LGWP & HC Refrigerants Solubility Tests Performed in Running Scroll Compressor

Similar documents
Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

Development of Large Capacity CO2 Scroll Compressor

Tip Seal Behavior in Scroll Compressors

Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

Test on a Twin-Screw Compressor

Investigation of Suction Process of Scroll Compressors

Ball Beating Lubrication in Refrigetation Compressors

Scroll Compressor Performance With Oil Injection/Separation

Scroll Compressor Operating Envelope Considerations

Application of Computational Fluid Dynamics to Compressor Efficiency Improvement

Self-Adjusting Back Pressure Mechanism for Scroll Compressors

Linear Compressor Discharge Manifold Design For High Thermal Efficiency

Research of Variable Volume and Gas Injection DC Inverter Air Conditioning Compressor

Numerical Simulation for the Internal Flow Analysis of the Linear Compressor with Improved Muffler

CFD Analysis and Experiment Study of the Rotary Two-Stage Inverter Compressor with Vapor Injection

Using PV Diagram Synchronized With the Valve Functioning to Increase the Efficiency on the Reciprocating Hermetic Compressors

Development of a New Mechanism Compressor Named "Helical

Influencing Factors Study of the Variable Speed Scroll Compressor with EVI Technology

Development of a High Pressure, Oil Free, Rolling Piston Compressor

Predicting the Suction Gas Superheating in Reciprocating Compressors

GI ycols. R.H.P. Thomas, R. P. Robinson, R. H. Chen and W-T. Wu. Allied-Signal Corporation Buffalo Research Laboratory Buffalo, New York 14210

Impact Fatigue on Suction Valve Reed: New Experimental Approach

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Noise Characteristics Of A Check Valve Installed In R22 And R410A Scroll Compressors

Updated Performance and Operating Characteristics of a Novel Rotating Spool Compressor

Lubrication of Screw Compressor Bearings in the Presence of Refrigerants

Performance and Operating Characteristics of a Novel Rotating Spool Compressor

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors

The Estimation Of Compressor Performance Using A Theoretical Analysis Of The Gas Flow Through the Muffler Combined With Valve Motion

Correlation Between the Fluid Structure Interaction Method and Experimental Analysis of Bending Stress of a Variable Capacity Compressor Suction Valve

Operation of Compressors Through Use of Load Stands

Minimum Viscosity for Bearing Reliability in R290 Rotary Compressors

Axial and Radial Force Control for CO2 Scroll Expander

Development of R290 Compressor Used for Air Conditioner

Development of High Efficiency Rotary Compressor for Domestic Refrigerator Using HFC-134a

Development of Scroll Compressors for R410A

Efficiency Improvement of Rotary Compressor by Improving the Discharge path through Simulation

Evaluation of a Prototype Rotating Spool Compressor in Liquid Flooded Operation

Modeling and Testing of an Automobile AC Scroll Compressor, Part II: Model Validation

Performance Analysis of a Twin Rotary Compressor

Linear Compressor Suction Valve Optimization

Oil-Refrigerant R134a Mixture Non-Isothermal Two-Phase Flow Through the Radial Clearance of Rolling Piston Compressors

Purdue e-pubs. Purdue University. Stephan Lehr Technische Universitaet Dresden. Follow this and additional works at:

Improvement of the Volumetric and Isentropic Efficiency Due to Modifications of the Suction Chamber

Variable Volume-Ratio and Capacity Control in Twin-Screw Compressors

Testing of Low GWP Replacements for R-410A in Stationary Air Conditioning

Incorporating 3D Suction or Discharge Plenum Geometry into a 1D Compressor Simulation Program to Calculate Compressor Pulsations

Low GWP R-404A Alternatives for Commercial Refrigeration. Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals

System Soft-optimization Tests of Refrigerant R-32 in a 6-ton Rooftop Packaged Air-Conditioner

Pressure Strength Test Requirements for Hermetic Refrigerant Compressor Housings Using Fatigue Analysis

COMMERCIAL REFRIGERATION SYSTEMS WITH CO 2 AS REFRIGERANT

Soft-optimization test of R-410A alternative refrigerant R-32 in a split condensing unit - Phase II

Performance Analysis of Centrifugal Compressor under Multiple Working Conditions Based on Time-weighted Average

PERFORMANCE AND CHARACTERISTICS OF COMPRESSOR/EXPANDER COMBINATION FOR CO 2 CYCLE ABSTRACT

Domain Decomposition Method for 3-Dimensional Simulation of the Piston Cylinder Section of a Hermetic Reciprocating Compressor

Capacity Modulation of Linear Compressor for Household Refrigerator

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory

Design Optimization for the Discharge System of the Rotary Compressor Using Alternative Refrigerant R410a

The Effect of Refrigerant Dissolved in Oil on Journal Bearings Reliability

Foam Flow of Oil-Refrigerant R134A Mixture in a Small Diameter Tube

New Techniques for Recording Data from an Operating Scotch Yoke Mechanism

Performance Measurement of Revolving Vane Compressor

Outgassing and Absorption Rates of Oil/ Refrigerant Mixtures

Hermetic Compressor Manifold Analysis With the Use of the Finite Element Method

THE IMPORTANCE OF SUCTION LINES

Design of a High Efficiency Scroll Wrap Profile for Alternative Refrigerant R410A

Development and Experiences with a Hermetic CO2 Compressor

Pressure Indication of Twin Screw Compressor

Heat Transfer Research on a Special Cryogenic Heat Exchanger-a Neutron Moderator Cell (NMC)

A Twin Screw Combined Compressor And Expander For CO2 Refrigeration Systems

Capacity and pressure similar to R-507. Flooded systems. Low temperature (-46.7 C). R22 replacement as long as the condenser has the right size.

Design and Development of a Variable Rotary Compressor

Characterization and Performance Testing of Two- Stage Reciprocating Compressors using a Hot-Gas Load Stand with Carbon Dioxide

Pressure = 15.2 bar TXV. 10K super heat. Pressure = 1.82 bar. Line temp = 8 C. Line temp = 9 C

Study of PTCR Behavior for Wide Voltage and Ambient Temperature Variations and Optimizing the PTC Start Induction Run Motor & Overload

A High Reliability Study of the Scroll Compressor

Valve Losses in Reciprocating Compressors

Minimum Viscosity for Bearing Reliability in Rotary Compressors

Experiences with Application of a CO2 Reciprocating Piston Compressor for a Heat Pump Water Heater

Vibration Related Testing for Hermetic Compressor Development

Single- or Two-Stage Compression

Blocked Suction Unloading Improves Part Load Efficiency of Semi-Hermetic Reciprocating Compressor

Internal Leakage Effects in Sliding Vane, Rotary Compressors

Multifunctional Screw Compressor Rotors

A Study of Valve Design Procedure in Hermetic Compressor

Small Variable Speed Hermetic Reciprocating Compressors for Domestic Refrigerators

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

Characterizers for control loops

An Investigation of Liquid Injection in Refrigeration Screw Compressors

Real Gas Performance Analysis of a Scroll or Rotary Compressor Using Exergy Techniques

Development Of The Compressor For Miniature Pulse Tube Cryocooler

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Impact of Refrigerant Fluid Properties on the Compressor Selection

Compressors. Basic Classification and design overview

Refrigeration Scroll For Parallel Applications

SELECTION CRITERIA FOR SAFETY VALVE

Purdue e-pubs. Purdue University. Lee G. Tetu Carrier Corporation. Follow this and additional works at:

A Study on Noise Reducion in a Scroll Compressor

CFD Simulation of the Flow Through Reciprocating Compressor Self-Acting Valves

Comparative Analysis of Two Types of Positive Displacement Compressors for Air Conditioning Applications

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 LGWP & HC Refrigerants Solubility Tests Performed in Running Scroll Compressor Pierre Ginies Danfoss Commercial Compressors, France, p.ginies@danfoss.com Guillaume Rebiere Danfoss Commercial Compressors, France, rebiere.guillaume@gmail.com Julie Mandon Danfoss Commercial Compressors, France, julie.mandon@ecam.fr Jean Guillaume Cheurlin Danfoss Commercial Compressors, France, jean-guillaume.cheurlin@insa-lyon.fr Follow this and additional works at: http://docs.lib.purdue.edu/icec Ginies, Pierre; Rebiere, Guillaume; Mandon, Julie; and Cheurlin, Jean Guillaume, "LGWP & HC Refrigerants Solubility Tests Performed in Running Scroll Compressor" (2016). International Compressor Engineering Conference. Paper 2476. http://docs.lib.purdue.edu/icec/2476 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

1436, Page 1 LGWP & HC refrigerant solubility tests performed in running scroll compressor Pierre GINIES *, Guillaume REBIÈRE; Julie MANDON ; Jean Guillaume CHEURLIN Danfoss Commercial Compressors, 01600 Trevoux, France p.ginies@danfoss.com, rebiere.guillaume@gmail.com; julie.mandon@ecam.fr ; jean-guillaume.cheurlin@insa-lyon.fr * Corresponding Author ABSTRACT This paper presents the results of investigations on Low Global Warming Potential refrigerants and R290 solubility with different lubricants. Solubility impacts a lot the final lubricant-refrigerant mixture reaching the bearing lubricant inlet and in the same way can impact compressor reliability on wet vapor flowing back to compressor inlet Experimental data, measured in operating compressors, are compared to static steady state values coming from PVT plots. R407C and R410A, two well-known HFC refrigerants, are added as a reference. This work highlights the differences between dynamic solubility (tests performed in a compressor) and static solubility (from PVT plots). A comparison of the impact on the dynamic solubility has been done when a steering feature is added. This work allows us to define the best compromise between different lubricants in these new applications. 1. INTRODUCTION Recent developments in regulations governing the use of refrigerants with respect to their global environmental impact (2006/842/EC "F-GAS" regulation recently voted in the EU with a new revision coming into force on January 1rst 2015, or 2009/125/EC Eco-design directive about energy performance) imply the introduction of new refrigerants and the adequate lubricant for these new applications. Natural refrigerant R290 and some LGWP refrigerants based on HFO and their blends are part of the solution. For example, R290 has a Global Warming Potential (GWP) equal to 3 which is roughly 500 times lower than R407C and 600 times lower than R410A. As a consequence, tests with R290 and several HFO based mixtures have been performed in running compressor by sampling a small quantity of lubricant/refrigerant mixture from the oil sump. The mixture was sampled at several saturation suction temperatures and superheat conditions. The compressors used were standard scroll compressors. This article presents the results of these tests and compares them with static steady state solubility values from PVT plots, especially at low superheat. 2. STEADY STATE SOLUBILITY Steady state values are provided by PVT plots (also named Daniel plots). They indicate the solubility of the refrigerant in the respective lubricant and the viscosity of the mixture in accordance with temperature and pressure. These plots are useful for the first comparisons of refrigerants and lubricants. However, they are more suitable for heat exchangers than compressors. Actually, the accuracy of data for low superheat conditions is unsatisfactory because of the slope of pressure curves (Figure 1). Furthermore, only a few oil ratio values are given (100%, 90%, 80% and 70% in most of plots, each 10% at best).

1436, Page 2 Figure 1 : R410A PVT plot with ISO 32 POE oil, low superheat highlighted 3. EXPERIMENTAL METHOD 3.1 R290 evaluation Solubility tests must be performed in compressor in order to know the real behavior of lubricant/refrigerant mixtures at low superheat. Furthermore, the PVT plots only provide static steady state values, hence the usefulness of these tests in dynamic conditions corresponding to low super heat conditions. These tests were run in a refrigeration loop which included a scroll compressor. An oil pump is fixed to the lower end of the crankshaft ( Figure 2). Its rotation enables the oil sump lubricant to be stirred. This could homogenize the lubricant/refrigerant mixture and lead to an outgassing process. The compressor used is a standard model. It is equipped with a valve in order to sample a small quantity of lubricant/refrigerant mixture from the oil sump. These samples are made when the system conditions are stable. Then the solubility is obtained by a similar process to the one of oil circulation rate measurement (ASHRAE standard 41.4-1996). The tests were performed at several saturated suction temperatures (from -10 C to +15 C) and superheat conditions (5K, 10K and 20K). This allows us to check the lubricant/refrigerant mixture behavior all over the application range of the compressor. Figure 2 : Type of compressor used for the tests

1436, Page 3 RESULTS AND DISCUSSION Five R290-based couples were tested. Two references with R407C and R410A were added. The Table 1 lists the different couples and the viscosity grade of the lubricants used. Refrigerant Lubricant Grade R407C POE 32 R410A POE 32 R290 Lub1 68 R290 Lub2 46 R290 Lub3 68 R290 Lub4 68 R290 Lub5 68 Table 1 : Lubricant/refrigerant couples studied The Figure 3 presents the static steady state solubility from PVT plots data. SH (K) SST ( C) Figure 3 : Steady state solubility provided by PVT plots at different saturated suction temperatures and superheat conditions We used the oil sump sampling method to compare several lubricants on compressors. The results are shown in Figure 4. We can see 3 different groups of solubility level: Lub 5 ; Lub2 and Lub 1-Lub3-Lub4.

1436, Page 4 Figure 4 : Dynamic solubility measured in running compressor for T sat = 10 C Solubility from PVT plots and tests in running compressor can now be compared in order to notice a potential dynamic effect. This comparison at low superheat for T sat = 10 C is presented by Figure 5. R407C and R410A curves are removed in the following graph. Figure 5 : Comparison of solubility from PVT plots (dotted line) and dynamic solubility tests performed in compressor

1436, Page 5 A5% difference between PVT charts and tests performed in compressor values is noticed. In some case this shows that the refrigerant mass is reduce by 70% to 80%. The real solubility (in running conditions) is lower than the steady state solubility provided by PVT plots. P.J. Rubas and C.W. Bullard (1993) already observed a solubility decrease during the startup of compressor. This solubility difference is also noticeable with both references R407C and R410A (Figure 6). Figure 6 : Comparison of solubility from PVT plots and tests for R407C and R410A with POE oil This decrease in solubility may be caused by the stirring effect in the oil sump produced by the moving parts, including the crankshaft and the oil pump. Said stirring effect leads to the foaming of the lubricant/refrigerant mixture which brings a decrease in solubility. T. Yanagisawa and T. Shimizu (1985) had early noticed that foaming caused by stirring effect in rolling piston type rotary compressor. 3.2 FGAS: new LGWP refrigerant investigation On the work for new LGWP refrigerant applications we use similar evaluation method than the one we did for R290. The idea was to see what the existing similarities could be. Figure 7 shows the results when we compare the Daniel plots solubility data for different POE lubricants with potential replacement LGWP refrigerant candidates versus known applications.

1436, Page 6 Figure 7 : Steady state solubility provided by PVT plots at 10 C saturated suction temperature and at several superheat conditions The potential R404A new refrigerant replacement candidates; solubility % on static (Daniel plot) are on the same level than the R404A and R410A. We can see that the solubility level for R404A and the new refrigerant candidates have a similar percentage value versus SH. We can note that the solubility percentage tends to be higher than the R407C refrigerant solubility in lubricant. Static solubility: POE32/R407C < POE/R449A ~ POE32/R410A ~ POE32b/R448A To have a better vision of the behavior on oil sump we need some experimental tests to know the real values on the oil sump. We perform similar testing process than we carried out for R290 with new LGWP refrigerants comparing the measurements of the refrigerant oil sump solubility % with sampling technique Figure 8 : Dynamic solubility measured in running compressor when the compressor is running with R410A, R407C, R448A and R449A refrigerants

1436, Page 7 Dynamic solubility with HFO mixtures: can be sorted as followed: POE32/R407C ~ POE32/R410A < POE32/R448A < POE32/R449A < PVE68/R448A. We note on this test, that dynamic conditions when using new HFO blends, R448A and R449A, have a higher solubility with the same oil. So, refrigerant concentration on lubricant is higher than what we have with existing R404A refrigerant at the same operating point. 3.2 Evaluation of potential out gassing process on oil sump for reduction of the solubility percentage. The idea was to evaluate the potential lubricant outgassing on the oil sump. Figure 9 : Comparison of solubility % for Daniel plot, and dynamic measurement for: design 1; design 2 & reference On Figure 9 we compare the Daniel plot versus sampling measurement on reference compressor and sampling measurement with two oil sump designs to see the changes in steering effect. The first design has a cage around the oil pump pickup tube. The oil has a slightly lower solubility than in a standard compressor, according to the measures for most of temperatures. On the second design, we add one stirrer feature on the oil pickup tube. With this design, on the presence of the stirrer, the solubility is higher in each point, whatever the temperature. Contrary to our expectations, the stirrer increased oil solubility. This result seems to be linked to the stirring action on the oil sump surface level. However, the oil solubility sampling fitting is placed on the compressor shell at the edge of the housing and is therefore far from the agitation zone. It is possible that the arrangement of the measuring equipment is not adequate with the desired results. For the next degassing tests it would be wise to place the solubility sampling location as close as possible to the oil pumping area.

1436, Page 8 3.3 HC/HFO trends Some of the new LGWP refrigerants are based on HFO. In line with our work done with R290 and some HFO reliability investigations, we want to compare the behavior of HFOs with lubricants in oil sump and compare it to the data measured with R290. Figure 10 : Solubility % comparison on dynamic oil sump conditions The results on Figure 10 show that the HFO evaluated behave not that far from R290 on the selected lubricants. This helps us to build up the compressor lubricant selection and qualification program. 4. CONCLUSIONS R290 solubility tests in running compressor have given lower values than PVT plots. The difference between dynamic and static values reaches 5 to 10 percent of refrigerants in mass of lubricant. This small value brings significant differences. It could be caused by the stirring of the refrigerant/lubricant mixture. Other tests are scheduled in order to study this effect by implementing a stirrer in the oil sump. The concept of outgassing by steering effect process seems to be promising but the real measurement of lubricant solubility % is not so easy to carry out within the area of the oil pickup tube inlet without disturbing its efficiency. The solubility test developed for R290 was used on new LGWP refrigerants evaluation and helps to compare properties and this was confirmed during reliability testing. This measurement principle gives a better knowledge on what happens inside the compressor oil sump. This work will help on the lubricant candidate selection process for compressor on reliability evaluation.

1436, Page 9 NOMENCLATURE HFC hydrofluorocarbon GWP global warming potential POE polyol ester lubricant T temperature AKB alkylbenzene lubricant PAG polyalkylene glycol lubricant HFO Hydro Fluoro Olefin SST saturated suction temperature ( C) SH super heat (K) SDT saturated discharge temperature ( C) Daniel plot or PVT pressure temperature viscosity data Subscripts Oil lubricant Lub lubricant Sat saturation R refrigerant REFERENCES - ANSI/ASHRAE Standard 41.4-1996 (RA 2006) - Method for Measurement of Proportion of Lubricant in Liquid Refrigerant - Ginies P., Dewitte P., Terrier M.F., Charni M. (2014) - Review of Hydrocarbon Lubricants Behavior, 2700. Proceedings of the 15th International Refrigeration and Air Conditioning Conference at Purdue - Rubas P.J., Bullard C.W. (1993) - Assessment of Factors Contributing to Refrigerator Cycling Losses,, Air Conditioning and Refrigeration Center, University of Illinois at Urbana-Champaign ACRC TR-45 July 1993 - Yanagisawa T., Shimizu T. (1985) - Foaming of refrigerating oil in a rolling piston type rotary compressor, Shizuoka University Rev. Int. Froid 1986 Vol 9 Janvier, 17-20 AKNOWLEDGEMENTS It would not have been possible to lead this study without the contribution of ATEX lab technicians and manager. In addition I enjoyed a very nice co-authors team work with a trainee engineers. The work on HC refrigerant is issue from the R&D activities work during the Next Generation of Heat Pumps working with Natural fluids EU project. This project has received funding from the European Union s Seventh Program for research, technological development and demonstration under grant agreement No [307169].