Installation Instructions

INSTALLATION & OPERATION MANUAL FOR Stockpot Range

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

INSTALLATION, OPERATION, SERVICE & PARTS MANUAL FOR STOCK POT RANGE MODELS VSP100, VSP200 & VSP300

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

Instruction Manual No. 742, 8/98

North American Orifice Metering System

Operating and Maintenance Instructions

/2004 US/CA

SL G3. Warning

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1

Your safety and the safety of others are very important.

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

Standard Gas Countertop Griddle

IPG IGNITION GAS PILOTS BACK-LOADED GAS

Gas Countertop Hot Plates

ACCESSORY KIT INSTALLATION INSTRUCTIONS

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

G96 Series BASOTROL Dual Operator Valve

INSTALLATION INSTRUCTIONS

INSTALLATION GUIDE Gas Rangetops

FLOMIXERS SELECTION DATA ALL GASES

Propane Conversion Kit Instruction

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

ACCESSORY KIT INSTALLATION MANUAL

GAS FRYER Instruction Manual Model #5099NS

Natural Gas to L.P. Gas Conversion Kit

Fire's Edge. Fire Pit or Fire Pit Insert Model 100A-M (Manual Operation) OWNER S MANUAL / OPERATING AND MAINTENANCE INSTRUCTIONS

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

MEGR-1627 Instruction Manual

Propane Conversion Kit Instruction

SPECIFICATIONS ATTENTION

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

Certified LP/Propane Line Pressure Regulator Guidebook

installation instructions

Installation Instructions

Installation Instructions For Propane Gas Conversion (Kit Part No ) This kit is designed for conversion to Propane Gas

ACCESSORY KIT INSTALLATION INSTRUCTIONS

MEGR-1912 Instruction Manual

GM Series Dual-Block Multi-Function Gas Control Valves

GAS VALVE RETROFIT KIT Pull Through Tube Heater Models

BGA158 Series CE Approved Class A Shutoff Gas Valve

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

ACCESSORY KIT INSTALLATION INSTRUCTIONS

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Line Pressure Regulator. Class I or Class II. FRS 7../6 Series

PGM PREPIPED GAS MANIFOLD

Installation Instructions

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

BGA158 Series CE Approved Class B Shutoff Gas Valve

Installation Instructions For Natural Gas Conversion

LINE PRESSURE REGULATOR GUIDEBOOK 7TH EDITION

Required Indoor Draft Hood. Optional Outdoor Vent Cap

Propane Conversion Kit Instructions

Line Pressure Regulators Class I or Class II. FRS 7../6 Series

Propane Conversion Kit Instruction

Operator: Save these instructions for future use!

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

Thank You for Attending Today s Webinar. Today s Featured Speaker

INSTALLATION INSTRUCTIONS

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Types 749B and R130 Changeover Manifolds

Gas Furnaces 95AF2V. Warranty Heat Exchanger - 20 Year Limited Parts - 5 Year Limited

Natural Gas to L.P. Gas Conversion Kit

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

INSTALLATION OPERATION MAINTENANCE

RB1700 Series Regulator Medium Duty Commercial & Industrial Regulator

G92 Series BASOTROL Automatic Pilot Gas Valve

Power Flame Incorporated. Nova Premix. Installation and Operation Manual

1805 Series Relief Valves

553 Series.

Gas Furnaces 95AF. Warranty Heat Exchanger - 20 Year Limited Parts - 5 Year Limited. 95% AFUE 44,000 to 110,000 Btuh Input 2 to 5 Tons Add-On Cooling

Gas Appliance Pressure Regulators and. Line Pressure Regulator. FRS 7../6 Series FRS 5... Series

Power Flame Incorporated. Nova Premix. Installation and Operation Manual

Model 141-A Regulators

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

S300 Series. Valve Link. Features. Fisher Controls

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Residential and Small Commercial

Butterfly Control Valve. DMK/6 Series

VG Series VGG and VGD Gas Valves for use with SKP Electro-hydraulic Actuators

INSTRUCTIONS FOR FM4460N SERIES HIGH PRESSURE, METAL TUBE FLOWMETERS

High-Pressure Boiler Inspection Procedures: A Complete Checklist

GAS DELIVERY PRESSURE AND MEASUREMENT

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

VG Series VGG and VGD Gas Valves for use with SKP Electro-hydraulic Actuators

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

Transcription:

GAS SUPPLY APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers and Water Heaters Pending Water Heaters AM 399W AM 500W AM 750W AM 1000W With Rapid Recovery Option AM 199R AM 250R AM 399R AM 500R AM 750R AM 1000R AM Gas Supply Piping Example Pending 05/15/2015 05/15/2015 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 Page 1 of 8

Table of Contents 1. GENERAL INTRODUCTION... 3 2. GAS TRAIN COMPONENTS... 3 3. GAS PRESSURE REQUIREMENTS... 3 4. GAS PIPING... 4 5. GAS SUPPLY MAIN SIZING... 5 6. GAS HEADER SIZING... 5 Technical Support: (Mon Fri, 8am-5pm EST) 1 (800) 526-0288 DISCLAIMER The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including, but not limited to, implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual, for incidental or consequential damages occurring in connection with the furnishing, performance, or use of these materials. Page 2 of 8 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 05/15/2015

1. GENERAL INTRODUCTION The AERCO AM Series gas fired boilers and water heaters are modulating input boilers that require an adequate volume and pressure of natural or propane gas for proper operation. The gas requirements specified herein must be satisfied to ensure efficient combustion. Designers and installers must adhere to the specifications of AERCO and of the local authorities having jurisdiction. A thorough understanding and knowledge of these guidelines is required for the successful design and installation of AM Series boilers and water heaters. 2. GAS TRAIN COMPONENTS The AM Series unit is a stainless steel modular boiler consisting of individual combustion chambers, each having its own gas train (gas valve, pre-combustion chamber, and burner), blower, check valve, igniter, and flame detector, but connected to a common flue. Each group of these components is referred to as a module. The gas train components have been designed to operate at high combustion and seasonal efficiencies by closely controlling both the volume and air/fuel mixture to the burner. Below are descriptions of each of the gas train components for each module. GAS VALVE An electronic, modulating gas valve with 100% tight shutoff. It controls the amount of gas delivered to the burner. MODULATING PRE-MIX BLOWER A variable speed blower mounted to the combustion chamber, where combustion air and gas mix prior to entering the burner, providing controlled combustion. The outlet of the blower leads to a check valve, which prevents any backflow of combustion gases. LOW NOx BURNER A metal fiber mesh covers a stainless steel burner head on which combustion occurs. The burner operation is stable throughout the entire input range of the boiler. 3. GAS PRESSURE REQUIREMENTS The AERCO AM Series of boilers and water heaters require a stable gas input pressure. The inlet supply to the unit must be at least 3 W.C. when firing at maximum input. Maximum allowable gas pressure is 13 W.C. Static gas pressure (when the unit is not firing) may vary, however actual gas pressure should be measured when the unit is in operation (firing). Measure the gas pressure with a manometer at the port provided in the gas valve. In a multiple boiler installation, gas pressure should initially be set for a single boiler in operation and then remaining boilers should be staged on at full fire to ensure that gas pressures never fall below the minimum allowable pressure of 3 W.C. An external gas pressure regulator is mandatory for the State of Massachusetts, regardless of supply pressure; for all other jurisdictions, a lock-up style regulator is required when supply pressure is greater than 13 W.C. (see Fig. 1). The regulator must be installed with at least 2 feet of pipe between the regulator and the unit gas inlet. The regulator discharge range must able to maintain 3 W.C. Gas regulators are self-contained with tapped diaphragm vent ports allowing the diaphragm to change its position. These vents typically require piping to the outside. Every AM unit requires a manual shutoff valve. CSA requires that no other components can be installed between the boiler and this shutoff valve except for pipe fittings such as a pipe union. If an external regulator is used, an additional isolation/service valve must be installed upstream of the regulator (see Figure 1). Gas piping should contain ground unions for removal of the gas piping to the unit for maintenance or service as required. Gas piping should never obstruct removal of the unit side panels 05/15/2015 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 Page 3 of 8

and should not be supported from the unit itself. Gas piping should be supported properly from the floor or overhead as the installation allows. CAUTION! The unit must be isolated from the system when leak testing the gas piping. Drip legs are typically required at the gas supply of each unit to prevent any dirt, weld slag, or debris from entering the boiler gas train inlet pipe. When multiple units are installed, some utilities and local codes require a full size drip leg on the main gas supply line in addition to the drip leg at each unit. The bottom of the gas drip leg(s) should be removable without disassembling any gas piping. The weight of the gas pipe should not be supported from the bottom of the drip leg. The drip leg(s) should not be used to support any or part of the gas piping. GAS PRESSURE REGULATOR MANUAL GAS SHUT-OFF VALVE GAS SUPPLY LINE: MAINTAIN AT LEAST 3 W.C. NATURAL GAS PRESSURE AT MAXIMUM BTU/HR INPUT DRIP LEG 4. GAS PIPING Figure 1: Single Boiler Gas Pipe Connections All gas piping and components must comply with NFPA local codes, and utility requirement minimums. Only gas approved fittings, valves, and pipe should be utilized. Standard industry practice for gas piping is Schedule 40 iron pipe and fittings. All high and low gas pressure piping systems must comply with local utility and building codes. Assembled piping should be clean of all debris, pipe chips, or foreign material to prevent any from entering the unit s boiler gas train. Piping should be tested as prescribed in NFPA 54. Equipment should be isolated before testing any piping system over the allowable pressure. DO NOT EXCEED 13 W. C. on the inlet side of the unit at any time. Page 4 of 8 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 05/15/2015

5. GAS SUPPLY MAIN SIZING The fuel supplier, or utility, should be consulted to confirm that sufficient volume and normal pressure is provided to the building at the discharge side of the gas meter or supply pipe. For existing installations with gas equipment, gas pressure should be measured with a manometer to ensure sufficient pressure is available. Before sizing gas piping, a survey of all connected gas devices should be made. Gas piping supplying more than one gas device must be able to handle the total connected input within the allowable gas pressure drop. The allowable minimum and maximum gas pressure for each device should be considered. Whenever the minimum and maximum gas pressures vary between devices, gas pressure regulators at each unit should be installed to allow regulation at any individual unit. Gas pressure must never exceed the maximum allowable rating of any connected device. The total length of gas piping as well as fitting pressure drop must be considered when sizing the gas piping. Total equivalent length should be calculated from the meter or source location to the last unit connected. Gas piping Table 1, containing data extracted from NFPA 54, should be used as a minimum guideline. Gas pipe size should be selected on the total equivalent length from the table. The gas volume for cfh flow will be the input divided by the calorific value of the fuel to be supplied. Nominal Iron Pipe Size Table 1: Gas Supply Main Piping Minimum Size Requirements Maximum Capacity of Pipe in Cubic Feet of Gas / Hour (Gas pressure = 0.5 psig or less, pressure drop = 0.5 inches of w. c.) (Natural Gas with Specific Gravity of 0.60) Length of Pipe in Feet 10 20 30 40 60 80 100 1-1/4 1,390 957 768 657 528 452 400 1-1/2 2,090 1,430 1,150 985 791 677 600 2 4, 020 2,760 2,220 1,900 1,520 1,300 1,160 2-1/2 6,400 4,400 3,530 3,020 2,430 2,080 1,840 3 11,300 7,780 6,250 5,350 4,290 3,670 3,260 4 23,100 15,900 12,700 10,900 8,760 7,490 6,640 5 41,800 28,700 23,000 19,700 15,800 13,600 12,000 NOTE For further information refer to the latest edition of the National Fuel Gas Code Handbook, ANSI Z223.1 6. GAS HEADER SIZING Main supply gas pipe sizing should be developed for the total plant. Boiler gas manifold piping should be sized based on the volume requirements and lengths between boilers and the fuel main. Header sizes can be either full size or stepped in size as units are connected. A typical gas piping header diagram for two AERCO AM Series boilers is illustrated in Figure 2. Header should be located above or behind boiler. Gas piping should not be installed directly over top or front of any part of boiler. 05/15/2015 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 Page 5 of 8

MANUAL GAS SHUT-OFF VALVE #2 GAS PRESSURE REGULATOR #2 MANUAL GAS SHUT-OFF VALVE #1 GAS PRESSURE REGULATOR #1 GAS SUPPLY LINE: MAINTAIN AT LEAST 3 W.C. NATURAL GAS PRESSURE AT MAXIMUM BTU/HR INPUT DRIP LEG #1 DRIP LEG #2 Figure 2: Typical Multiple Boiler Gas Manifold Construction Ensure proper clearances for maintenance. Piping should not interfere with the removal of the unit s covers nor impede maintenance. Observe service clearances around the boiler as listed below and as shown in AMR Sales Drawings: TOP of the boiler: 20 (500 mm) FRONT of the boiler: 31.5 (1000 mm) RIGHT side: 4 (100 mm) LEFT side: 4 (100 mm) BACK of the boiler: 20 (500 mm) Page 6 of 8 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 05/15/2015

NOTES: 05/15/2015 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 Page 7 of 8

Change Log: Date Description Changed By 04/08/2014 Rev B: Release Curtis Harvey 05/15/2015 Rev C: Updated to support AM Series Rapid Recovery models Curtis Harvey AERCO International, Inc., 2015 Page 8 of 8 AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288 05/15/2015